Air System Sizing Summary for 000 1PAV Esp Arquibancada

Transcrição

Air System Sizing Summary for 000 1PAV Esp Arquibancada
Air System Sizing Summary for 000 1PAV Esp Arquibancada
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ......... 000 1PAV Esp Arquibancada
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 327,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 90,1
Sensible coil load .................................................. 57,1
Coil L/s at Jan 1600 ............................................. 3489
Max block L/s ...................................................... 3489
Sum of peak zone L/s .......................................... 3489
Sensible heat ratio .............................................. 0,633
m²/kW .................................................................... 3,6
W/m² .................................................................. 275,5
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 25,6 / 19,3
Leaving DB / WB ........................................... 11,9 / 11,4
Coil ADP .................................................................. 10,4
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 56
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 3489 L/s
Standard L/s ........................................................ 3452 L/s
Actual max L/(s-m²) ............................................ 10,67 L/(s-m²)
Fan motor BHP ........................................................ 4,89 BHP
Fan motor kW .......................................................... 3,88 kW
Fan static .................................................................. 600 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................ 2070 L/s
L/(s-m²) ................................................................. 6,33 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 1 of 25
Air System Sizing Summary for 000 1PAV Esp Plenario
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .................. 000 1PAV Esp Plenario
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 230,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 65,5
Sensible coil load .................................................. 39,1
Coil L/s at Jan 1500 ............................................. 2253
Max block L/s ...................................................... 2253
Sum of peak zone L/s .......................................... 2253
Sensible heat ratio .............................................. 0,596
m²/kW .................................................................... 3,5
W/m² .................................................................. 285,0
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1500
OA DB / WB ................................................... 35,5 / 25,7
Entering DB / WB ........................................... 26,5 / 20,2
Leaving DB / WB ........................................... 12,0 / 11,5
Coil ADP .................................................................. 10,4
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 59
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 2253 L/s
Standard L/s ........................................................ 2229 L/s
Actual max L/(s-m²) .............................................. 9,79 L/(s-m²)
Fan motor BHP ........................................................ 3,16 BHP
Fan motor kW .......................................................... 2,50 kW
Fan static .................................................................. 600 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................ 1725 L/s
L/(s-m²) ................................................................. 7,50 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 2 of 25
Air System Sizing Summary for 1PAV Atendimento
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ......................... 1PAV Atendimento
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 25,3 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 2,7
Sensible coil load ................................................... 1,8
Coil L/s at Jan 1600 .............................................. 113
Max block L/s ....................................................... 113
Sum of peak zone L/s ........................................... 113
Sensible heat ratio .............................................. 0,665
m²/kW .................................................................... 9,3
W/m² .................................................................. 108,1
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 26,5 / 19,7
Leaving DB / WB ........................................... 13,0 / 12,5
Coil ADP .................................................................. 11,5
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 113 L/s
Standard L/s ......................................................... 112 L/s
Actual max L/(s-m²) .............................................. 4,46 L/(s-m²)
Fan motor BHP ........................................................ 0,01 BHP
Fan motor kW .......................................................... 0,01 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 30 L/s
L/(s-m²) ................................................................. 1,19 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 3 of 25
Air System Sizing Summary for 1PAV Cerimonial
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ............................ 1PAV Cerimonial
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 110,1 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 20,8
Sensible coil load .................................................. 14,2
Coil L/s at Dec 1400 ............................................. 916
Max block L/s ....................................................... 916
Sum of peak zone L/s ........................................... 916
Sensible heat ratio .............................................. 0,684
m²/kW .................................................................... 5,3
W/m² .................................................................. 189,1
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1400
OA DB / WB ................................................... 34,6 / 25,6
Entering DB / WB ........................................... 25,8 / 19,0
Leaving DB / WB ........................................... 12,8 / 12,2
Coil ADP .................................................................. 11,3
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 916 L/s
Standard L/s ......................................................... 907 L/s
Actual max L/(s-m²) .............................................. 8,32 L/(s-m²)
Fan motor BHP ........................................................ 0,11 BHP
Fan motor kW .......................................................... 0,08 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................. 203 L/s
L/(s-m²) ................................................................. 1,84 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 4 of 25
Air System Sizing Summary for 1PAV ChefeDepartamento1
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ........... 1PAV ChefeDepartamento1
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 17,3 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 3,8
Sensible coil load ................................................... 3,0
Coil L/s at Feb 1700 ............................................. 223
