Frequency converter for centrifugal pumps Operating manual

Transcrição

Frequency converter for centrifugal pumps Operating manual
PED
Frequency converter for centrifugal pumps
Operating manual
Translation of the original
operating manual
J.H. Hoffmann GmbH & Co. KG | Littau 3-5 | DE-35745 Herborn | Telephone: +49 (0) 27 72 / 933-0
Fax: +49 (0) 27 72 / 933-100 | E-mail: [email protected] | www.herborner-pumpen.de
A-PD 04 GB
EC Declaration of Conformity
Herborner Pumpenfabrik
J.H. Hoffmann GmbH & Co. KG
Littau 3-5, DE-35745 Herborn
Ms J. Weygand is authorised to create the technical documentation.
Herborner Pumpenfabrik
J.H. Hoffmann GmbH & Co. KG
J. Weygand
Littau 3-5, DE-35745 Herborn
We hereby declare that the
Frequency converter
PED (Premium Efficiency Drive)
complies with all pertinent provisions of the standards
EN 60204-1 (2007)
EN 61000-3-2 (2006)
EN 61000-6-1 (2007)
EN 61000-6-3 (2007)
The machine also complies with all pertinent provisions of the following EC directives:
- Directive 2004/108/EC, Annexes I and II
- Directive 2006/95/EC
Herborn, 30-04-2013
....................................................................
Signature
(Management)
Original
J.H. Hoffmann GmbH & Co. KG | Littau 3-5 | DE-35745 Herborn | Telephone: +49 (0) 27 72 / 933-0
Fax: +49 (0) 27 72 / 933-100 | E-mail: [email protected] | www.herborner-pumpen.de
Table of contents
1
2
3
4
5
Important information ............................................................................ 6
1.1 Information about documentation.......................................................... 6
1.1.1 Other applicable documents ....................................................... 6
1.1.2 Storing the documentation......................................................... 6
1.1.3 Symbols ............................................................................... 6
1.2 Qualified staff ................................................................................. 7
1.3 CE marking ..................................................................................... 7
1.4 Safety instructions ............................................................................ 7
1.4.1 General information ................................................................ 8
1.4.2 Transport & storage ................................................................. 9
1.4.3 Commissioning ..................................................................... 10
1.4.4 Operation ........................................................................... 11
1.4.5 Maintenance and inspection ..................................................... 12
1.4.6 Repairs .............................................................................. 14
1.4.7 Disassembly & disposal ........................................................... 14
1.5 Proper use ................................................................................... 15
1.6 Responsibility................................................................................ 15
1.7 Contacts for further information ......................................................... 16
Overview of the drive control................................................................. 17
2.1 Model description ........................................................................... 17
2.2 Scope of delivery ........................................................................... 18
2.3 Description of the PED drive control ..................................................... 19
Installation ........................................................................................ 19
3.1 Safety instructions for installation ....................................................... 19
3.2 Installation requirements .................................................................. 20
3.2.1 Suitable ambient conditions ..................................................... 20
3.2.2 Suitable installation location for the motor-integrated drive control...... 21
3.2.3 Basic connection versions ........................................................ 21
3.2.4 Short circuit and ground protection ............................................ 22
3.2.5 Wiring instructions ................................................................ 23
3.2.6 Preventing electromagnetic interferences..................................... 24
3.3 Installing the drive control integrated in the motor ................................... 24
3.3.1 Mechanical installation ........................................................... 24
3.3.2 Power connection ................................................................. 30
3.3.3 Connections for brake resistor .................................................. 33
3.3.4 Control ports ....................................................................... 33
3.3.5 Terminal connection diagram ................................................... 37
3.4 Installing the wall-mounted drive control ............................................... 37
3.4.1 Suitable installation location for wall mounting .............................. 37
3.4.2 Mechanical installation ........................................................... 39
3.4.3 Power connection ................................................................. 43
3.4.4 Brake chopper ..................................................................... 43
3.4.5 Control connections ............................................................... 43
Commissioning ................................................................................... 44
4.1 Safety instructions for commissioning ................................................... 44
4.2 Communication ............................................................................. 45
4.3 Block diagram ............................................................................... 46
4.4 Start-up steps ............................................................................... 47
Parameters ....................................................................................... 48
5.1 Safety instructions for working with parameters ....................................... 48
5.2 General information on parameters ...................................................... 48
5.2.1 Explanation of operating modes................................................. 48
5.2.2 Structure of the parameter tables .............................................. 52
Operating manual PED
3
6
7
8
9
10
4
5.3 Application parameters .................................................................... 53
5.3.1 Basic parameters .................................................................. 53
5.3.2 Preset speed mode ................................................................ 59
5.3.3 Motorised potentiometer ......................................................... 60
5.3.4 PID process controller ............................................................ 61
5.3.5 Analogue inputs.................................................................... 64
5.3.6 Digital inputs ....................................................................... 66
5.3.7 Analogue output ................................................................... 67
5.3.8 Digital outputs ..................................................................... 68
5.3.9 Relay ................................................................................ 69
5.3.10 External fault ...................................................................... 71
5.3.11 Motor current limit ................................................................ 71
5.3.12 Stall detection ..................................................................... 73
5.4 Performance parameters .................................................................. 74
5.4.1 Motor data.......................................................................... 74
5.4.2 I²T ................................................................................... 77
5.4.3 Switching frequency .............................................................. 78
5.4.4 Controller data .................................................................... 78
5.4.5 Quadratic characteristic.......................................................... 81
5.4.6 Synchronous motor controller data ............................................. 81
Error detection and troubleshooting......................................................... 83
6.1 List of the LED flash codes for error recognition ....................................... 83
6.2 List of errors and system errors........................................................... 85
Technical data ................................................................................... 88
7.1 General data ................................................................................ 88
7.1.1 General technical data for 400V devices ....................................... 88
7.1.2 General technical data for 230V devices ....................................... 89
7.2 Derating of output power .................................................................. 90
7.2.1 Derating due to increased ambient temperature ............................. 91
7.2.2 Derating due to installation altitude ........................................... 92
7.2.3 Derating due to clocking frequency............................................. 93
Optional accessories ............................................................................ 94
8.1 Adapter plates .............................................................................. 94
8.1.1 Motor adapter plates ............................................................. 94
8.1.2 Wall adapter plates ............................................................... 97
8.2 MMI manual control unit including a 3 m RJ11 connection cable on an M12 plug . 100
8.3 PC communication cable USB on M12 plug (converter RS485/RS232 integrated) . 100
Guidelines, norms and standards ............................................................101
9.1 EMC limit classes ........................................................................... 101
9.2 Classification acc. to IEC/EN 61800-3 ................................................... 101
9.3 Standards and guidelines ................................................................. 102
9.4 Required markings for UL ................................................................. 102
9.5 Quickstart guide ........................................................................... 104
9.5.1 Quickstart guide for asynchronous motors .................................... 104
9.5.2 Quickstart guide for synchronous motors ..................................... 105
9.6 Parameter settings provided ex works .................................................. 106
List of key words ...............................................................................107
Operating manual PED
Overview of sizes
L
H
B
Dimensional drawings
The drive controls are available in the following performance classes with
the specified size names.
Size
PED
motor integrated
MA
MB
MC
MD
Recommended
motor power [kW]
0.55 / 0.75 /
1.1 / 1.5
2.2 / 3.0 / 4.0
5.5 / 7.5
11.0 / 15.0 /
18.5 / 22.0
Dimensions
[L x W x H] mm
233 x 153 x 120
270 x 189 x 140
307 x 223 x 181
414 x 294 x 232
Sizes
Operating manual PED
5
Important information
1 Important information
This chapter contains important information on safe handling of the
product and on the operating manual.
1.1 Information about documentation
The following information explains how to navigate through the
documentation.
We assume no liability for any damage resulting from the non-observance
of this manual.
Provide the operator of the system with this manual so it is available as
and when required.
1.1.1
Other applicable documents
This refers to all manuals that describe how to operate the drive control
system and any other manuals for the equipment used.
1.1.2
Storing the documentation
Store this manual and all other applicable documents safely so they are
available as and when required.
1.1.3
Symbols
DANGER
Note on safety: Non-observance will result in death or serious injury.
WARNING
Note on safety: Non-observance may result in death or serious injury.
ATTENTION!
Non-observance may result in materials being damaged and may affect the
function of the drive control.
6
Operating manual PED
Important information
Additional information on operating the drive control.
Action: This symbol indicates that you have to perform an action. The
required actions are described step by step.
This symbol indicates the result of an action.
1.2 Qualified staff
In the context of this operating manual and the information relating to
the product itself, qualified staff refers to electronic specialists who are
familiar with the installation, assembly, start-up and operation of the
drive control and the dangers involved, and whose specialist training and
knowledge of relevant standards and regulations provide them with the
necessary abilities.
1.3 CE marking
With the CE marking, we, as the manufacturer of the device, confirm that
the drive control meets the basic requirements of the following
guidelines:
– Directive on Electromagnetic Compatibility (Directive 2004/108/EC of
the Council)
– Low Voltage Directive (Directive 2006/95/EC of the Council)
You can download the declaration of conformity from www.herbornerpumpen.de.
1.4 Safety instructions
The following warnings, precautionary measures and comments are
provided for your safety and serve to prevent damage to the drive control
and the components connected to it. This chapter contains warnings and
information that are generally applicable when handling drive controls.
They are split into general information, transport & storage, start-up,
operation, repairs and dismantling & disposal.
Specific warnings and comments that apply to specific activities can be
found at the start of the appropriate chapters and are repeated and
added to at various critical points in these chapters.
Please read this information carefully as it is provided for your personal
safety and will also prolong the life of the drive control and connected
devices.
Operating manual PED
7
Important information
1.4.1
General information
WARNING
This drive control carries a dangerous voltage and controls revolving
mechanical parts that may be hazardous.
Failure to regard warnings or non-compliance with the information in this
manual may result in death, serious injury or serious damage to property.
Only appropriately trained persons may perform work on this drive
control. These persons must be familiar with all safety instructions and
all measures relating to installation, operation and maintenance that
are contained in this manual. Proper and safe operation of the drive
control requires proper transport, installation, operation and
maintenance.
WARNING
Danger of fire or electric shock.
Improper use, changes and the use of spare parts and accessories not sold
or recommended by the manufacturer of the drive control may result in fire,
electric shock and injury.
The cooling elements in the drive control and motor may reach
temperatures above 70 °C. Ensure sufficient distance from
neighbouring components during installation. Allow sufficient time for
cooling before working on the drive control or motor. If necessary,
protection should be installed against accidental contact.
ATTENTION!
The drive control can only be operated safely if the required environmental
conditions listed in the “Suitable environmental conditions” chapter are met.
ATTENTION!
This operating manual must be kept near the device and available to all
users.
8
Operating manual PED
Important information
ATTENTION!
Please read these safety instructions and warnings before installation and
start-up; this also applies to all warning signs attached to the device. Make
sure that the warning signs are legible and replace missing or damaged
signs.
1.4.2
Transport & storage
ATTENTION!
Risk of damage to the drive control.
If the information is not observed, the drive control could be damaged and
destroyed during subsequent start-up.
Proper and safe operation of the drive control requires proper storage,
set-up and assembly as well as careful operation and maintenance.
The drive control must be protected from mechanical jolts and
vibrations during transport and storage. Protection from impermissible
temperatures (see technical data) must also be guaranteed.
Operating manual PED
9
Important information
1.4.3
Commissioning
WARNING
Danger of injury through electric shock.
Non-observance of warnings may result in serious injury or damage.
Only hard-wired network connections are permitted. The device must
be grounded (DIN EN 61140; VDE 0140-1).
Frequency converters of the PED range may have touch currents of
3.5mA. In accordance with DIN EN 61800-5-1 section 4.3.5.5.2, an
extra protective grounding conductor with the same cross-section as
the original protective grounding conductor must be fitted. A second
protective grounding conductor can be connected under the mains
supply (position marked with a ground symbol) on the outside of the
device. A M6x15 screw (torque: 4.0 Nm) suitable for the connection is
supplied with the adapter plates.
If three-phase frequency inverters are used, it is not permitted to use
standard type A FI protection switches, or RCDs (residual currentoperated protective devices) to protect against direct or indirect
contact. According to DIN VDE 0160, section 5.5.2 and EN 50178,
section 5.2.11.1, the FI protection switch must be universal current
sensitive (RCD type B).
The following terminals may lead to dangerous currents even when the
motor is not running:
– Supply terminals X1: L1, L2, L3
– Motor connection terminals X2: U, V, W
– Connecting terminals X6, X7: Relay contacts for relays 1 and 2
– PTC connection terminals T1/T2
If different voltages are used (e.g. +24 V/230 V), crossing cable runs
are not permitted under any circumstances. The operator must also
ensure compliance with the applicable regulations (e.g. double or
reinforced insulation acc. to DIN EN 61800-5-1).
The drive control contains components susceptible to electrical
discharge. These components may be destroyed through improper
handling; therefore, precautionary measures against electrostatic
charges must be taken when work is performed on these components.
10
Operating manual PED
Important information
1.4.4
Operation
WARNING
Danger of injury due to electric shocks or restarting motors.
Non-observance of warnings may result in serious injury or damage.
Observe the following instructions during operation:
– The drive control runs at high voltages.
– When electrical devices are operated, some of their parts are always
subject to dangerous voltage.
– Emergency stop equipment according to DIN EN 60204-1; VDE 01131:2007-06 must function in all the control device's operating modes.
Resetting the emergency stop equipment may not result in
uncontrolled or undefined restarting.
– In order to ensure safe disconnection from the mains, the mains
cable has to be fully disconnected from the drive control in a
synchronous manner.
– A pause of at least 1 to 2 mins must be observed between
consecutive mains activations for devices with a single-phase feed
and for size D (11 to 22kW).
– Certain parameter settings may result in the drive control restarting
automatically after the supply voltage has failed.
ATTENTION!
