SecuriFire
B3-REL16E
Relay board with 24 V contacts
The B3-REL16E board contains 16 bistable 24 V / 3 A relays.
Each relay output can be used as a VdS-compliant extinguishing
interface in connection with an input on the B3-IM8.
Fig. 1 B3-REL16E
Domain: SCP3000
____________________________________________________________________________________________________________________
Function/Application
Plug for relays (X2) and (X3)
The B3-REL16E has 16 freely programmable bistable 24V / 3A relays for connecting fire incident controls.
Defining whether the contact is a working or normally closed contact is done with planning software. Further, for each relay a “FailSafe-Position” can be defined for instances in which there is a
power failure or the SCP is switched off.
Plug X2
Designation
Relay R16
Relay R15
he connection to the B5-BAF / B5-MRI16 is on the rear side using
a 32-pin male connector via relay BUS. The peripheral devices are
connected on the front side of the board with two 16-pin plug-in
terminals.
Relay R14
Interfaces
Relay R13
X1 Connection to the relay BUS
X2 Connector plug for relays 9-16 (24V / 3A)
X3 Connector plug for relays 1-8
BR1-16
Relay R12
(24V / 3A)
Jumper for setting operation mode “Relay contact” or
“VdS-compliant interface”
Relay R11
Relay R10
Relay R9
Plug X3
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Designation
Terminal
1
Relay R8
2
3
Relay R7
4
5
Relay R6
6
7
Relay R5
8
9
Relay R4
10
11
Relay R3
12
13
Relay R2
14
15
Relay R1
16
Technical data X2 und X3
Relay design
bistable
Switching voltage
max. 30 V AC / 30 V DC
Switching current
max. 3 A
Breaking capacity
max. 60W (2 A at 30 V)
Contact protection
Small 3.15 A fuse with slow-acting triggering
Contact resistance
max. 30 mΩ
2
Mechanical
plug-in screw terminal, max. 2.5 mm
Jumper settings
With jumpers BR1 to BR16 you select “Relay output” or VdScompliant “Extinguishing” standard interface.
Fig. 2 B3-REL16E interfaces
Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland
4
2
4
2
3
1
3
1
Relay output
“Extinguishing” standard interface
T 811108 en d
1/3
Data sheet
Planning
The country-specific directives apply when planning and installing
automatic fire detector systems.
When connecting inductive loads, it is recommended to use a
freewheel diode (e.g. 1N4007).
The B3-REL16E can be fitted in the unit rack of each SecuriFire
3000 at slots 11 to 13 of the unit rack. However, a B5-BAF or B5MRI16 board must be fitted to slot 9.
B3-REL16E
X3
...
...
R4
R4
R3
R3
R2
R2
R1
R1
Defining whether the contact is a working or normally closed contact is done with planning software SecuriFire Studio. By programming an “Active in Fail-Safe-Position”, the state of each individual relay can be defined for power supply failure or shut down of
the SCP.
These are additionally fused for using the relay as a standard extinguishing interface, and the alarm resistors (680 Ω) and monitoring resistors (3.3 kΩ) are already installed.
Additionally, two inputs also have to be planned on the B3-IM8.
Holding magnet
+
_
4
2
3
1
The B3-REL16E is supported beginning with SecuriFire Studio
R 1.0.
B5-PSU
Connection examples
X5
Vext
GND
B3-REL16E
X3
...
...
R4
R4
R3
R3
R2
R2
R1
R1
Siren
+
Fig. 4 Connecting normally closed contact
4
2
3
1
B5-PSU
X5
Vext
GND
Fig. 3 Connecting working contact
2/3
T 811108 en d
B3-REL16E
Data sheet
Interface compliant with VDE 0833-2 and VdS 2496 standards for
connecting a fire alarm control panel to an electric control unit.
In the command direction, this is comprised of any output with
monitoring resistors (already included in the B3-REL16E). In the
alarm direction, this is comprised of two monitored inputs (B3-IM8).
The “Extinguishing” standard interface is NOT for directly actuating an extinguishing system!
The SecuriFire 3000 can be used either as a fire alarm control
panel or electrical control unit.
B3-REL16E
X3 (or X2)
Fault in
extinguishing
system
SST
3
1
B3-IM8
1 2 3
680R
3k3
4
2
X13
3
1
Fault in
extinguishing
system
Extinguishing
system triggered
B3-IM8
SST
1 2 3
X13
C
L
Extinguishing
system
triggered
4
2
FACP
C
L
3k3
3k3
680R
Extinguish
command
R4
R4
R3
R3
R2
R2
R1
R1
680R
EST
X3 (or X2)
...
...
...
...
R4
R4
R3
R3
R2
R2
R1
R1
B3-REL16E
Extinguish
command
C
L
max. 1000m
max. 1000m
Fig. 5 SecuriFire 3000 as fire alarm control panel
Fig. 6 SecuriFire 3000 as control unit
Article numbers / spare parts
Short designation
B3-REL16E
ST-SET REL16
ST-SET REL16 W
Relay board with 24 V contacts (incl. ST-SET REL16)
2 pcs. plug straight (frontal screwable)
2 pcs. plug angled
Art. number CH
115.979 066
239.972 312
239.239 690
Art. number
20-1000005-01-01
20-1040100-01-01
FG74105
Technical data
provided by the unit at slot 9 via the relay BUS
according to control panel
according to control panel
440/315 g
Power supply
Protection type
Ambient temperature, Relative humidity, Air pressure
Weight (gross/net)
B3-REL16E
T 811108 en d, 20.08.2015 Rd
First edition: 27.08.2010 Rd
The product specifications contained in this document are subject to change without notice.
© Copyright by Securiton
3/3

Documentos relacionados

Modulo reles GFE-MPX-REL

Modulo reles GFE-MPX-REL There is also a LED indication of ALARM condition for each individual zone. The LED RED indicator will be ON when the relay is active. These relay outputs are not monitored. The d.i.l switch allows...

Leia mais