Max block L/s ....................................................... 223
Sum of peak zone L/s ........................................... 223
Sensible heat ratio .............................................. 0,806
m²/kW .................................................................... 4,6
W/m² .................................................................. 217,2
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Feb 1700
OA DB / WB ................................................... 34,5 / 25,5
Entering DB / WB ........................................... 24,5 / 17,7
Leaving DB / WB ........................................... 13,2 / 12,5
Coil ADP .................................................................. 11,9
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 223 L/s
Standard L/s ......................................................... 221 L/s
Actual max L/(s-m²) ............................................ 12,89 L/(s-m²)
Fan motor BHP ........................................................ 0,03 BHP
Fan motor kW .......................................................... 0,02 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 23 L/s
L/(s-m²) ................................................................. 1,30 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 5 of 25
Air System Sizing Summary for 1PAV ChefeDepartamento2
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ........... 1PAV ChefeDepartamento2
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 17,9 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 4,5
Sensible coil load ................................................... 3,8
Coil L/s at Feb 1600 ............................................. 282
Max block L/s ....................................................... 282
Sum of peak zone L/s ........................................... 282
Sensible heat ratio .............................................. 0,836
m²/kW .................................................................... 3,9
W/m² .................................................................. 253,2
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Feb 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 24,2 / 17,3
Leaving DB / WB ........................................... 12,9 / 12,3
Coil ADP .................................................................. 11,7
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 282 L/s
Standard L/s ......................................................... 279 L/s
Actual max L/(s-m²) ............................................ 15,76 L/(s-m²)
Fan motor BHP ........................................................ 0,03 BHP
Fan motor kW .......................................................... 0,03 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 23 L/s
L/(s-m²) ................................................................. 1,26 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 6 of 25
Air System Sizing Summary for 1PAV Circulacao4a
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ........................ 1PAV Circulacao4a
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 194,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 21,3
Sensible coil load .................................................. 15,5
Coil L/s at Feb 1700 ............................................ 1091
Max block L/s ...................................................... 1091
Sum of peak zone L/s .......................................... 1091
Sensible heat ratio .............................................. 0,729
m²/kW .................................................................... 9,1
W/m² .................................................................. 109,6
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Feb 1700
OA DB / WB ................................................... 34,5 / 25,5
Entering DB / WB ........................................... 24,8 / 18,3
Leaving DB / WB ........................................... 12,9 / 12,3
Coil ADP .................................................................. 11,6
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 1091 L/s
Standard L/s ........................................................ 1080 L/s
Actual max L/(s-m²) .............................................. 5,62 L/(s-m²)
Fan motor BHP ........................................................ 0,13 BHP
Fan motor kW .......................................................... 0,10 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................. 147 L/s
L/(s-m²) ................................................................. 0,76 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 7 of 25
Air System Sizing Summary for 1PAV Circulacao5
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .......................... 1PAV Circulacao5
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 12,8 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 1,2
Sensible coil load ................................................... 0,8
Coil L/s at Dec 1400 ............................................... 55
Max block L/s ......................................................... 55
Sum of peak zone L/s ............................................. 55
Sensible heat ratio .............................................. 0,683
m²/kW ................................................................... 10,6
W/m² .................................................................... 94,3
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1400
OA DB / WB ................................................... 34,6 / 25,6
Entering DB / WB ........................................... 25,3 / 18,8
Leaving DB / WB ........................................... 12,7 / 12,2
Coil ADP .................................................................. 11,3
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ........................................................ 55 L/s
Standard L/s ........................................................... 54 L/s
Actual max L/(s-m²) .............................................. 4,28 L/(s-m²)
Fan motor BHP ........................................................ 0,01 BHP
Fan motor kW .......................................................... 0,01 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 10 L/s
L/(s-m²) ................................................................. 0,76 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 8 of 25
Air System Sizing Summary for 1PAV Circulacao6
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .......................... 1PAV Circulacao6
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 12,8 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 1,5
Sensible coil load ................................................... 1,0
Coil L/s at Jan 1400 ................................................ 55
Max block L/s ......................................................... 55
Sum of peak zone L/s ............................................. 55
Sensible heat ratio .............................................. 0,626
m²/kW .................................................................... 8,3
W/m² .................................................................. 120,4
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1400
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 27,5 / 20,4
Leaving DB / WB ........................................... 12,7 / 12,2