Risk of damage to the drive control.
If the information is not observed, the drive control could be damaged and
destroyed during subsequent start-up.
Observe the following instructions during operation:
– The motor parameters, especially the l2T settings, have to be
configured properly to provide proper motor overload protection.
– The drive control has internal motor overload protection. See P0610
(level 3) and P0335. I2T is ON by default. Motor overload protection
can also be ensured via an external PTC.
– The drive control may not be used as “Emergency stop equipment”
(see DIN EN 60204-1; VDE 0113-1:2007-06).
– Drive controls are maintenance-free if operated properly. If the air
contains dust, the cooling fins of the motor and drive control have to
be cleaned regularly.
Operating manual PED
11
Important information
1.4.5
Maintenance and inspection
The drive controls may only be maintained and inspected by electricians
with recognised training. Unless explicitly described in this manual,
changes to hardware and software may only be undertaken by Herborner
pumps experts.
1.4.5.1
Cleaning the drive controls
Drive controls are maintenance-free if operated properly. If the air
contains dust, the cooling fins of the motor and drive control have to be
cleaned regularly. If devices are fitted with integrated fans (optional for
size C, standard for size D), we would recommend cleaning with
compressed air.
1.4.5.2
Measurement of insulation resistance on control part
An insulation test on the control card's input terminals is not permitted.
1.4.5.3
Measurement of insulation resistance on power part
The power part of a PED is tested with 1.9kV in the course of series
testing.
Should the insulation resistance have to be measured during a system
test, this can be done under the following conditions:
12
-
an insulation test can be undertaken for the power part alone,
-
to avoid excessively high voltages, all the PED's connection cables
must be disconnected before testing,
-
a 500V DC insulation tester should be used.
Operating manual PED
Important information
L1 L2
L3
Ground
W
V
U
500V
DC insulation test system
Fig. 1:
1.4.5.4
Insulation test on the power board
Pressure test on a PED
A standard PED must not be pressure-tested.
Operating manual PED
13
Important information
1.4.6
Repairs
ATTENTION!
Risk of damage to the drive control.
If the information is not observed, the drive control could be damaged and
destroyed during subsequent start-up.
Repairs to the drive control may only be performed by the Herborner
Pumps Service department.
WARNING
Danger of injury through electric shock.
Non-observance of warnings may result in serious injury or damage.
When the drive control is disconnected from the mains voltage, live
device parts and connections may not be touched immediately in case
the condensers are still live.
1.4.7
Disassembly & disposal
Screw and snap-on connections are easy to release
and allow the drive control to be dismantled into its
individual parts. These parts can be sorted for
recycling. Please comply with local regulations during
disposal.
Components with electronic parts may not be
disposed of along with normal household waste. They
have to be collected separately with used electrical
and electronic equipment in accordance with
applicable legislation.
14
Operating manual PED
Important information
1.5 Proper use
If the device is installed in a machine, inverters may not be started up
(i.e. intended operation may not begin) until it has been determined that
the machine complies with the regulations of EC Directive 2006/42/EC
(Machinery Directive); DIN EN 60204-1; VDE 0113-1:2007-06 must be
observed.
Start-up (i.e. beginning intended operation) is only permitted if the EMC
Directive (2004/108/EC) is complied with.
The harmonised standards of DIN EN 50178; VDE 0160:1998-04 must be
applied for this drive control along with DIN EN 60439-1; VDE 0660500:2005-01.
This drive control may not be operated in areas where there is a danger
of explosion.
Repairs may only be performed by authorised repair bodies. Independent
and unauthorised intervention may result in death, injury and damage.
The warranty provided by KOSTAL will be invalidated in such cases.
External mechanical loads such as stepping on the housing are not
permitted.
Using drive units in equipment that is not fixed is
considered as an exceptional environmental condition
and is only permitted if allowed by the standards and
guidelines applicable on site.
1.6 Responsibility
As a basic principle, electronic devices are not fail-proof. The operator
and/or the contractor setting up the machine or system is responsible for
ensuring that the drive switches to a safe state if the device fails.
The “Electrical equipment of machines” section in DIN EN 60204-1; VDE
0113-1:2007-06, “Safety of machinery” describes the safety requirements
for electrical control units. These are provided for the safety of people
and machines and must be observed in order to retain the functional
capability of the machine or system.
An emergency stop feature does not have to result in the power supply to
the drive being switched off. To avoid dangerous situations, it may be
useful for individual drives to remain operational or for specific safety
procedures to be initiated. The effectiveness of emergency stop measures
is evaluated by means of a risk assessment for the machine or system and
Operating manual PED
15
Important information
its electrical equipment, and is determined by selecting a circuit category
according to DIN EN 13849 “Safety of machinery – Safety-related parts of
control systems”.
1.7 Contacts for further information
Further information is available from:
www.herborner-pumps.com
16
Operating manual PED
Overview of the drive control
2 Overview of the drive control
This chapter contains information on the scope of delivery for the drive
control and the function description.
2.1 Model description
Fig. 2:
Article description
Key
1 Drive control series: PED
2
3
4
5
6 Housing: G0 – standard (black with
inscription);
Installation location/size: M – integrated in
0 – standard (cooling element);
a motor, size: A, B, C, D
0 – standard (with potentiometer); 00 –
standard screw connections
7 Firmware version: S00 – standard
Input voltage: 2 – 230V 4 – 400 V
8 Versions: 000 – standard; 001 – specific
Recommended motor power: 0.55; 0.75;
9 Equipment generation: 1 – current
1.1; 1.5; 2.2; 3; 4; 5.5; 7.5; 11; 15; 18.5;
version
22 kW
Printed circuit board: L00 – standard
(without brake chopper);
A00 – standard (without TTL evaluation);
– standard (without field bus)
Operating manual PED
17
Overview of the drive control
2.2 Scope of delivery
Compare your product with the scope of delivery provided below.
1
2
3
4
5
6
7
8
Fig. 3:
Scope of delivery
Key
Drive control article number
1 Drive control (variant)
2 Poly bag containing fastening bolts
3 Cable screw connections
4 Operating manual
18
Adapter plate article number
5 Adapter plate with connecting terminal
6 Poly bag containing connecting material
for terminal block
7 Seal (not part of the scope of delivery)
8 Motor (not part of the scope of delivery)
Operating manual PED
Installation
2.3 Description of the PED drive control
The PED drive control is a device for speed control in three-phase AC
motors.
The drive control can be integrated in the motor (with the standard
adapter plate) or fitted close to the motor (with the wall installation
adapter plate).
The permitted ambient temperatures specified in the technical data refer
to operation at nominal load. In many cases, higher temperatures may be
permitted after a detailed technical analysis. These have to be approved
by KOSTAL on a case-by-case basis.
3 Installation
3.1 Safety instructions for installation
WARNING
Installation may only be performed by appropriately qualified
employees who are trained in the set-up, installation, start-up and
operation of the product. Work performed on the drive control by
unqualified staff and non-observance of warnings may result in serious
injury or damage.
The device must be grounded in accordance with DIN EN 61140; VDE
0140, NEC and other relevant standards. Mains connections must be
hardwired.
Operating manual PED
19
Installation
3.2 Installation requirements
3.2.1
Suitable ambient conditions
Altitude of the installation
site:
up to 1000 m above sea level / over 1000 m with reduced
performance (1% per 100 m) (max. 2000 m) (see chapter 7.2)
Ambient temperature:
-25 °C to +50 °C (different ambient temperatures may be
possible in individual cases) (see chapter 7.2)
Relative humidity:
≤ 96%, condensation not permitted
Resistance to vibration and acc. to FN 942 017 part 4; 5.3.3.3 Combined test 2;
shock:
5...200 Hz for sinusoidal oscillation
Electromagnetic
compatibility:
Immune to interference acc. to DIN EN 61800-3
Cooling:
Surface cooling:
sizes A to C: free convection;
size C: with option of integrated fan
size D: with integrated fans
Tab. 1:
Ambient conditions
Ensure that the housing type (protection type) is suitable for the
operating environment:
– Ensure that the seal between the motor and the adapter plate is
inserted correctly.
– All unused cable screw connections must be sealed.
– Check that the cover of the drive control is closed and bolted down
tightly.
Although the drive control can, in principle, be painted later on, the user
must nevertheless check the material compatibility of the intended paint.
Failure to comply with this requirement may eventually result in the loss
of the protection class (particularly in respect to seals and fibre-optic
elements). The standard colour is black (RAL 9005).
Disassembling the circuit boards (even for the purpose of painting the
housing sections) renders the warranty void!
Mounting points and sealing surfaces must be kept free of paint for
purposes of EMC and grounding!
20
Operating manual PED
Installation
3.2.2 Suitable installation location for the motor-integrated drive control
Ensure that the motor with a motor-integrated drive control is only
installed and operated if aligned as shown in the following diagram.
Fig. 4:
Motor installation location/permitted alignments
3.2.3
Basic connection versions
Fig. 5:
Star or triangle connection for drive controls integrated in the motor
Operating manual PED
21
Installation
ATTENTION!
Risk of damage to the drive control.
The correct phase sequence must be observed when the drive control is
connected as the motor could otherwise be overloaded.
Ensure that the phase sequence is correct when connecting the motor.
The supplied assembly material can be used to connect core end sleeves
and cable shoes. Fig. 4 shows the different connection options.
Unused open cable ends in the motor terminal box
must be insulated.
If a PTC or Klixxon is used, the bridging contact fitted
on the connection terminal for the PTC in the delivery
state has to be removed.
The cross-section of the supply line must be designed according to the
transfer category and maximum permitted current. The contractor
starting up the device must ensure protection for the power line.
3.2.4
Short circuit and ground protection
The drive control contains internal short circuit and ground protection.
22
Operating manual PED
Installation
3.2.5
Wiring instructions
The control connections of the application card are located inside the
drive control.
The configuration may vary depending on the version.
Terminals:
Plug terminal clamp with activation
button (slot screwdriver, max. width 2.5
mm)
Connection cross-section:
0.5 to 1.5 mm2, single-wire, AWG 20 to
AWG 14
Connection cross-section:
0.75 to 1.5 mm2, fine-wired, AWG 18 to
AWG 14
Connection cross-section:
0.5 to 1.0 mm2, fine-wired, (core end
sleeves with and without plastic collar)
Length of stripped insulation: 9 to 10 mm
The terminals for the mains cable are located inside the drive control.
The PED also has the option of being equipped with terminals for
connecting a brake resistor.
The configuration may vary depending on the version.
Core end sleeves with plastic collars and lugs are recommended.
Terminals:
Spring force connection
(slot screwdriver, max. width 2.5 mm)
Connection cross-section: 0.2 to 10 mm2, rigid, 0.2 to 6 mm2, flexible
Connection cross-section: 0.25 to 6 mm2
(core end sleeves without plastic collar)
Connection cross-section: 0.25 to 4 mm2
(core end sleeves with plastic collar)
Connection cross-section: 0.25 to 1.5 mm2 for 2 conductors of the same
cross-section
(twin-core end sleeves with plastic collar)
Conductor cross-section: AWG 24 to AWG 8
Length of stripped insulation: 15 mm
Mounting temperature: -5°C to +100°C
Operating manual PED
23
Installation
3.2.6
Preventing electromagnetic interferences
Screened lines should be used for control circuits where possible. The
shielding should be applied to the line end with special care and without
laying the leads across longer stretches without shielding.
Screening for analogue target values should only be applied on one side of
the
drive
control.
In principle, control cables should always be laid as far away from powerconducting lines as possible; separate ducts may have to be used. If lines
do cross, they should do so at an angle of 90°.
Upstream circuit elements, such as protector switches and brake coils, or
circuit elements that are operated via the outputs of the drive control
have to be interference-suppressed. RC circuits are suitable as AC voltage
protector switches, while free-wheeling diodes or varistors are usually
used as DC voltage protector switches. These interference suppression
devices are attached directly to the protector switch coils. The power
supply for a mechanical brake may not be carried in the same cable.
Power connections between the drive control and motor should always be
shielded or reinforced, and the shielding must have large-scale grounding
at both ends. The use of EMC cable screw connections is recommended.
These are not part of the scope of delivery.
Wiring suitable for EMC must be ensured.
3.3 Installing the drive control integrated in the motor
3.3.1
Mechanical installation
3.3.1.1 Mechanical installation of sizes A - C
Proceed as follows when mechanically installing the drive control:
1. Open the standard motor connection box.
2. Disconnect the wires from the connection terminals. Memorise or write
down the connection sequence.
3. Remove the motor terminal block if necessary.
4. Remove the fastening screws of the connection housing and take out
the housing. Make sure that the seal is not damaged.
24
Operating manual PED
Installation
4
1
2
3
2
Fig. 6:
Assembly sequence: Connection box – adapter plate sizes A - C
The standard adapter plate is a plate the underside of
which is not reworked. There are no holes.
You can order individually modified adapter plates
from KOSTAL for selected motors.
5. Modify the adapter plate (1) by producing the necessary holes (2) for
mounting on the motor.
The commissioning technician is responsible for
protection class compliance when sealing the adapter
plate
on
the
motor.
If you have any questions, please ask your KOSTAL
contact.
6. Fit the seal (3).
7. Lead the motor connection line past the connection terminal and
through the adapter plate; attach the adapter plate to the motor with
the four retaining bolts and the four spring elements (4) (torque: 2.0
Nm).
Operating manual PED
25
Installation
When mounting the adapter plates, ensure that all
four screws, including the spring elements, are
tightened to the corresponding torque! All contact
points must be free of dirt/paint because otherwise a
correct protective conductor connection is not
ensured!
8. Attach the motor wires in the correct circuit, see also Fig. 5 (torque:
3.0 Nm). We would recommend using insulated M5 annular cable
sockets with a connection cross-section of 4 to 6 mm2.
When installing the motor wires, ensure that all bolts
on the terminal board are fitted with the nuts
provided even if the star point is not connected!