Coil ADP .................................................................. 11,1
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ........................................................ 55 L/s
Standard L/s ........................................................... 54 L/s
Actual max L/(s-m²) .............................................. 4,28 L/(s-m²)
Fan motor BHP ........................................................ 0,01 BHP
Fan motor kW .......................................................... 0,01 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 19 L/s
L/(s-m²) ................................................................. 1,50 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 9 of 25
Air System Sizing Summary for 1PAV Circulacao7
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .......................... 1PAV Circulacao7
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 118,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 17,3
Sensible coil load .................................................. 13,7
Coil L/s at Dec 1500 ............................................ 1029
Max block L/s ...................................................... 1029
Sum of peak zone L/s .......................................... 1029
Sensible heat ratio .............................................. 0,792
m²/kW .................................................................... 6,8
W/m² .................................................................. 146,7
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1500
OA DB / WB ................................................... 34,9 / 25,7
Entering DB / WB ........................................... 24,3 / 17,8
Leaving DB / WB ........................................... 13,2 / 12,6
Coil ADP .................................................................. 11,9
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 1029 L/s
Standard L/s ........................................................ 1018 L/s
Actual max L/(s-m²) .............................................. 8,72 L/(s-m²)
Fan motor BHP ........................................................ 0,12 BHP
Fan motor kW .......................................................... 0,10 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 90 L/s
L/(s-m²) ................................................................. 0,76 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 10 of 25
Air System Sizing Summary for 1PAV Circulacao8
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .......................... 1PAV Circulacao8
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 254,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 33,1
Sensible coil load .................................................. 25,5
Coil L/s at Jan 1600 ............................................. 1858
Max block L/s ...................................................... 1858
Sum of peak zone L/s .......................................... 1858
Sensible heat ratio .............................................. 0,770
m²/kW .................................................................... 7,7
W/m² .................................................................. 130,3
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 24,6 / 18,0
Leaving DB / WB ........................................... 13,1 / 12,5
Coil ADP .................................................................. 11,8
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 53
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 1858 L/s
Standard L/s ........................................................ 1839 L/s
Actual max L/(s-m²) .............................................. 7,31 L/(s-m²)
Fan motor BHP ........................................................ 0,22 BHP
Fan motor kW .......................................................... 0,17 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................. 193 L/s
L/(s-m²) ................................................................. 0,76 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 11 of 25
Air System Sizing Summary for 1PÀV Copa
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ..................................... 1PÀV Copa
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 19,5 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 6,6
Sensible coil load ................................................... 5,7
Coil L/s at Dec 1500 ............................................. 430
Max block L/s ....................................................... 430
Sum of peak zone L/s ........................................... 430
Sensible heat ratio .............................................. 0,855
m²/kW .................................................................... 3,0
W/m² .................................................................. 338,9
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1500
OA DB / WB ................................................... 34,9 / 25,7
Entering DB / WB ........................................... 24,1 / 17,3
Leaving DB / WB ........................................... 13,1 / 12,5
Coil ADP .................................................................. 11,9
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 430 L/s
Standard L/s ......................................................... 425 L/s
Actual max L/(s-m²) ............................................ 22,04 L/(s-m²)
Fan motor BHP ........................................................ 0,05 BHP
Fan motor kW .......................................................... 0,04 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 30 L/s
L/(s-m²) ................................................................. 1,54 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 12 of 25
Air System Sizing Summary for 1PAV DivisaoComunicacaoEx
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ...... 1PAV DivisaoComunicacaoEx
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 52,3 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 5,6
Sensible coil load ................................................... 4,9
Coil L/s at Jan 1600 .............................................. 372
Max block L/s ....................................................... 372
Sum of peak zone L/s ........................................... 372
Sensible heat ratio .............................................. 0,867
m²/kW .................................................................... 9,3
W/m² .................................................................. 107,3
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 24,0 / 17,1
Leaving DB / WB ........................................... 13,0 / 12,4
Coil ADP .................................................................. 11,8
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 372 L/s
Standard L/s ......................................................... 368 L/s
Actual max L/(s-m²) .............................................. 7,11 L/(s-m²)
Fan motor BHP ........................................................ 0,04 BHP
Fan motor kW .......................................................... 0,03 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 23 L/s
L/(s-m²) ................................................................. 0,43 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 13 of 25
Air System Sizing Summary for 1PAV Plenario_Arquibancada
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ....... 1PAV Plenario_Arquibancada
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 557,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ..................................................... 156,7
Sensible coil load .................................................. 96,6
Coil L/s at Jan 1600 ............................................. 5741
Max block L/s ...................................................... 5741
Sum of peak zone L/s .......................................... 5741
Sensible heat ratio .............................................. 0,617
m²/kW .................................................................... 3,6
W/m² .................................................................. 281,3
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 25,8 / 19,5
Leaving DB / WB ........................................... 11,7 / 11,3
Coil ADP .................................................................. 10,2
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 57
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 5741 L/s
Standard L/s ........................................................ 5681 L/s
Actual max L/(s-m²) ............................................ 10,31 L/(s-m²)
Fan motor BHP ........................................................ 8,04 BHP
Fan motor kW .......................................................... 6,38 kW
Fan static .................................................................. 600 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................ 3795 L/s
L/(s-m²) ................................................................. 6,81 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 14 of 25
Air System Sizing Summary for 1PAV Preparo
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ................................. 1PAV Preparo
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 16,0 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 8,3
Sensible coil load ................................................... 7,7
Coil L/s at Dec 1700 ............................................. 884
Max block L/s ....................................................... 884
Sum of peak zone L/s ........................................... 884
Sensible heat ratio .............................................. 0,926
m²/kW .................................................................... 1,9
W/m² .................................................................. 520,7
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1700
OA DB / WB ................................................... 33,9 / 25,4
Entering DB / WB ........................................... 23,6 / 18,5
Leaving DB / WB ........................................... 16,3 / 15,8
Coil ADP .................................................................. 15,4
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 62
Design supply temp. ................................................ 16,0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 884 L/s
Standard L/s ......................................................... 874 L/s
Actual max L/(s-m²) ............................................ 55,22 L/(s-m²)
Fan motor BHP ........................................................ 0,10 BHP
Fan motor kW .......................................................... 0,08 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 23 L/s
L/(s-m²) ................................................................. 1,43 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 15 of 25
Air System Sizing Summary for 1PAV Public Anais
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ......................... 1PAV Public Anais
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 59,8 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 10,0
Sensible coil load ................................................... 8,1
Coil L/s at Mar 1600 ............................................. 610
Max block L/s ....................................................... 610
Sum of peak zone L/s ........................................... 610
Sensible heat ratio .............................................. 0,814
m²/kW .................................................................... 6,0
W/m² .................................................................. 166,8
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Mar 1600
OA DB / WB ................................................... 34,1 / 25,1
Entering DB / WB ........................................... 24,4 / 17,7
Leaving DB / WB ........................................... 13,3 / 12,6
Coil ADP .................................................................. 12,0
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 51
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 610 L/s
Standard L/s ......................................................... 604 L/s
Actual max L/(s-m²) ............................................ 10,20 L/(s-m²)
Fan motor BHP ........................................................ 0,07 BHP
Fan motor kW .......................................................... 0,06 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 60 L/s
L/(s-m²) ................................................................. 1,00 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 16 of 25
Air System Sizing Summary for 1PAV Recepcao1
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ............................ 1PAV Recepcao1
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 13,9 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 3,8
Sensible coil load ................................................... 2,1
Coil L/s at Jan 1400 .............................................. 102
Max block L/s ....................................................... 102
Sum of peak zone L/s ........................................... 102
Sensible heat ratio .............................................. 0,560
m²/kW .................................................................... 3,7
W/m² .................................................................. 270,6
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1400
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 30,4 / 22,8
Leaving DB / WB ........................................... 13,0 / 12,5
Coil ADP .................................................................. 11,1
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 60
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 102 L/s
Standard L/s ......................................................... 101 L/s
Actual max L/(s-m²) .............................................. 7,32 L/(s-m²)
Fan motor BHP ........................................................ 0,01 BHP
Fan motor kW .......................................................... 0,01 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 60 L/s
L/(s-m²) ................................................................. 4,32 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 17 of 25
Air System Sizing Summary for 1PAV Recepcao2
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ............................ 1PAV Recepcao2
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 15,6 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 3,9
Sensible coil load ................................................... 3,4