1
2
Fig. 7:
Bridging contact
9. If a motor PTC/Klixxon is available, wire the connection cables to
terminals T1 and T2 (1) (torque: 0.6 Nm).
During assembly, ensure that the connection cable is
not crushed.
26
Operating manual PED
Installation
If the motor is fitted with a temperature sensor, this
is connected to the T1 and T2 terminals (1) - the
bridging contact (2) inserted for delivery must be
removed for this purpose.
When the bridge is in place, the temperature of the
motor is not monitored!
10. Plug the drive control onto the adapter plate and fasten it evenly
using the four lateral bolts (torque: 4.0 Nm).
3.3.1.2 Mechanical installation of size D
Proceed as follows to mechanically install the drive control:
1. Open the standard motor connection box.
2. Remove the connection housing's retaining bolts and take the housing
off. Be careful not to damage the seal.
Fig. 8:
Assembly sequence: Connection box – adapter plate, size D
Key
1 Adapter plate option (variant)
2 Holes depending on motor
3 Seal
4 Retaining bolts with spring elements
5 O-ring seal
Operating manual PED
6
7
8
9
10
PED/adapter plate support
Junction plate heightening option
Original junction plate (not included)
Extended screw option (for 7)
Retaining bolts with spring elements
option
27
Installation
The standard adapter plate is a plate the underside of
which is not reworked. No holes have been produced
yet.
You can order individually modified adapter plates
from KOSTAL for selected motors.
3. Modify the adapter plate (1) by producing the necessary holes (2) for
mounting on the motor.
The commissioning technician is responsible for
protection class compliance when sealing the adapter
plate
on
the
motor.
If you have any questions, please ask your KOSTAL
contact.
4. Fit the seal (3).
5. Screw the adapter plate on to the motor with the four retaining bolts
and four spring elements (10) (torques: M4 to 2.4 Nm, M5 to 5.0 Nm,
M6 to 8.5 Nm).
When mounting the adapter plates, ensure that all
four screws, including the spring elements, are
tightened to the necessary torque! All contact points
must be free of dirt/paint because otherwise a
correct protective conductor connection is not
ensured!
6. Secure the original junction plate (8), if necessary using the optional
junction plate heightening part (7) and the optional extended screw
(9), back on the motor.
7. Connect four strands (PE, U, V, W) of the corresponding cross-section
(depending on rating of PED used) to the original junction plate.
The connection strands (approx. 30 cm) needed to wire
the motor junction plate/PED are not included in the
scope of supply!
8. Screw the support (6) to the adapter plate with four retaining bolts (4)
and four spring elements (4). Please ensure that the seal (5) sits
28
Operating manual PED
Installation
perfectly. Guide the four strands (PE, U, V, W) through the PED's
support.
9. Attach the drive control to the support (6) and secure it evenly with
two M8 screws (torque: max. 21.0 Nm).
Fig. 9:
Bridging contact
10 If present, wire the connection cable of the motor PTC/Klixxon to the
T1 and T2 terminals (1) (torque: 0.6 Nm).
During assembly, ensure that the connection cable is
not crushed!
If the motor is fitted with a temperature sensor, this
is connected to the T1 and T2 terminals (1) - the
bridging contact (2) inserted for delivery must be
removed
for
this
purpose.
When the bridge is in place, the temperature of the
motor is not monitored!
Operating manual PED
29
Installation
3.3.2
Power connection
3.3.2.1 Power connection for sizes A - C
Fig. 10:
Power connection sizes A - C
Unscrew the four bolts from the housing cover of the drive control and
remove the cover.
Guide the power cable through the cable connection and connect the
phases to contacts L1, N for 230V or L1, L2, L3 for 400V and the ground
cable to the PE contact of the connection terminal. The cable screw
connection provides strain relief, and the PE connection cable must be
connected in a leading fashion (considerably longer).
When connecting a brake resistor to an optional
braking module, cables with shielding and double
insulation must be used.
Terminal
no.
Designation
Assignment
1
L1
Mains phase 1
2
L2
Mains phase 2
3
L3
Mains phase 3
4
PE
Ground cable
Tab. 2:
30
3~ 400V terminal configuration X1
Operating manual PED
Installation
Terminal
no.
Designation
Assignment
1
L1
DC mains (+) (565V)
2
L2
Not assigned
3
L3
DC mains (-)
4
PE
Ground cable
Tab. 3:
DC feed 250 to 750V terminal assignment X1
Terminal
no.
Designation
Assignment
1
L1
Mains phase 1
2
N
Neutral wire
3
PE
Ground cable
4
Tab. 4:
Not used
1~ 230V terminal configuration X1
3.3.2.2 Power connection for size D
Fig. 11:
Power connection for size D
Operating manual PED
31
Installation
Unscrew the four screws from the drive control's housing cover and
take off the cover.
Guide the mains connection cable through the cable screw connection
and connect the phases with the L1, L2, L3 contacts for 400 V and the
ground cable with the PE contact on the connection terminal. The
cable screw connection provides strain relief, and the PE connection
cable must be connected in a leading fashion (considerably longer)!
When connecting a brake resistor to an optional
braking module, cables with shielding and double
insulation must be used!
Terminal
no.
Designation
Assignment
1
L1
Mains phase 1
2
L2
Mains phase 2
3
L3
Mains phase 3
4
PE
Ground cable
Tab. 5:
3~ 400 V terminal assignment X1
Terminal
no.
Designation
Assignment
1
L1
DC mains (+) (565V)
2
L2
Not assigned
3
L3
DC mains (-)
4
PE
Ground cable
Tab. 6:
DC feed 250 to 750 V terminal assignment X1
Terminal
no.
Designation
Assignment
1
PE
Ground cable
2
U
Motor phase 1
3
V
Motor phase 2
4
W
Motor phase 3
Tab. 7:
32
Motor connection assignment X4
Operating manual PED
Installation
3.3.3
Connections for brake resistor
Terminal
no.
Designation
Assignment
1
B+
Connection for brake resistor (+)
2
B–
Connection for brake resistor (-)
Tab. 8:
Optional terminal configuration for brake chopper
3.3.4
Control ports
3.3.4.1
Fig. 12:
Control port of the standard application board
Control port of the standard application board
ATTENTION
Danger of external signals being coupled in.
Use only shielded control lines.
Guide the required control cables into the housing through the cable
screw connections.
Connect the control cables according to the figure and/or table. Use
shielded control cables.
Place the cover on the housing of the drive control and bolt it (torque:
2.0 Nm) tight.
Operating manual PED
33
Installation
Terminal
no.
Designation
Assignment
1
24 V In
Ext. power supply
2
GND (ground)
Ground
3
24 V Out
Int. power supply
4
GND (ground)
Ground
5
24 V Out
Int. power supply
6
Dig. In 1
Target value release
(parameter 1.131)
7
Dig. In 2
Free (not assigned)
8
Dig. In 3
Free (not assigned)
9
Dig. In 4
Error reset
(parameter 1.180)
10
En HW (release)
Enable hardware
11
Dig. Out 1
Fault message
(parameter 4.150)
12
Dig. Out 2
Free (not assigned)
13
A. Out 0 ... 20 mA
Actual frequency
(parameter 4.100)
14
10 V Out
For ext. voltage divider
15
A. Out 0 ... 10 V
Actual frequency
(parameter 4.100)
16
A GND (ground 10 V)
Ground
17
A. In 1
PID feedback (parameter 3.060)
18
A GND (ground 10 V)
Ground
19
A. In 2
Free (not assigned)
20
A GND (ground 10 V)
Ground
Tab. 9:
34
Terminal configuration X5 of the standard application board
Operating manual PED
Installation
Terminal
no.
Designation
Assignment
1
COM
Centre contact relay 1
2
NO
Normally open relay 1
3
NC
Normally closed relay 1
Tab. 10: Terminal configuration X6 (relay 1)
In the factory setting, relay 1 is programmed as “relay
error” (parameter 4.190).
Terminal
no.
Designation
Assignment
1
COM
Centre contact relay 2
2
NO
Normally open relay 2
3
NC
Normally closed relay 2
Tab. 11: Terminal configuration X7 (relay 2)
In the factory setting, “no function” is assigned to
relay 2
(parameter 4.210).
Operating manual PED
35
Installation
3.3.4.2
Fig. 13:
Control port of the basic application board
Control port of the basic application board
Terminal
no.
Designation
Assignment
1
Dig. In 1
Target value release
(parameter 1.131)
2
A. In 1
Free (not assigned)
3
Dig. In 2
Free (not assigned)
4
A GND (ground 10 V)
Ground
5
Dig. Out 1
Fault message
(parameter 4.150)
6
10 V Out
For ext. voltage divider
7
24 V Out
Int. power supply
8
24 V Out
Int. power supply
9
En HW (release)
Enable hardware
10
GND (ground)
Ground
Tab. 12: Terminal configuration X5 of the basic application board
36
Operating manual PED
Installation
3.3.5
Terminal connection diagram
Fig. 14:
Connection diagram
The drive control is ready once a 400 V AC mains supply has been
activated (on terminals L1 to L3) or a 565 V DC mains supply has been
activated (on terminals L1 and L3).
The drive control can also be started up by connecting an external 24 V
voltage.
The presetting required for this is described in the "System parameters"
chapter.
3.4 Installing the wall-mounted drive control
3.4.1
Suitable installation location for wall mounting
Ensure that the installation location for a PED wall mounting meets the
following conditions:
– The drive control has to be mounted on an even and fixed surface.
– The drive control may only be mounted on non-flammable bases.
– There must be a minimum of 20 cm clearance all around the drive
control to ensure free convection.
Operating manual PED
37
Installation
The following figure shows the assembly dimensions and the free spaces
required for installing the drive control.
Fig. 15:
Minimum clearances
For the "wall mounting" version, the line length between the motor and
PED may not exceed 5 m. A shielded cable with the required cross-section
must be used. There must be a PE connection (underneath the wall
mounting's terminal board)!
38
Operating manual PED
Installation
3.4.2
Mechanical installation
Fig. 16:
Wiring on the motor connection box
Open the motor connection box.
ATTENTION
Depending on the required motor voltage, the star or triangle connection
must be made in the motor connection box!
Use a suitable EMC screw connection to attach the shielded cable to
the motor connection box and ensure that the shielding contact is in
order (large surface).
Connecting a PE connection in the motor connection box is mandatory.
Close the motor connection box.
Operating manual PED
39
Installation
Fig. 17:
Fastening the adapter plate to a wall
DANGER!
The drive control may not be installed without an adapter plate!
Find a position that meets the required ambient conditions described
in the "Installation requirements" section.
To achieve optimum self-convection of the drive control, ensure that
the (EMC) screw connection is facing upwards when installing.
If there is no additional ventilation for the PED (optional for size C),
only vertical installation is permitted.
40
Operating manual PED
Installation
Fig. 18:
Wiring
1. Release the screw (1) to remove the contact plate from the adapter
plate. The (M6x15) PE connection (3) is underneath this contact plate.
2. Guide the connection cable from the motor to the adapter plate
through the integrated EMC screw connection.
3. This PE connection (torque: 4.0 Nm) must be made to the same ground
potential of the motor. The cross-section of the equipotential bonding
line must correspond to at least the cross-section of the power cable.
4. Reattach the contact plate using the screw (1).
Operating manual PED
41
Installation
5. Wire the motor cable to contacts U, V, W (and the star point in some
cases) in the connection terminal, as described in the "Basic connection
versions" chapter. Use cable shoes (M5) to do this.
6. Before connecting an existing motor PTC to the T1 and T2 terminals,
remove the pre-assembled short-circuit bridge (2).
The motor PTC is potential-free once the PED is connected, therefore
it
must
be
connected
using
a
separate
motor
lead.
Replace the dummy screw with a suitable standard screw connection
and guide both ends to T1 and T2.
Fig. 19:
Attaching the drive control
7. Position the drive control (1) on the adapter plate (2) so that the collar
of the adapter dips into the opening on the floor of the cooling
element.
8. Fasten the control unit to the adapter plate with the help of the
screws (3) provided (torque: 4.0 Nm).
42
Operating manual PED
Commissioning
3.4.3 Power connection
The power connections should be designed as described in section 3.3.2
ff. "Installing the drive control integrated in the motor".
3.4.4 Brake chopper
The brake connections should be designed as described in section 3.3.3
ff. "Installing the drive control integrated in the motor".
3.4.5 Control connections
The control connections should be designed as described in section 3.3.4
ff. "Installing the drive control integrated in the motor".
Operating manual PED
43
Commissioning
4 Commissioning
4.1 Safety instructions for commissioning
ATTENTION!
Danger of damage
If the information is not observed, the drive control could be damaged and
destroyed during subsequent start-up.
Commissioning may only be performed by qualified staff. Safety
precautions and warnings must always be observed.
WARNING
Danger of injury
Non-observance of warnings may result in serious injury or damage.
Be sure that the power supply provides the correct voltage and is
designed for the required current.
Use suitable circuit breakers with the prescribed nominal current
between the mains and drive control.
Use suitable fuses with appropriate current values between the mains
and drive control (see technical data).
The drive control must be grounded with the motor according to
relevant regulations. Non-compliance may result in serious injury.
44
Operating manual PED
Commissioning
4.2 Communication
The drive control can be commissioned in the following ways:
– Using the PC software
Fig. 20:
PC software – start screen
– Using MMI
Fig. 21:
Manual control unit MMI
Operating manual PED
45
Commissioning
4.3 Block diagram
Reference
channel
Control
mode
1.130
1.100
Control modes
Internal potentiometer
Analogue input 1
Analogue input 2
HMI / PC
Motorized potentiometer
Total AI1 / AI2
PID present reference
Fieldbus
Frequency
control mode
PID feedback
Analogue input 1
Analogue input 2
PID process
control
3.060
Enable software
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Analogue input 1
Analogue input 2
Fieldbus
Autostart
Preset speed
mode
1.131
Low-/ Highspeed
Revers Speed
direction
Motor current limit
f
I
Ramps
f
Reference
X(-1)
speed
t
t
1.150
Fig. 22:
46
1.020
1.021
5.070
5.071
Motor
control
t
1.051
1.053
1.050
1.052
General structure of target value generation
Operating manual PED
Commissioning
4.4 Start-up steps
Parameterisation is possible prior to installation.