Coil L/s at Apr 1700 .............................................. 270
Max block L/s ....................................................... 270
Sum of peak zone L/s ........................................... 270
Sensible heat ratio .............................................. 0,888
m²/kW .................................................................... 4,0
W/m² .................................................................. 247,9
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Apr 1700
OA DB / WB ................................................... 32,2 / 24,3
Entering DB / WB ........................................... 23,9 / 17,0
Leaving DB / WB ........................................... 13,2 / 12,6
Coil ADP .................................................................. 12,0
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 270 L/s
Standard L/s ......................................................... 268 L/s
Actual max L/(s-m²) ............................................ 17,33 L/(s-m²)
Fan motor BHP ........................................................ 0,03 BHP
Fan motor kW .......................................................... 0,03 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 15 L/s
L/(s-m²) ................................................................. 0,96 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 18 of 25
Air System Sizing Summary for 1PAV RecepcaoCerimonial
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ........... 1PAV RecepcaoCerimonial
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 15,6 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 3,9
Sensible coil load ................................................... 3,4
Coil L/s at Apr 1700 .............................................. 270
Max block L/s ....................................................... 270
Sum of peak zone L/s ........................................... 270
Sensible heat ratio .............................................. 0,888
m²/kW .................................................................... 4,0
W/m² .................................................................. 247,9
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Apr 1700
OA DB / WB ................................................... 32,2 / 24,3
Entering DB / WB ........................................... 23,9 / 17,0
Leaving DB / WB ........................................... 13,2 / 12,6
Coil ADP .................................................................. 12,0
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 270 L/s
Standard L/s ......................................................... 268 L/s
Actual max L/(s-m²) ............................................ 17,33 L/(s-m²)
Fan motor BHP ........................................................ 0,03 BHP
Fan motor kW .......................................................... 0,03 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 15 L/s
L/(s-m²) ................................................................. 0,96 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 19 of 25
Air System Sizing Summary for 1PAV Restaurante
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .......................... 1PAV Restaurante
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 392,4 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 85,6
Sensible coil load .................................................. 57,4
Coil L/s at Dec 1600 ............................................ 3698
Max block L/s ...................................................... 3698
Sum of peak zone L/s .......................................... 3698
Sensible heat ratio .............................................. 0,671
m²/kW .................................................................... 4,6
W/m² .................................................................. 218,2
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1600
OA DB / WB ................................................... 34,6 / 25,6
Entering DB / WB ........................................... 26,1 / 19,4
Leaving DB / WB ........................................... 13,1 / 12,5
Coil ADP .................................................................. 11,6
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 54
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 3698 L/s
Standard L/s ........................................................ 3660 L/s
Actual max L/(s-m²) .............................................. 9,42 L/(s-m²)
Fan motor BHP ........................................................ 0,43 BHP
Fan motor kW .......................................................... 0,34 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................. 897 L/s
L/(s-m²) ................................................................. 2,29 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 20 of 25
Air System Sizing Summary for 1PAV Sala Tecnica
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ......................... 1PAV Sala Tecnica
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 12,2 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 9,5
Sensible coil load ................................................... 6,9
Coil L/s at Dec 1400 ............................................. 551
Max block L/s ....................................................... 551
Sum of peak zone L/s ........................................... 551
Sensible heat ratio .............................................. 0,727
m²/kW .................................................................... 1,3
W/m² .................................................................. 780,8
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1400
OA DB / WB ................................................... 34,6 / 25,6
Entering DB / WB ........................................... 23,6 / 17,8
Leaving DB / WB ........................................... 13,0 / 12,5
Coil ADP .................................................................. 11,9
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 58
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 551 L/s
Standard L/s ......................................................... 545 L/s
Actual max L/(s-m²) ............................................ 45,15 L/(s-m²)
Fan motor BHP ........................................................ 0,06 BHP
Fan motor kW .......................................................... 0,05 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 14 L/s
L/(s-m²) ................................................................. 1,12 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 6,85 L/s/person
Page 21 of 25
Air System Sizing Summary for 1PAV SecretarioDepart
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name .................. 1PAV SecretarioDepart
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 25,9 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 4,3
Sensible coil load ................................................... 2,7
Coil L/s at Jan 1500 .............................................. 156
Max block L/s ....................................................... 156
Sum of peak zone L/s ........................................... 156
Sensible heat ratio .............................................. 0,621
m²/kW .................................................................... 6,0
W/m² .................................................................. 166,3