Parameterisation can be performed before the drive
control
is
installed
in
the
motor.
The drive control has a 24 V low-voltage input for this
purpose, which can supply the electric system without
requiring mains power.
The start-up can be performed using a PC communication cable USB at
plug M12 with integrated interface converter RS485/RS232 (article no.
10023950) or using the PED manual control unit MMI with connection
cable RJ11 at plug M12 (article no. 10004768).
Start-up using the PC:
Install the PE-Drive software (you can obtain programming software
from HERBORNER PUMPS free of charge in the Download center).
Connect the PC to the M12 plug M1 with the optional connection cable.
Load or determine the motor data record (parameters 33.030 to
33.050); it may be necessary to optimise the speed control (parameters
34.100 to 34.101).
Perform the application settings (ramps, inputs, outputs, target values
etc.).
Optional: Define an access level (1 – MMI, 2 – user, 3 – manufacturer).
Please also refer to the quickstart guide in chapter 9.5.
In order to ensure an ideal operating structure for the PC software, the
parameters are classified into different access levels. The following levels
exist:
1. Manual control unit: – the drive control is programmed using the
manual control unit
2. User: – the basic parameters can be programmed into the drive control
using the PC software
3. Manufacturer: – an extended selection of parameters can be
programmed into the drive control using the PC software
Operating manual PED
47
Parameters
5 Parameters
This chapter contains the following:
– An introduction to the parameters
– An overview of the most important start-up and operation parameters
5.1 Safety instructions for working with parameters
WARNING
Danger of injury due to restarting motors.
Non-observance may result in serious injury or damage.
Certain parameter settings and changing parameter settings during
operation may result in the PED drive control restarting
automatically after the supply voltage has failed, or in undesirable
changes in the operating behaviour.
If parameters are changed while the device is in
operation, it may take a few seconds for the effect to
become noticeable.
5.2 General information on parameters
5.2.1
Explanation of operating modes
The operating mode is the instance in which the reference is generated.
In the case of frequency setting mode, this is a simple conversion of the
raw input reference into a rotation speed reference; in the case of PID
process control, the reference and feedback are compared and the
system then regulates to a specific process variable.
Frequency setting mode:
The references from the “reference channel” (1.130) are rescaled into
frequency references. 0% is the “low speed” (1.020), 100% is the “high
speed” (1.021).
The reference's plus or minus sign is the decisive factor in rescaling.
48
Operating manual PED
Parameters
PID process control:
The reference for the PID process control is read in percentage steps as in
the “frequency setting mode”. 100% corresponds to the working range of
the connected sensor, which is read in from the active channel (selected
by the “PID feedback”).
Depending on the control difference, a rotation speed value is output to
the control output with the help of the amplification factors for the
proportional gain (3.050), integral gain (3.051) and derivative gain
(3.052). In order to prevent the integral share from increasing infinitely in
the case of uncontrollable control differences, this value is limited to a
specific set value (corresponding to the “maximum frequency” (1.021)).
PID inverse:
The PID feedback can be inverted using the 3.061 parameter. The feedback
is imported inversely, i.e. 0 V…10 V correspond internally to 100%…0%.
Please note that the reference must also be defined inversely.
For example:
A sensor with an analogue output signal of (0 V…10 V) is to operate as the
source of the feedback channel (at AIx). At an output variable of 7 V
(70%), this is to be regulated inversely. The internal feedback then
corresponds to 100% – 70% = 30%. Accordingly, the specified reference is
30%.
Fig. 23:
PID process control
Operating manual PED
49
Parameters
Stand-by function in PID process control:
This function can provide energy savings in applications such as booster
stations where PID process control is used to control to a specific process
value and the pump has to run at a “minimum frequency” (1.020). As the
inverter can reduce the rotation speed of the pump in normal operation
when the process variable is reducing, but it is never able to fall below
the “minimum frequency” (1.020), this provides an opportunity for
stopping the motor if it is running during a waiting time, the “PID standby time” (3.070) with the “minimum frequency” (1.020).
Once the reference diverges from the set % value, the “PID stand-by
hysteresis” (3.071), the control (the motor) is started again.
Fig. 24:
50
Stand-by function in PID process control
Operating manual PED
Parameters
Preset speed:
In this operating mode, preset speed references are transferred to the
motor control. There are 7 preset speeds (2.051 to 2.057) that are BCD
coded and attached permanently to digital inputs 1 to 3. These seven
preset speeds can be released in three groups via the “preset speed
mode” (2.050) parameter:
0 = preset speed 1, 1 = preset speeds 1 to 3, 2 = preset speeds 1 to 7.
DI 3
DI 2
DI 1
Selection
Parameters
Presetting
0
0
0
Min. frequency
1.020
0 Hz
0
0
1
Preset speed 1
2.051
10 Hz
0
1
0
Preset speed 2
2.052
20 Hz
0
1
1
Preset speed 3
2.053
30 Hz
1
0
0
Preset speed 4
2.054
35 Hz
1
0
1
Preset speed 5
2.055
40 Hz
1
1
0
Preset speed 6
2.056
45 Hz
1
1
1
Preset speed 7
2.057
50 Hz
Tab. 13: Logic table of fixed frequencies
Operating manual PED
51
Parameters
5.2.2
Structure of the parameter tables
Fig. 25:
Example of a parameter table
Key
1 Parameter number
2 Description in the parameter manual on
page ...
3 Parameter name
4 Transfer status
0 = switch drive control off and on for
transfer
1 = set hardware release again
2 = during operation
5 Value range (from – to – factory setting)
52
6 Unit
7 Field for entering an own value
8 Explanation of the parameter
9 There are more parameters that relate
to these parameters
Operating manual PED
Parameters
5.3 Application parameters
5.3.1
Basic parameters
1.020
Relationship to
parameter:
Unit: Hz
Low speed
Parameter manual:
Transfer status:
p. xy
2
1.150
3.070
min:
0
max.:
400
def.:
0
Own value (to
be entered!)
The low speed is the frequency provided by the drive control as soon as it
is released and no additional target value is pending.
This frequency is not reached if
a) acceleration is carried out while the drive is not moving.
b) the frequency inverter is blocked. The frequency is then reduced to 0
Hz before it is blocked.
c) the frequency inverter reverses (1.150). The revolving field is reversed
at 0 Hz.
d) the stand-by function (3.070) is active.
1.021
Relationship to
parameter:
Unit: Hz
High speed
Parameter manual:
Transfer status:
p. xy
2
1.050
1.051
min:
5
max.:
400
def.:
50
Own value (to
be entered!)
The high speed is the frequency produced by the inverter depending on
the reference.
1.050
Relationship to
parameter:
Unit: s
Deceleration 1:
Parameter manual:
Transfer status:
p. xy
2
1.021
1.054
min:
0.1
max.:
1000
def.:
5
Own value (to
be entered!)
Deceleration 1 is the time that the inverter takes to brake to 0 Hz from
the high speed (1.021).
If the set deceleration time cannot be reached, the fastest possible
deceleration time is implemented.
Operating manual PED
53
Parameters
1.051
Relationship to
parameter:
1.021
1.054
Unit: s
Acceleration 1
Parameter manual:
Transfer status:
p. xy
2
min:
0.1
max.:
1000
def.:
5
Own value (to
be entered!)
Acceleration 1 is the time that the inverter takes to accelerate from 0 Hz
to the high speed.
The acceleration time can be increased as a result of certain
circumstances, e.g. if the drive control is overloaded.
1.052
Relationship to
parameter:
1.021
1.054
Unit: s
Deceleration 2
Parameter manual:
p. xy
Transfer status:
2
min:
0.1
max.:
1000
def.:
10
Own value
(to be entered!)
Deceleration 2 is the time that the inverter takes to brake to 0 Hz from
the high speed (1.021).
If the set deceleration time cannot be reached, the fastest possible
deceleration time is implemented.
1.053
Relationship to
parameter:
1.021
1.054
Unit: s
Acceleration 2
Parameter manual:
Transfer status:
p. xy
2
min:
0.1
max.:
1000
def.:
10
Own value
(to be entered!)
Acceleration 2 is the time that the inverter takes to accelerate from 0 Hz
to the high speed.
The acceleration time can be increased as a result of certain
circumstances, e.g. if the drive control is overloaded.
54
Operating manual PED
Parameters
1.054
Unit: integer
Ramp selection
Relationship to
parameter:
Parameter manual:
Transfer status:
1.050 to 1.053
p. xy
2
min:
0
max.:
6
def.:
0
Own value (to
be entered!)
Selection of used ramp pair
0 = deceleration 1 (1.050) / acceleration 1 (1.051)
1 = deceleration 2 (1.052) / acceleration 2 (1.053)
2 = digital input 1 (false = ramp pair 1 / true = ramp pair 2)
3 = digital input 2 (false = ramp pair 1 / true = ramp pair 2)
4 = digital input 3 (false = ramp pair 1 / true = ramp pair 2)
5 = digital input 4 (false = ramp pair 1 / true = ramp pair 2)
6 = PED soft PLC
1.100
Relationship to
parameter:
1.130
1.131
2.051 to 2.057
3.050 to 3.071
Unit: integer
Control mode
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
3
def.:
0
Own value (to
be entered!)
Selecting the operating mode.
After software release (1.131) and hardware release, the drive control
runs as follows:
0 = frequency control mode, with the target value of the selected
reference channel (1.130)
1 = PID process control, with the target value of the PID process control
(3.050–3.071)
2 = preset speed mode, with the frequencies specified by parameters
2.051–2.057
3 = selection from PED soft PLC
Operating manual PED
55
Parameters
1.130
Unit: integer
Reference channel
Relationship to
parameter:
Parameter manual:
Transfer status:
3.062 to 3.069
p. xy
2
min:
0
max.:
10
def.:
0
Own value (to
be entered!)
Determines the source from where the reference is to be read.
0 = internal potentiometer
1 = analogue input 1
2 = analogue input 2
3 = MMI/PC
4 = SAS
6 = motor potentiometer
7= total analogue inputs 1 and 2
8 = PID preset reference mode (3.062)
9 = field bus
10 = reference from PED soft PLC
1.131
Relationship to
parameter:
1.132
1.150
2.050
4.030
4.050
Unit: integer
Enable software
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
13
def.:
0
Own value (to
be entered!)
WARNING
The motor may start immediately, depending on the change made.
Selection of the source for the control release.
0 = digital input 1
1 = digital input 2
2 = digital input 3
3 = digital input 4
4 = analogue input 1 (has to be selected in parameter 4.030)
5 = analogue input 2 (has to be selected in parameter 4.050)
6 = field bus
7 = SAS
8 = digital input 1 right / digital input 2 left
1.150 must be set to “0”
9 = autostart:
10 = PED Soft-PLC
11 = preset frequency input (all inputs which are selected in parameter
2.050)
12 = internal potentiometer
13 = membrane keyboard (start & stop buttons
The motor may start immediately if hardware is enabled (En.Hw. Fig. 8)
and a reference has been provided.
This cannot be prevented even with parameter 1.132.
56
Operating manual PED
Parameters
1.132
Relationship to
parameter:
Unit: integer
Start protect
Parameter manual:
Transfer status:
p. xy
2
1.131
min:
0
max.:
6
def.:
1
Own value (to
be entered!)
Selection of behaviour in response to enabling software (parameter
1.131).
No effect if autostart was selected.
0 = immediate start when high signal is received at start input of control
release
1 = start only if rising shoulder at start input of control release
2 = digital input 1 (function active at high signal)
3 = digital input 2 (function active at high signal)
4 = digital input 3 (function active at high signal)
5 = digital input 4 (function active at high signal)
6 = PED soft PLC
1.150
Relationship to
parameter:
1.131
4.030
4.050
Unit: integer
Direction of rotation
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
12
def.:
0
Own value (to
be entered!)
Selecting the direction of rotation specification
0 = dependent on target value (depending on the plus or minus sign of
the target value: positive: forward; negative: backwards)
1 = forwards only (direction of rotation cannot be changed)
2 = backwards only (direction of rotation cannot be changed)
3 = digital input 1 (0 V = forwards, 24 V = backwards)
4 = digital input 2 (0 V = forwards, 24 V = backwards)
5 = digital input 3 (0 V = forwards, 24 V = backwards)
6 = digital input 4 (0 V = forwards, 24 V = backwards)
7 = reference from PED soft PLC
8 = analogue input 1 (must be selected in parameter 4.030)
9 = analogue input 2 (must be selected in parameter 4.050)
10 = membrane keyboard button for changing direction of rotation (only
when motor is running)
11 = membrane keyboard button 1 forwards / 2 reverse (change always
possible)
12 = membrane keyboard button 1 forwards / 2 reverse (change only
possible when motor is stationary)
Operating manual PED
57
Parameters
1.180
Relationship to
parameter:
Unit: integer
Reset
Parameter manual:
Transfer status:
p. xy
2
1.181
1.182
min:
0
max.:
5
def.:
4
Own value (to
be entered!)
Selection of the source for error confirmation.
Errors can only be confirmed once the error has been remedied.
Some errors can only be confirmed by switching the control off and then
on again,
see list of errors.
Auto-confirmation via parameter 1.181.
0 = no manual confirmation possible
1 = rising shoulder at digital input 1
2 = rising shoulder at digital input 2
3 = rising shoulder at digital input 3
4 = rising shoulder at digital input 4
5 = membrane keyboard (acknowledgement button)
1.181
Relationship to
parameter:
Unit: s
Automatic reset
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:1000 000
1.180
1.182
def.:
Own value (to
be entered!)
0
In addition to the reset function (1.180), an automatic reset can be
selected.