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1500
OA DB / WB ................................................... 35,5 / 25,7
Entering DB / WB ........................................... 27,4 / 20,6
Leaving DB / WB ........................................... 13,1 / 12,5
Coil ADP .................................................................. 11,5
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 56
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 156 L/s
Standard L/s ......................................................... 154 L/s
Actual max L/(s-m²) .............................................. 6,02 L/(s-m²)
Fan motor BHP ........................................................ 0,02 BHP
Fan motor kW .......................................................... 0,01 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 53 L/s
L/(s-m²) ................................................................. 2,03 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 22 of 25
Air System Sizing Summary for 1PAV SlAutomacao
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ........................ 1PAV SlAutomacao
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 22,9 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 7,4
Sensible coil load ................................................... 6,8
Coil L/s at Dec 1500 ............................................. 547
Max block L/s ....................................................... 547
Sum of peak zone L/s ........................................... 547
Sensible heat ratio .............................................. 0,927
m²/kW .................................................................... 3,1
W/m² .................................................................. 322,0
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1500
OA DB / WB ................................................... 34,9 / 25,7
Entering DB / WB ........................................... 24,0 / 17,0
Leaving DB / WB ........................................... 13,5 / 12,8
Coil ADP .................................................................. 12,3
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0,2
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 547 L/s
Standard L/s ......................................................... 541 L/s
Actual max L/(s-m²) ............................................ 23,87 L/(s-m²)
Fan motor BHP ........................................................ 0,06 BHP
Fan motor kW .......................................................... 0,05 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 12 L/s
L/(s-m²) ................................................................. 0,54 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 23 of 25
Air System Sizing Summary for 1PAV SuperintendenciaRH
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ............ 1PAV SuperintendenciaRH
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 123,3 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 20,7
Sensible coil load .................................................. 15,2
Coil L/s at Jan 1600 ............................................. 1037
Max block L/s ...................................................... 1037
Sum of peak zone L/s .......................................... 1037
Sensible heat ratio .............................................. 0,734
m²/kW .................................................................... 6,0
W/m² .................................................................. 167,9
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Jan 1600
OA DB / WB ................................................... 35,2 / 25,6
Entering DB / WB ........................................... 25,3 / 18,5
Leaving DB / WB ........................................... 13,0 / 12,4
Coil ADP .................................................................. 11,7
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ..................................................... 1037 L/s
Standard L/s ........................................................ 1026 L/s
Actual max L/(s-m²) .............................................. 8,41 L/(s-m²)
Fan motor BHP ........................................................ 0,12 BHP
Fan motor kW .......................................................... 0,10 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................. 173 L/s
L/(s-m²) ................................................................. 1,40 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 7,50 L/s/person
Page 24 of 25
Air System Sizing Summary for 1PAV SuperintendenteRH
Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15
Prepared by: Termacon Projetos e Consultoria Ltda
11/04/2015
01:39
Air System Information
Air System Name ............. 1PAV SuperintendenteRH
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV
Number of zones .......................................................... 1
Floor Area ................................................................ 25,7 m²
Location ........................................... Porto Velho, Brazil
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data ................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ........................................................ 5,7
Sensible coil load ................................................... 4,6
Coil L/s at Dec 1600 ............................................. 349
Max block L/s ....................................................... 349
Sum of peak zone L/s ........................................... 349
Sensible heat ratio .............................................. 0,806
m²/kW .................................................................... 4,5
W/m² .................................................................. 223,1
Water flow @ 5,6 °K rise ....................................... N/A
kW
kW
L/s
L/s
L/s
Load occurs at ................................................. Dec 1600
OA DB / WB ................................................... 34,6 / 25,6
Entering DB / WB ........................................... 24,2 / 17,6
Leaving DB / WB ........................................... 13,2 / 12,6
Coil ADP .................................................................. 12,0
Bypass Factor ........................................................ 0,100
Resulting RH .............................................................. 52
Design supply temp. ................................................ 12,8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0,0
°C
°C
°C
°C
%
°C
OK
°K
Supply Fan Sizing Data
Actual max L/s ...................................................... 349 L/s
Standard L/s ......................................................... 346 L/s
Actual max L/(s-m²) ............................................ 13,60 L/(s-m²)
Fan motor BHP ........................................................ 0,04 BHP
Fan motor kW .......................................................... 0,03 kW
Fan static .................................................................... 50 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................... 27 L/s
L/(s-m²) ................................................................. 1,04 L/(s-m²)
Hourly Analysis Program v4.70
L/s/person ................................................................ 3,80 L/s/person
Page 25 of 25