0
>0
1.182
Relationship to
parameter:
= no automatic confirmation
= time for automatic reset of error in seconds
Unit:
Number of automatic resets
Parameter manual:
Transfer status:
p. xy
2
1.180
1.181
min:
0
max.:
500
def.:
5
Own value (to
be entered!)
In addition to the automatic reset (1.181), it is possible to limit the
maximum number of automatic resets here.
0
>0
58
= no restriction on automatic confirmations
= maximum number of permitted automatic confirmations
Operating manual PED
Parameters
5.3.2
Preset speed mode
This mode has to be selected in parameter 1.100,
see also the section on selecting the operating mode
2.050
Relationship to
parameter:
Unit: integer
Preset speed mode
Parameter manual:
Transfer status:
p. xy
1.100
2.051 to 2.057
2
min:
0
max.:
3
def.:
2
Own value (to
be entered!)
Selection of the digital inputs used for the preset speeds
0 = Digital In 1
(preset speed 1) (2.051)
1 = Digital In 1, 2 (preset speeds 1 - 3) (2.051 to 2.053)
2 = Digital In 1, 2, 3
(preset speeds 1 - 7) (2.051 to 2.057)
3 = membrane keyboard (button 1 = fixed frequency 1 / button 2 = fixed
frequency 2)
2.051 to 2.057
Relationship to
parameter:
1.020
1.021
1.100
1.150
2.050
Unit: Hz
Preset speed
Parameter manual:
Transfer status:
p. xy
2
min:
-400
max.:
+400
def.:
0
Own value (to
be entered!)
The frequencies that are to be output at the digital inputs 1 - 3 specified
in parameter 2.050 depending on the switching patterns.
See chapter 5.2.1 on preset speeds.
Operating manual PED
59
Parameters
5.3.3
Motorised potentiometer
This mode must be selected in parameter 1.130. This function can be
used as a source of target values for frequency setting mode as well as
for the PID process controller.
2.150
Relationship to
Parameter:
1.130
4.030
4.050
unit: integer
MOP digital Input
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
8
def.:
3
Own value
(to be
entered!)
Selection of the source for increasing and reducing the target value
0 = Digital In 1 + / Digital In 2 1 = Digital In 1 + / Digital In 3 2 = Digital In 1 + / Digital In 4 3 = Digital In 2 + / Digital 3 4 = Digital In 2 + / Digital In 4 5 = Digital In 3 + / Digital In 4 6 = Analogue In 1 + / Analogue In 2 (must be selected in parameter 4.030 / 4.050)
7 = reference from customer PLC
8 = membrane keyboard (button 1 - / button 2 +)
2.151
Relationship to
parameter:
1.020
1.021
Unit: %
MOP step range
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
def.:
1
Own value (to
be entered!)
Increments at which the target value changes per keystroke.
2.152
Relationship to
parameter:
Unit: s
MOP step time
Parameter manual:
Transfer status:
p. xy
2
min:
0.02
max.:
1000
def.:
0.04
Own value (to
be entered!)
Indicates the time during which the target value is totalled with a
permanent signal.
60
Operating manual PED
Parameters
2.153
Relationship to
parameter:
Unit: s
MOP response time
Parameter manual:
Transfer status:
p. xy
2
min:
0.02
max.:
1000
def.:
0.3
Own value (to
be entered!)
Indicates the time for which the signal is considered permanent.
2.154
Relationship to
parameter:
Unit: integer
MOP reference memory
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
def.:
0
Own value (to
be entered!)
Defines whether the target value of the motor potentiometer is retained
even after power outage.
0 = disable
1 = enable
5.3.4
PID process controller
This mode has to be selected in parameter 1.100,
the target value source has to be selected in parameter 1.130,
see also chapter 5.2.1, “Explanation of operating modes – preset speed”.
3.050
Relationship to
parameter:
Unit:
PID proportional gain
Parameter manual:
Transfer status:
p. xy
2
1.100
1.130
min:
0
max.:
100
def.:
1
Own value (to
be entered!)
Proportional share of PID controller
3.051
Relationship to
parameter:
Unit: 1/s
PID integral gain
Parameter manual:
Transfer status:
p. xy
2
1.100
1.130
min:
0
max.:
100
def.:
1
Own value (to
be entered!)
Integral share of PID controller
Operating manual PED
61
Parameters
3.052
Relationship to
parameter:
1.100
1.130
Unit: s
PID derivative gain
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
def.:
0
Own value (to
be entered!)
Differential share of PID controller
3.060
Relationship to
parameter:
1.100
1.130
3.061
Unit: integer
PID feedback
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
2
def.:
0
Own value (to
be entered!)
Selection of the input source from which the feedback for the PID
process controller is imported:
0 = analogue input 1
1 = analogue input 2
3.061
Relationship to
parameter:
3.060
Unit: integer
PID inverted
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
def.:
0
Own value (to
be entered!)
The source of the feedback (parameter 3.060) is inverted
0 = disable
1 = enable
3.062 to 3.068
Relationship to
parameter:
1.130
3.069
Unit: %
PID preset reference
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
def.:
0
Own value (to
be entered!)
The PID preset reference depending on the switching patterns is to be
issued at the digital inputs 1 – 3 specified in parameter 3.069 (has to be
selected in parameter 1.130).
3.069
62
PID preset reference mode
Unit: integer
Operating manual PED
Parameters
Relationship to
parameter:
Parameter manual:
Transfer status:
p. xy
2
1.100
3.062 to 3.068
min:
0
max.:
2
def.:
0
Own value (to
be entered!)
Selection of the digital inputs used for fixed frequencies
0 = Digital In 1
(PID preset reference 1) (3.062)
1 = Digital In 1, 2 (PID preset references 1 – 3) (3.062 to 3.064)
2 = Digital In 1, 2, 3
(PID preset references 1 – 7) (3.062 to
3.068)
3.070
Relationship to
parameter:
Unit: s
PID stand-by time
Parameter manual:
Transfer status:
S. xy
2
1.020
min:
0
max.:
10 000
def.:
0
Own value (to
be entered!)
If the drive control runs for the set time at the low speed (parameter
1.020), the motor is stopped (0 Hz), see also Chapter 5.2.1, “PID process
control”
0
>0
3.071
Relationship to
parameter:
= disable
= waiting time until stand-by function is enabled
Unit: %
PID stand-by hysteresis
Parameter manual:
Transfer status:
p. xy
2
3.060
min:
0
max.:
50
def.:
0
Own value (to
be entered!)
Condition for waking up the PID controller from stand-by.
Once the control difference exceeds the set value as %, the control
begins again, see also “Control mode (parameter 1.100) – PID controller”.
Operating manual PED
63
Parameters
5.3.5 Analogue inputs
For analogue inputs 1 and 2 (Alx display Al1/Al2)
4.020/4.050
Relationship to
parameter:
Unit: integer
Alx reference type
Parameter manual:
Transfer status:
p. xy
2
min:
1
max.:
2
def.:
1
Own value (to
be entered!)
Function of analogue inputs 1/2:
1 = voltage input
2 = current input
4.021/4.051
Relationship to
parameter:
Unit: %
Alx minimum input
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
def.:
0
Own value (to
be entered!)
Specifies the minimum value of the analogue inputs as a percentage of
the range.
Example:
4.022/4.052
Relationship to
parameter:
0…10 V or 0…20 mA = 0%…100%
2…10 V or 4…20 mA = 20%…100%
Unit: %
Alx maximum input
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
def.:
100
Own value (to
be entered!)
Specifies the maximum value of the analogue inputs as a percentage of
the range.
Example:
0…10 V or 0…20 mA = 0%…100%
2…10 V or 4…20 mA = 20%…100%
4.023/4.053
Relationship to
parameter:
Unit: %
Alx dead time
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
def.:
0
Own value (to
be entered!)
Dead time as percentage of the range of the analogue inputs.
64
Operating manual PED
Parameters
4.024/4.054
Relationship to
parameter:
Unit: s
Alx filter time
Parameter manual:
Transfer status:
p. xy
2
min:
0.02
max.:
1.00
def.:
0
Own value (to
be entered!)
Filter time of analogue inputs in seconds.
4.030/4.060
Relationship to
parameter:
Unit: integer
AIx function
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
def.:
0
Own value (to
be entered!)
Function of analogue inputs 1/2
0 = analogue input
1 = digital input
4.033/4.063
Relationship to
parameter:
Parameter manual:
Transfer status:
p. xy
2
4.034/4.064
4.035/4.065
Unit:
Alx physical unit
min:
0
max.:
10
def.:
0
Own value (to
be entered!)
Selection of different physical values to be displayed.
0=%
1 = bar
2 = mbar
3 = psi
4 = Pa
5 = m3/h
6 = l/min
7 = °C
8 = °F
9=m
10 = mm
Operating manual PED
65
Parameters
4.034/4.064
Relationship to
parameter:
Parameter manual:
Transfer status:
p. xy
2
5.3.6
0
Unit:
Alx physical maximum
Parameter manual:
Transfer status:
p. xy
2
min:-10 000
max.:+10 000
4.033/4.063
4.034/4.064
def.:
Own value (to
be entered!)
Selection of the lower limit of a physical value to be displayed.
4.035/4.065
Relationship to
parameter:
min:-10 000
max.:+10 000
4.033/4.063
4.035/4.065
Unit:
Alx physical minimum
def.:
Own value (to
be entered!)
100
Selection of the upper limit of a physical value to be displayed.
Digital inputs
4.110 to 4.113
Relationship to
parameter:
Unit: integer
DIx inverted
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
def.:
0
Own value (to
be entered!)
This parameter can be used to invert the digital input.
0 = disable
1 = enable
66
Operating manual PED
Parameters
5.3.7
Analogue output
4.100
Relationship to
parameter:
Unit: integer
AO1 function
Parameter manual:
Transfer status:
p. xy
2
4.101
4.102
min:
0
max.:
40
def.:
0
Own value (to
be entered!)
Selection of the process value that is output at the analogue output.
The standardisation (4.101/4.102) has to be adapted, depending on the
selected process value.
0 = not assigned / PED soft PLC
1 = intermediate circuit voltage
2 = supply voltage
3 = motor voltage
4 = motor current
5 = frequency feedback
6 = speed measured externally by speed sensor (if available)
7 = current angle or position (if available)
8 = IGBT temperature
9 = internal temperature
10 = analogue input 1
11 = analogue input 2
12 = frequency reference
13 = motor power
14 = torque
15 = field bus
16 = PID reference (as of V3.60)
17 = PID actual value (as of V3.60)
4.101
Relationship to
parameter:
Unit:
AO1 minimum output
Parameter manual:
Transfer status:
p. xy
2
min: -10 000
max.: +10 000
4.100
def.:
Own value (to
be entered!)
0
Describes which area is to be broken down into the 0-10 V output voltage
or the 0-20 mA output current.
4.102
Relationship to
parameter:
Unit:
AO1 maximum output
Parameter manual:
Transfer status:
p. xy
2
4.100
Operating manual PED
min: -10 000
max.: +10 000
def.:
Own value (to
be entered!)
0
67
Parameters
Describes which area is to be broken down into the 0-10 V output voltage
or the 0-20 mA output current.
5.3.8 Digital outputs
For digital outputs 1 and 2 (DOx display DO1/DO2)
4.150/4.170
Relationship to
parameter:
4.151/4.171
4.152/4.172
Unit: integer
DOx function
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
50
def.:
0
Own value (to
be entered!)
Selection of the process value to which the output should switch.
0 = not assigned / PED soft PLC
1= DC bus voltage
2= line voltage
3= motor voltage
4= motor current
5= frequency feedback
6= –
7= –
8= IGBT temperature
9= internal temperature
10= error (NO)
11= inverted error (NC)
12= final release levels
13= digital input 1
14= digital input 2
15= digital input 3
16= digital input 4
17= ready for operation
18= ready
19= operation
20= ready for operation + ready
21= ready for operation + ready + operation
22= ready + operation
23 = motor power
24 = torque
25 = field bus
26 = analogue input 1 (as of V3.60)
27 = analogue input 2 (as of V3.60)
28 = PID reference (as of V3.60)
29 = PID actual value (as of V3.60)
50 = torque
4.151/4.171
Relationship to
68
Unit:
DOx on
Parameter manual:
Transfer status:
min:
-10
Own value (to
Operating manual PED
Parameters
parameter:
000
p. xy
2
4.150/4.170
be entered!)
max.:10 000
def.:
0
If the set process value exceeds the switch-on limit, the output is set to
1.
4.152/4.172
Relationship to
parameter:
Unit:
DOx off
Parameter manual:
Transfer status:
p. xy
2
4.150/4.170
min:
000
-10
Own value (to
be entered!)
max.:10 000
def.:
0
If the set process parameter falls below the switch-on limit, the output is
set to 0.
5.3.9 Relay
For relays 1 and 2 (Rel.x – display Rel. 1/Rel. 2)
4.190/4.210
Relationship to
parameter:
Unit: integer
Rel.x function
Parameter manual:
Transfer status:
p. xy
2
4.191/4.211
4.192/4.212
min:
0
max.:
50
def.:
0
Own value (to
be entered!)
Selection of the process value to which the output should switch.
0= not assigned / PED Soft-PLC
1= DC bus voltage
2= line voltage
3= motor voltage
4= motor current
5= frequency feedback
6= –
7= –
8= IGBT temperature
9= internal temperature
10= error (NO)
11= inverted error (NC)
12= final release levels
13= digital input 1
14= digital input 2
15= digital input 3
16= digital input 4
17= ready for operation
Operating manual PED
69
Parameters
18= ready
19= operation
20= ready for operation + ready
21= ready for operation + ready + operation
22= ready + operation
23 = motor power
24 = torque
25 = field bus
26 = analogue input 1 (as of V3.60)
27 = analogue input 2 (as of V3.60)
28 = PID reference (as of V3.60)
29 = PID actual value (as of V3.60)
50 = motor current limit active
4.191/4.211
Relationship to
parameter:
4.190/4.210
Unit:
Rel.x on
Parameter manual:
Transfer status:
p. xy
2
min:
000
-10
Own value (to
be entered!)
max.:10 000
def.:
0
If the set process value exceeds the switch-on limit, the output is set to
1.
4.192/4.212
Relationship to
parameter:
4.190/4.210
Unit:
Rel.x off
Parameter manual:
Transfer status:
p. xy
2
min:
000
-10
Own value (to
be entered!)
max.:10 000
def.:
0
If the set process parameter falls below the switch-on limit, the output is
set to 0.
4.193/4.213
Relationship to
parameter:
4.194/4.214
Unit: s
Rel.x on delay
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
10 000
def.:
0
Own value (to
be entered!)
Specifies the length of the switch-on delay.
70
Operating manual PED
Parameters
4.194/4.214
Relationship to
parameter:
Unit: s
Rel.x off delay
Parameter manual:
Transfer status:
p. xy
2
4.193/4.213
min:
0
max.:
10 000
def.:
0
Own value (to
be entered!)
Specifies the length of the switch-off delay.
5.3.10 External fault
5.010/5.011
Unit: integer
External fault 1/2
Relationship to
parameter:
Parameter manual:
4.110 to 4.113
p. xy
Transfer status:
2
min:
0
max.:
4
def.:
0
Own value (to
be entered!)
Selection of the source from which an external error can be reported.
0 = not assigned / PED Soft-PLC
1 = digital input 1
2 = digital input 2
3 = digital input 3
4 = digital input 4
If the selected digital input has a high signal, the inverter switches to
error no. 23/24 external fault 1/2.
Parameters 4.110 to 4.113 DIx inverse can be used to invert the logic of
the digital input.
5.3.11 Motor current limit
This function limits the motor current to a parameterised maximum value
after a parameterised current-time zone has been reached.
This motor current limit is monitored at application level and thereby
limits with relatively low dynamics. This has to be taken into
consideration when selecting this function.
The maximum value is determined using the “motor current limit as %”
parameter (5.070). This is stated as a percentage and relates to the
nominal motor current specified in the “motor current” type plate data
(33.031).
Operating manual PED
71
Parameters
The maximum current-time zone is calculated from the product of the
“motor current limit in s” parameter (5.071) and the fixed overcurrent of
50% of the required motor current limit.
As soon as this current-time zone is exceeded, the motor current is
restricted to the limit value by reducing the rotation speed. If the output
current of the drive control exceeds the motor current (parameter
33.031) multiplied by the set limit as % (parameter 5.070) for the set
time (parameter 5.071), the speed of the motor is reduced until the
output current is below the set limit.
This reduction is undertaken by a PI controller that operates depending
on the current difference.
The entire function can be deactivated by setting the “motor current
limit
as %” parameter (5.070) to zero.
5.070
Relationship to
parameter:
5.071
33.031
Unit: %
Motor current limit
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
250
def.:
0
Own value (to
be entered!)
0 = disable
5.071
Relationship to
parameter:
5.070
33.031
Parameter manual:
Transfer status:
p. xy
2
5.075
Relationship to
parameter:
33.034
Unit: s
Motor current limit
min:
0
max.:
100
def.:
1
Own value (to
be entered!)
Unit:
Gearbox factor
Parameter manual:
Transfer status:
S. xy
2
min:
0
max.:
1000
Def.:
1
Own value (to
be entered!)
A gearbox factor can be set here.
The mechanical speed display can be adjusted using the gearbox factor.
72
Operating manual PED
Parameters
5.3.12 Stall detection
5.080
Relationship to
parameter:
Unit: integer
Stall detection
Parameter manual:
Transfer status:
p. xy
2
5.081
min:
0
max.:
1
def.:
0
Own value (to
be entered!)
This parameter can be used to activate stall detection.
0 = disable
1 = enable
5.081
Relationship to
parameter:
Unit: s
Blocking time
Parameter manual:
Transfer status:
p. xy
2
5.080
min:
0
max.:
50
def.:
2
Own value (to
be entered!)
Indicates the time after which a blockage is detected.
5.090
Relationship to
parameter:
Unit: integer
Parameter set change
Parameter manual:
Transfer status:
S. xy
2
min:
0
max.:
7
Def.:
0
Own value (to
be entered!)
Selection of active data set.
0 = not assigned
1 = data set 1 active
2 = data set 2 active
3 = digital input 1
4 = digital input 2
5 = digital input 3
6 = digital input 4
7 = PED soft PLC
The 2nd data set is only displayed in the PC software when this
parameter is <> 0. The values of the data set currently selected are
always displayed in the MMI.
Operating manual PED
73
Parameters
5.4 Performance parameters
5.4.1
Motor data
33.001
Relationship to
parameter:
34.010
Unit: Integer
Type of motor
Parameter manual:
Transfer status:
S. xy
1
min:
1
max.:
2
def.:
1
Own value (to
be entered!)
Selecting the type of motor
1 = asynchronous motor
2 = synchronous motor
The parameters are shown depending on the type of motor selected.
The type of control (parameter 34.010) must also be selected.
33.015
Relationship to
parameter:
Unit: %
R optimisation
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
200
def.:
100
Own value (to
be entered!)
If necessary, this parameter can be used to optimise the start-up
behaviour.
33.031
Relationship to
parameter:
5.070
Unit: A
Motor current
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
150
def.:
0
This is used to set the nominal motor current I
triangle connection.
74
M,N
Own value (to
be entered!)
for either the star or
Operating manual PED
Parameters
33.032
Relationship to
parameter:
Unit: W
Motor power
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
55 000
def.:
0
Own value (to
be entered!)
A performance value [W] P M,N has to be set here that corresponds to the
motor power.
33.034
Relationship to
parameter:
Parameter manual:
p. xy
min:
1
def.:
Own value (to
be entered!)
0
Unit: Hz
Motor frequency
Parameter manual:
Transfer status:
p. xy
1
min:
40
max.:
100
def.:
This is where the nominal motor frequency f
33.050
Relationship to
parameter:
0
The value from the motor's type plate data has to be entered here for the
nominal motor rotation speed n M,N.
33.035
Relationship to
parameter:
Transfer status:
max.:10 000
34.120
5.075
Unit: rpm
Motor speed
M,N
Own value (to
be entered!)
0
is set.
Unit: Ohm
Stator resistance
Parameter manual:
Transfer status:
p. xy
1
min:
0
Own value (to
be entered!)
max.:
30
def.:
0.001
The stator resistance can be optimised here, if the automatically
determined value (motor identification) is insufficient.
33.105
Relationship to
Unit: H
Leakage inductance
Parameter manual:
Operating manual PED
Transfer status:
min:
0
Own value (to
75
Parameters
parameter:
p. xy
1
max.:
100
def.:
0
be entered!)
Only for asynchronous motors.
Here the leakage inductance can be optimised if the automatically
calculated value (of motor identification) isn't sufficient.
33.110
Relationship to
parameter:
Unit: V
Motor voltage
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
680
def.:
0
Own value (to
be entered!)
Only for asynchronous motors.
This is used to set the nominal motor voltage U M,N for either the star or
triangle connection.
33.111
Relationship to
parameter:
Unit: 1
Motor cos phi
Parameter manual:
Transfer status:
p. xy
1
min:
0.5
max.:
1
def.:
0
Own value (to
be entered!)
Only for asynchronous motors.
The value from the motor's type plate data has to be entered here for
the power factor cos phi.
33.200
Relationship to
parameter:
Unit: H
Stator inductance
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
100
def.:
0
Own value (to
be entered!)
For synchronous motors only.
The stator inductance can be optimised here if the automatically
determined value (motor identification) is insufficient.
33.201
76
Nominal flux
Unit: mVs
Operating manual PED
Parameters
Relationship to
parameter:
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
5000
def.:
0
Own value (to
be entered!)
For synchronous motors only.
The nominal flux can be optimised here if the automatically determined
value (motor identification) is insufficient.
5.4.2
I²T
I2T fact. motor
33.010
Relationship to
parameter:
Unit: %
Parameter manual:
Transfer status:
p. xy
2
33.031
33.011
min:
0
max.:
1000
def.:
100
Own value (to
be entered!)
The percentage current threshold (in relation to motor current 33.031) at
the start of integration can be set here.
I2T time
33.011
Relationship to
parameter:
Unit: s
Parameter manual:
Transfer status:
p. xy
2
33.010
min:
0
max.:
1200
def.:
25
Own value (to
be entered!)
Time after which the drive control switches off with I²T.
33.138
Relationship to
parameter:
Unit: s
Holding current time
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.: 128 000
33.010
def.:
Own value (to
be entered!)
2
Only for asynchronous motors.
This is the time during which the drive is held at continuous current after
the brake ramp has been completed.
Operating manual PED
77
Parameters
5.4.3
Switching frequency
The internal switching frequency (clocking frequency) can be changed in
order to control the power element. A high setting reduces noise in the
motor but increases EMC emissions and losses in the drive control.
34.030
Relationship to
parameter:
Unit: Hz
Switching frequency
Parameter manual:
Transfer status:
p. xy
2
min:
1
max.:
4
def.:
2
Own value (to
be entered!)
Selection of the switching frequency for the inverter
1 = 16 kHz
2 = 8 kHz
4 = 4 kHz
5.4.4
Controller data
34.010
Relationship to
parameter:
33.001
34.011
Unit: integer
Control method
Parameter
manual:
p. xy
Transfer status:
2
min:
100
max.:
201
def.:
100
Own value (to
be entered!)
Selection of the type of control.
100 = open-loop asynchronous motor
101 = closed-loop asynchronous motor
200 = open-loop synchronous motor
201 = closed-loop synchronous motor
78
Operating manual PED
Parameters
34.011
Relationship to
parameter:
34.010
34.012
34.013
Unit: integer
Type of encoder
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
2
def.:
0
Own value (to
be entered!)
Selection of the type of sensor
0 = inactive
1 = TTL sensor
2 = HTL sensor
WARNING
When selecting the HTL sensor, 24V is transmitted via the interface.
If using a TTL sensor, this could result in damage to the sensor.
34.012
Relationship to
parameter:
34.010
34.011
34.013
Parameter manual:
Transfer status:
p. xy
2
34.010
34.011
34.012
0
max.:
10 000
def.:
1024
Own value (to
be entered!)
Unit: °
Encoder offset
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
360
def.:
0
Own value (to
be entered!)
An encoder offset for the sensor can be set here.
34.021
Relationship to
parameter:
min:
Selection of the line count of the sensor used.
34.013
Relationship to
parameter:
Unit: integer
Encoder line count
Unit:
Flying restart
Parameter manual:
Transfer status:
p. xy
1
min:
0
max.:
1
def.:
1
Own value (to
be entered!)
This parameter is used to activate the capture function.
0 = disable
1 = enable
Operating manual PED
79
Parameters
34.090
Relationship to
parameter:
Unit: mA/rad/s
Speed control Kp
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.: 10 000
def.:
Own value (to
be entered!)
150
The control boost of the speed control can be optimised here, if the
automatically determined results (of the motor identification) are
insufficient.
34.091
Relationship to
parameter:
Unit: s
Speed control Tn
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
10
def.:
4
Own value (to
be entered!)
The reset time of the speed control can be optimised here, if the
automatically determined results (of the motor identification) are
insufficient.
34.110
Relationship to
parameter:
33.034
Unit:
Slip trimmer
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
def.:
1
Own value (to
be entered!)
Only for asynchronous motors.
This parameter can be used to optimise or deactivate slippage
compensation.
0 = disable (performance as on the grid)
1 = compensation for slippage.
34.130
Relationship to
parameter:
Unit:
Voltage control reserve
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
2
def.:
0.95
Own value (to
be entered!)
Only for asynchronous motors.
This parameter can be used to adjust voltage output.
80
Operating manual PED
Parameters
5.4.5
Quadratic characteristic
34.120
Relationship to
parameter:
Unit: integer
Quadratic characteristic
Parameter manual:
Transfer status:
p. xy
2
34.121
min:
0
max.:
1
def.:
0
Own value
(to be
entered!)
Only for asynchronous motors.
The quadratic characteristic curve function can be activated here.
0 = disable
1 = enable
34.121
Relationship to
parameter:
Unit: %
Flux compensation
Parameter manual:
Transfer status:
p. xy
2
34.120
min:
0
max.:
100
def.:
50
Own value (to
be entered!)
Only for asynchronous motors.
The percentage by which the flux is to be reduced can be set here.
An overvoltage shutdown can occur if there are any major changes in
operation.
5.4.6
Synchronous motor controller data
Field weakening
34.225
Relationship to
parameter:
Unit: integer
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
Def.:
0
Own value
(to be
entered!)
For synchronous motors only.
0 = disable, the motor cannot be run in the field weakening.
1 = enable, the motor can be placed in the field weakening until the
inverter has reached its current limit or the maximum permissible
electromotive force.
Operating manual PED
81
Parameters
34.226
Relationship to
parameter:
34.227
Unit: %
Starting current
Parameter manual:
Transfer status:
p. xy
2
min:
5
max.:
1000
Def.:
25
Own value
(to be
entered!)
For synchronous motors only.
Here the current which was stamped in the motor before starting the
control can be adjusted. As % of nominal motor current.
34.227
Relationship to
parameter:
34.226
Unit: s
Init time
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
100
Def.:
0.25
Own value
(to be
entered!)
For synchronous motors only.
Here the time during which the start up current 34.226 is stamped can be
set.
34.228 – 34.230
Relationship to
parameter:
Unit: integer
Startup procedure
Parameter manual:
Transfer status:
p. xy
2
min:
0
max.:
1
Def.:
0
Own value
(to be
entered!)
For synchronous motors only.
By changing the startup procedure to “Controlled”, higher starting
torques can be achieved.
0 = regulated, the inverter switches directly to the controller after the
stamping phase.
1 = controlled, after the stamping phase the rotation field is increased by
the control with start ramp 34.229 up to start frequency 34.230, then
switched to the controller.
82
Operating manual PED
Error detection and troubleshooting
6 Error detection and troubleshooting
This chapter contains the following:
– A list of the LED flash codes for error recognition
– A description of error recognition using PC tools
– A list of errors and system errors
– Notes on error detection with the MMI
WARNING
Risk of injury and electric shock.
Non-observance of warnings may result in serious injury or damage.
Repairs to the device may only be performed by the HERBORNER
PUMPS Service department.
Damaged parts or components have to be replaced with parts
from the appropriate list of spare parts.
The frequency inverter has to be disconnected prior to opening,
assembly or disassembly.
6.1 List of the LED flash codes for error recognition
When an error occurs, the LEDs on the drive control display a flashing
code that allows the errors to be diagnosed.
The following table contains an overview.
Operating manual PED
83
Error detection and troubleshooting
Red
LED
Green
LED
State
Boot loader active (flashing in turn)
Ready for operation (activate En_HW for operation)
Operation
Warning
Error
Identification of motor data
Initialisation
Firmware update
Bus error operation
Bus error ready for operation
Tab. 14: LED flash codes
Key
84
LED off
LED on
LED flashing
LED flashing quickly
Operating manual PED
Error detection and troubleshooting
6.2 List of errors and system errors
When an error occurs, the inverter is switched off; you can find the
corresponding error numbers in the flash code table or the PC tool.
Error messages can only be confirmed once the error
has been remedied.
Error messages can be confirmed as follows:
– digital input (programmable)
– via the MMI (manual operating unit)
– auto confirmation (parameter 1.181, page 38)
– switching the device off and on
– via field bus (CANOpen, Profibus DP, EtherCAD)
The following section contains a list of possible error messages.
Please contact the Herborner Pumps service department if you encounter
errors that are not listed here.
No.
Error name
Description of fault
Possible cause/remedy
1
Undervoltage 24 V
application
Supply voltage for the
application is less than 15 V
Overload of the 24 V
supply
2
Overvoltage 24 V
application
Supply voltage for the
application is greater than 31 V
Internal 24 V supply is
not OK or external supply
is not OK
6
Customer PLC version
error
The version of the customer
PLC doesn't match the device
firmware.
Check the version
numbers of the customer
PLC and device firmware
8
Communication
application<>power
Internal communication
between the application plate
and the power-conducting
plate is not OK
EMC interference
10
Parameter distributor
The internal distribution of
parameters during initialisation
failed
Parameter set is
incomplete
11
Time-out power
The power part does not
respond
Operation with 24 V
without mains feed-in
13
Cable break at analogue
in 1 (4–20 mA / 2–10 V)
Current or voltage is less than
Cable break, faulty
the lower limit of analogue
external sensor
input 1 (monitoring for this
error is activated automatically
by setting parameter 4.021 to
20)
Operating manual PED
85
Error detection and troubleshooting
No.
Error name
Description of fault
14
Cable break at analogue
in 2
(4–20 mA / 2–10 V)
Current or voltage is less than
Cable break, faulty
the lower limit of analogue
external sensor
input 2 (monitoring for this
error is activated automatically
by setting parameter 4.021 to
20)
15
Stall detection
The drive shaft of the motor is
stalled. 5.080
Remove the blockage
18
Excess frequency
inverter temperature
application
Inner temperature too high
Insufficient cooling, low
motor speed and high
torque, clocking
frequency too high
21
Bus time-out
No answer from bus sharing
unit or MMI/PC
Check bus wiring
22
Confirmation error
The number of maximum
automatic confirmations
(1.182) was exceeded
Check error history and
remedy error
23
External fault 1
The parameterised fault input
is active. 5.010
Correct the external
fault
24
External fault 2
The parameterised fault input
is active. 5.011
Correct the external
fault
25
Motor detection
Motor identification error
Check PED/motor and
PC/MMI/PED connections
/ restart motor
identification
32
Trip IGBT
Protection of the IGBT module
against overcurrent has been
triggered
Short circuit in the motor
or motor feed line /
controller settings
33
Overvoltage of
intermediate circuit
The maximum intermediate
circuit current has been
exceeded
Feedback by motor in
generating operation /
mains voltage too high /
faulty setting for
rotation speed control
Brake resistor not
connected or defective /
ramp times too short
34
Undervoltage of
intermediate circuit
The minimum intermediate
circuit current has not been
reached
Mains voltage too low,
mains connection
defective / check wiring
35
Excess motor
temperature
Motor PTC has been triggered
Overload of the motor
(e.g. high torque at low
motor speed) / ambient
temperature too high
36
Power failure
86
Possible cause/remedy
A phase is missing / mains
voltage has been disrupted
Operating manual PED
Error detection and troubleshooting
No.
Error name
Description of fault
Possible cause/remedy
38
Excess IGBT module
temperature
Excess IGBT module
temperature
Insufficient cooling, low
motor speed and high
torque, clocking
frequency too high
39
Overcurrent
Maximum output current of the
converter exceeded
Insufficient cooling, low
motor speed and high
torque, clocking
frequency too high /
ramp times too low /
brake not open
40
Excess frequency
inverter temperature
Inside temperature too high
Insufficient cooling, low
motor speed and high
torque, clocking
frequency too high
permanent overload /
reduce ambient
temperature / check fan
42
I2T motor safety shut-off
The internal I2T motor
protection (can be
parameterised) has been
triggered
Long-term overload
43
Ground leak
Ground leak during a motor
phase
Insulation error
45
Motor connection
disrupted
No motor current in spite of
control through frequency
inverter
No motor connected
46
Motor parameters
Plausibility check for motor
parameters failed
Parameter set not OK
47
Drive control
parameters
Plausibility check for drive
control parameters failed
Parameter set not OK
Please check the
parameters 33.001 and
34.010
48
Type plate data
No motor data entered.
Please enter the motor
data according to the
type plate
49
Power class restriction
Max. overload of the drive
Check application /
control exceeded for more than reduce load / use larger
60 sec.
drive control
Tab. 15: Error detection
Operating manual PED
87
Technical data
7 Technical data
7.1 General data
7.1.1
General technical data for 400V devices
This chapter contains the technical data.
Size
Rated motor power [kW]
(4-pin asynchr. motor)
MA
0.55
0.75
MB
1.1
1.5
2.2
3
MC
4
5.5
MD
7.5
11
Ambient temperature [°C]
-25 (non condensing) to +50 (without derating) *
Mains voltage [V]
3~ 400 -10% ... 480 +10%
Mains frequency [Hz]
47 to 63
Network configurations
Line current [A]
15
18.5
22
TN/TT
1.4
1.9
2.6
3.3
4.6
6.2
7.9
10.8
14.8
23.3
28.3
33.3
39.9
1.7
2.3
3.1
4.0
5.6
7.5
9.5
13.0
17.8
28.0
34.0
40.0
48.0
Nominal current, eff.
[IN at 8kHz/400 V]
Min. brake resistance [Ω]
100
Max. current, eff.
50
50
30
150% of the nominal current for 60 sec
Switching frequency [kHz]
130%
4, 8, 16, (factory setting 8)
Rotating field frequency [Hz]
0 - 400
2
Protective function
Undervoltage, overvoltage, I t restriction, short circuit, motor –inverter temperature, anti-tilt
protection, stall protection
Process control
PID controller, free configuration
Dimensions
233 x 153 x 120
270 x 189 x 140
307 x 223 x
181
414 x 294 x 232
3.9
5.0
8.7
21.0
[L x W x H] mm
Weight including adapter
plate [kg]
Protection type [IPxy]
EMC
65
55
approvals acc. to DIN EN 61800-3, class C2
Tab. 16: Technical data (technical changes reserved)
* in terms of the UL 508C standard, please see chapter 9.4!
88
Operating manual PED
Technical data
7.1.2
General technical data for 230V devices
Size
Rated motor power [kW]
(4-pin asynchr. motor)
MA
0.37
0.55
0.75
1.1
Ambient temperature [°C]
-10 (non condensing) to +40 (50 with derating) *
Mains voltage [V]
1~ 200 -10% ... 230 +10%
Mains frequency [Hz]
47 to 63
Network configurations
TN/TT
Line current [A]
4.5
5.6
6.9
9.2
2.3
3.2
3.9
5.2
Nominal current, eff.
[IN at 8kHz/400 V]
Min. brake resistance [Ω]
50
Max. current, eff.
of the nominal current for 60 sec
Switching frequency [kHz]
4, 8, 16, (factory setting 8)
Rotating field frequency [Hz]
0 - 400
Protective function
Undervoltage, overvoltage, I2t restriction, short circuit, motor –inverter temperature, anti-tilt
protection, stall protection
Process control
PID controller, free configuration
Dimensions
233 x 153 x 120
[L x W x H] mm
Weight including adapter
plate [kg]
3.9
Protection type [IPxy]
65
EMC
approvals acc. to DIN EN 61800-3, class C1
Tab. 17: Technical data (technical changes reserved)
* in terms of the UL 508C standard, please see chapter 9.4!
Designation
Function
Digital inputs 1–4
- Switching level low < 5 V / high > 15 V
- Imax (at 24 V) = 3 mA
- Rin = 8.6 kOhm
Analogue inputs 1, 2
- In +/- 10 V or 0–20 mA
- In 2–10 V or 4–20 mA
- Resolution 10 bits
- Rin = 10 kOhm
Digital outputs 1, 2
- Short-circuit proof
Operating manual PED
89
Technical data
Designation
Function
- Imax = 20 mA
Relays 1, 2
1 changeover contact (NO/NC)
maximum switching power *:
- at ohmic load (cos ϕ6= 1): 5 A at ~230 V or = 30 V
- under inductive load (cos ϕ6= 0.4 and L/R = 7 ms): 2 A at ~230 V
or
= 30 V
Maximum reaction time: 7 ms ± 0.5 ms
Electric life: 100 000 switching cycles
Analogue output 1
(current)
- Short-circuit proof
- Iout = 0.20 mA
- burden = 500 ohm
Analogue output 1
(voltage)
- Short-circuit proof
- Uout = 0..10 V
- lmax = 10 mA
Power supply 24 V
-
Power supply 10 V
- Auxiliary voltage U = 10 V DC
- short-circuit proof
- Imax = 30 mA
Auxiliary voltage U = 24V DC
short-circuit proof
Imax = 100 mA
external feeding of 24 V possible
Tab. 18: Specification of interfaces
* in terms of the UL 508C standard, the maximum allowed is 2 A!
7.2 Derating of output power
Drive controls of the PED series have two integrated PTC resistors as
standard which monitor both the heat sink temperature and the internal
temperature. As soon as a permissible IGBT temperature of 95°C or a
permissible internal temperature of 85°C is exceeded, the drive control
shuts down.
With the exception of the 22kW controller (size D 130%), all PED type
drive controls are designed for an overload of 150% for 60sec (every
10min). Reductions in the ability to handle overload and/or its duration
should be taken into account in the following circumstances:
– A clocking frequency permanently set too high >8kHz (loaddependent).
– A permanently increased heat sink temperature, caused by a
blocked air flow or a thermal blockage (dirty cooling ribs).
90
Operating manual PED
Technical data
– Depending on the type of assembly, permanently excessive ambient
temperature.
The respective max. output values can be determined from the following
characteristics curves.
7.2.1
Derating due to increased ambient temperature
max. Ausgangsstrom [%]
110%
100%
90%
80%
70%
60%
50%
-30
-20
-10
0
10
20
30
40
50
60
70
Umgebungstemperatur [°C]
Fig. 26:
Derating for drive control fitted on motor (all sizes)
max. Ausgangsstrom [%]
110%
100%
90%
80%
70%
60%
50%
-30
-20
-10
0
10
20
30
40
50
60
Umgebungstemperatur [°C]
Fig. 27:
Derating for drive control fitted on wall (sizes A - C)
Operating manual PED
91
Technical data
max. Ausgangsstrom [%]
110%
100%
90%
80%
70%
60%
50%
-30
-20
-10
0
10
20
30
40
50
60
70
Umgebungstemperatur [°C]
Fig. 28:
Derating for drive control fitted on wall (size C with fan option and size D)
7.2.2
Derating due to installation altitude
The following applies to all PED drive controls:
– No reduction in performance is needed in S1 mode up to 1000m
above sea level
– A reduction in performance of 1% every 100m is needed from 1000m
≥ 2000m. Overvoltage category 3 is observed!
– Overvoltage category 2 should be observed from 2000m ≥ 4000m
because of the lower air pressure!
In order to observe the overvoltage category:
– use external overvoltage protection in the PED's mains feed.
– reduce the input voltage.
Please contact the HERBORNER PUMPS Service department.
The respective max. output values can be determined from the following
characteristics curves.
92
Operating manual PED
Technical data
max. Ausgangsstrom [%]
110%
100%
90%
80%
70%
60%
50%
40%
0
500
1000
1500
2000
2500
3000
3500
4000
Höhe über NN [m]
Fig. 29:
Derating of maximum output current as a result of installation altitude
max. Eingangsspannung [%]
110%
100%
90%
80%
70%
60%
50%
40%
0
500
1000
1500
2000
2500
3000
3500
4000
Höhe über NN [m]
Fig. 30:
Derating of maximum input voltage as a result of installation altitude
7.2.3
Derating due to clocking frequency
The following diagram shows the output current, depending on clocking
frequency. To limit the thermal losses in the drive control, the output
current must be reduced.
Note: The clocking frequency is not reduced automatically!
The max. output values can be determined from the following
characteristics curve.
Operating manual PED
93
Optional accessories
120%
max. Ausgangsstrom [%]
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
2
4
6
8
10
12
14
16
Taktfrequenz [kHz]
Fig. 31:
Derating of maximum output current as a result of clocking frequency
8 Optional accessories
This chapter contains brief descriptions of the following optional
accessories
– Adapter plates
– Manual control unit MMI including connection cable RJ11 on plug M12
8.1 Adapter plates
8.1.1
Motor adapter plates
A standard motor adapter plate (with an integrated terminal board for
size A up to C) is available for each PED size.
PED size
A
B
C
D
Power [kW]
0.55 to 1.5
2.2 to 4
5.5 to 7.5
11.0 to 22.0
Designation
ADP MA MOT ADP MB MOT ADP MC MOT ADP MD MOT
0000 A00 000 1 0000 A00 000 1
0000 A00 000 1
0000 A00 000 1
The four holes for mounting the standard adapter plate on the motor are
introduced by Herborner pumps.
Below are technical drawings showing the possible locations of the holes
for each of the respective sizes.
94
Operating manual PED
Optional accessories
NOTE!
The following applies to size D PED drive controls:
An additional support is not necessarily needed in industrial use.
Fig. 32:
Hole pattern for size A standard adapter plate
Fig. 33:
Hole pattern for size B standard adapter plate
Operating manual PED
95
Optional accessories
Fig. 34:
Hole pattern for size C standard adapter plate
Fig. 35:
Hole pattern for size D standard adapter plate
If the existing flat seals are in a good condition, they should be reused.
96
Operating manual PED
Optional accessories
8.1.2
Wall adapter plates
A standard wall adapter plate (with an integrated terminal board for sizes
A to C) is available for each PED size.
Four holes for mounting the adapter plate, as well as an EMC screw
connection, are already present.
PED size
A
B
C
D
Power [kW]
0.55 to 1.5
2.2 to 4
5.5 to 7.5
11.0 to 22.0
Designation
ADP MA WDM
0000 A00 000 1
ADP MB WDM
0000 A00 000 1
ADP MC WDM
0000 A00 000 1
ADP MD WDM
0000 A00 000 1
Fig. 36:
Hole pattern for size A standard wall adapter plate
Operating manual PED
97
Optional accessories
Fig. 37:
Hole pattern for size B standard wall adapter plate
Fig. 38:
Hole pattern for size C standard wall adapter plate
98
Operating manual PED
Optional accessories
Fig. 39:
Hole pattern for size D standard wall adapter plate
Operating manual PED
99
Optional accessories
8.2 MMI manual control unit including a 3 m RJ11 connection
cable on an M12 plug
The MMI manual control unit is a purely industrial product (accessory)
which may only be used in conjunction with a PED! It is connected to the
integrated M12 interface of the PED. This operating unit allows the user
to write (program) and/or to visualise all the parameters of the PED. Up
to 8 complete data records can be stored in an MMI and copied to other
PEDs. As an alternative to the free PE-Drive software, complete
commissioning is available, external signals are not needed.
8.3 PC communication cable USB on M12 plug (converter
RS485/RS232 integrated)
As an alternative to the MMI manual control unit, a PED can also be put
into operation using the PC communication cable and the PE-Drive
software. The PE-Drive software is available free of charge from the
HERBORNER PUMPS homepage at www.herborner-pumps.com.
100
Operating manual PED
Guidelines, norms and standards
9 Guidelines, norms and standards
This chapter contains information about electromagnetic compatibility
(EMC), and guidelines, norms and standards. For binding information
about the relevant drive control approvals, please refer to the relevant
type plate!
9.1 EMC limit classes
Please note that EMC limit classes are only reached if the standard
switching frequency (clocking frequency) of 8 kHz is complied with.
Depending on the installation material used and/or extreme ambient
conditions, it might be necessary to use additional sheath wave filters
(ferrite rings). If the device is mounted on the wall, the length of the
shielded motor cables (with large surfaces on both sides) (max. 3 m) may
not exceed the permitted limits.
Wiring suitable for EMC also requires that EMC screw connections be used
on both sides (drive control and motor).
ATTENTION!
In a residential environment, this product can cause high-frequency
disruptions that may require interference suppression measures.
9.2 Classification acc. to IEC/EN 61800-3
The generic standard defines test procedures and severity levels for every
environment in the drive control category; these have to be complied
with.
Definition of environment
First environment (residential, commercial and industrial area):
All “areas” that are directly supplied by a public low-voltage connection,
such as:
– Residential area, e.g. houses, apartments etc.
– Retail area, e.g. shops, supermarkets
– Public institutions, e.g. theatres, stations
– Outside areas, e.g. petrol stations and parking areas
– Light industry, e.g. workshops, laboratories, small businesses
Operating manual PED
101
Guidelines, norms and standards
Second environment (industry):
Industrial surroundings with their own supply network that is separated
from the public low-voltage supply by a transformer.
9.3 Standards and guidelines
The following specifically apply:
– Directive on Electromagnetic Compatibility
(Directive 2004/108/EC of the Council EN 61800-3:2004)
– Low Voltage Directive
(Directive 2006/95/EC of the Council EN 61800-5-1:2003)
– Product standards list
9.4 Required markings for UL
Required markings
For installation on industrial machines in accordance with the Standard
for Industrial Machinery NFPA79 for recognised components, and NFPA70
for listed components, only. Please check the PED name plate for further
details.
Maximum ambient temperature:
Electronic
INV MA 2 0.37
INV MA 2 0.55
INV MA 2 0.75
INV MA 2 1.1
INV MA 4 1.5
INV MB 4 2.2
INV MB 4 3.0
INV MB 4 4.0
INV MC 4 5.5
INV MC 4 7.5
Adapter
ADP MA WDM
ADP MA WDM
ADP MA WDM
ADP MA WDM
ADP MA WDM
ADP MB WDM
ADP MB WDM
ADP MB WDM
ADP MC WDM
ADP MC WDM
Ambient
45°C
45°C
45°C
40°C
35°C
45°C
40°C
35°C
40°C
35°C
For listed parts (NFPA70):
Enclosure intended for use with field-installed conduit hubs, fittings or
closure plates UL approved in accordance with UL514B and CSA certified
in accordance with C22.2 No. 18, environmental type 1 or higher.
102
Operating manual PED
Guidelines, norms and standards
The PED is for use in pollution level 2 only.
Internal overload protection operates within 60 seconds of reaching 150%
of the motor full load current.
Suitable for use on a circuit capable of delivering no more than 5kA rms
symmetrical amperes, 230 volts for INV Mx 2 or 480 volts for INV Mx 4,
maximum when protected by fuses.
“Warning” – Use fuses rated 600V/10A for INV Mx 2 only.
“Warning” – Use fuses rated 600V/30A for INV MB 4 only.
“Warning” – Use fuses rated 600V/30A for INV MC 4 only.
Integral solid state short circuit protection does not provide branch
circuit protection. Branch circuit protection must be provided in
accordance with the manufacturer's instructions, national electrical code
and any additional local codes.
All wiring terminals marked to indicate proper connections for the power
supply, load and control circuitry.
The tightening, torque to connect the motor terminals, is 26 55 lb/in and
5.31 lb/in to connect the PTC.
For instructions for operator and servicing instructions on how to
mount and connect the products using the intended motor connection
adapter, please see sections 3.3 and 8.1.
Use 75oC copper wires only.
Connection of external motor over temperature sensing is required.
Operating manual PED
103
Guidelines, norms and standards
9.5 Quickstart guide
9.5.1
Quickstart guide for asynchronous motors
Plug the drive controller and
fasten it on the motor
Open the INVEOR
housing cocer
Connect L1, L2, L3, PE
to the clamps 1 – 4 on X1
Switch on the
line connector
communication
Installation
INVEORpc
PC
HMI
Option: cable (USB/M12)
Art.- no. 10023950
Option: MMI (RJ11/M12)
art.- no. 10004768
Motor name plate
asynchronous motor
Motor voltage
33.110
Enable software
Motor current
33.031
1.131
Start protect
1.132 disable
Motor power
33.032
Motor cos φ
33.111
Motor speed
33.034
+24V to Dig In1
clamp 6 on X5
Reference
Motor frequency
33.035
1.130
Enable hardware:
+24V to En.HW
clamp 10 on X5
Internal
Preset
reference
Autotune
Motor parameter
are calculated
Fig. 40:
104
External
Internal
potentiometer
Analogue input A.In 1/2
clamps 17/19 on X5
Fieldbus
Startup diagram for ASM
Operating manual PED
Guidelines, norms and standards
9.5.2
Quickstart guide for synchronous motors
Plug the drive controller and
fasten it on the motor
Open the INVEOR
housing cocer
Connect L1, L2, L3, PE
to the clamps 1 – 4 on X1
Switch on the
line connector
communication
Installation
INVEORpc
PC
HMI
Option: cable (USB/M12)
Art.- no. 10023950
Option: MMI (RJ11/M12)
art.- no. 10004768
Motor type 33.001
2: Synchronous motor
Control type
34.010 set to 200
Enable software
Motor current
33.031
Motor power
33.032
Start protect
1.132 disable
1.131
+24V to Dig In1
clamp 6 on X5
Motor speed
33.034
Reference
Motor frequency
33.035
1.130
External
Enable hardware:
+24V to En.HW
clamp 10 on X5
Internal
Autotune
Preset
reference
Analogue input A.In 1/2
clamps 17/19 on X5
Motor parameter
are calculated
n controller
34.090 / 34.091
Fig. 41:
Internal
potentiometer
Fieldbus
Startup diagram for SM
Operating manual PED
105
Guidelines, norms and standards
9.6 Parameter settings provided ex works
Number
Name
Value
33,001
Type of motor
1= Asynchronous motor
2= Synchronous motor
33,031
Motor current
Nominal motor current
(refer to the name plate)
33,032
Motor power
Nominal motor power
(refer to the name plate)
33,034
Motor speed
Nominal motor rotation
speed
(refer to the name plate)
33,035
Motor frequency
Nominal motor frequency
(refer to the name plate)
34,010
Type of control
100= asynchronous
200= synchronous
1,021
High speed
Nominal motor frequency
1,050
Deceleration
10s
1,051
Acceleration
10s
1,030
Reference channel
Internal potentiometer
5,070
Current limit
120%
5,071
Current limit
1s
Certain parameter settings and the changing of parameter settings during
operation can result in the PED drive control restarting automatically
after the supply voltage has failed, or in undesirable changes in the
operating behaviour.
106
Operating manual PED
10 List of key words
A
Accessories........................... 94
Ambient conditions ................. 20
Ambient temperature .............. 91
Analogue input ................. 34, 64
Analogue output ............... 34, 67
Automatic reset ..................... 58
B
Brake chopper ....................... 33
Brake resistor........................ 33
C
Cable screw connections ..... 20, 33
Cable shoes ..................... 22, 42
CE marking ............................ 7
Clocking frequency ................. 93
Commissioning ................. 10, 44
Communication ..................... 45
Connection cross-section .......... 23
Control connections ........... 33, 37
Control method ..................... 78
Control mode ........................ 55
Convection ........................... 37
D
Derating .............................. 90
Digital input ............... 34, 36, 66
Digital output.............. 34, 36, 68
Dimensional drawings ............... 5
Direction of rotation ............... 57
Disposal............................... 14
E
Electrical connection ......... 21, 30
EMC limit classes.................. 101
EMC screw connections ......24, 101
EMC standard ...................... 101
Enable software ..................... 56
Encoder ............................... 79
Energy-saving function ............ 50
Error detection ................. 83, 87
EU Declaration of Conformity ..... 7
Excess temperature ........... 86, 87
External fault ....................... 71
F
Factory setting...................... 52
Fan .................................... 20
FI protection switch ............... 10
Flying restart ........................ 79
Frequency setting mode .......... 48
G
Gearbox factor...................... 72
Ground protection ................. 22
H
High speed ........................... 53
HMI ................................... 100
I
I2T limit .............................. 77
Information .......................... 16
Installation ................. 21, 24, 37
Installation altitude ........... 20, 92
Installation instructions ........... 19
Installation location ............... 21
L
Leakage inductance................ 75
LED flash codes ..................... 83
Legal Notice ........................... 2
Low speed ........................... 53
M
Mains activation cycle ............. 11
Mains connection ................... 30
MMI.................................... 45
Motor ................................. 18
Motor adapter plates .............. 94
Motor cos φ .......................... 76
Motor current ....................... 74
Motor current limit ................ 71
Motor frequency .................... 75
Motor power ......................... 75
Motor speed ......................... 75
Motor voltage .................. 74, 76
Motorised potentiometer ......... 60
N
Norms .............................. 103
Number of automatic resets ...... 58
O
Operation ............................ 11
Optional accessories ............... 94
Overcurrent .......................... 87
Overload......................... 85, 86
Overvoltage ..................... 85, 86
P
Parameter set ....................... 85
Parameter set change ............. 73
Parameterisation ................... 47
Parameters .......................... 48
PC communication cable ........ 100
PID inverse ........................... 49
PID process control ................. 49
PID process controller ............. 61
Power save function................ 63
Preset speed ......................... 51
Preset speed mode ................. 59
Proper use ........................... 15
Protection class ................ 25, 28
Standards ........................... 102
Start protect ........................ 57
Stator inductance ............. 74, 76
Stator resistance ................... 75
Storage ................................. 9
Switching frequency ............... 78
System errors ....................... 85
T
Technical data ...................... 88
Terminal cross-section ............ 23
Transport .............................. 9
U
UL .................................... 102
Undervoltage ................... 85, 86
W
Wall adapter plates ................ 97
Wiring instructions ................. 23
Q
Quadratic characteristic .......... 81
Quickstart guide .................. 104
R
Ramps ............................ 53, 54
Reference channel ............ 55, 56
Regulations .......................... 15
Relay ............................. 35, 69
Repairs........................... 14, 83
Reset .................................. 58
Rotation speed ............ 34, 72, 75
S
Safety instructions................... 7
Sizes .................................... 5
Slip trimmer ......................... 80
SM field weakening ................. 81
SM startup procedure .............. 82
Speed control........................ 80
Stall detection ...................... 73
108
Operating manual PED

Documentos relacionados