Fronius Modbus Card, Register

Transcrição

Fronius Modbus Card, Register
/ Perfect Charging / Perfect Welding / Solar Energy
Fronius Modbus Card
Register Tables
42,0410,1885
010-25022015
DE
Beiblatt
Anlagenüberwachung
Leaflet
EN-US
Fronius Modbus Card
Register-Tabellen
System monitoring
0
DE
Inhaltsverzeichnis
Allgemeines ...............................................................................................................................................
Verwendete Abkürzungen.....................................................................................................................
Kommunikation mit dem Modbus Master..............................................................................................
Event Flags ...........................................................................................................................................
Register auslesen .................................................................................................................................
Nicht vorhandene Datensätze...............................................................................................................
Function Code 0x11 (Report Slave ID) .................................................................................................
Verfügbare Modelle...............................................................................................................................
Zeitverhalten der unterstützten Betriebsarten.......................................................................................
Vorzeichenkonvention für den Power Factor ........................................................................................
Auf der Karte gespeicherte Werte.........................................................................................................
Skalierungsfaktoren ..............................................................................................................................
Nicht beschreibbare Register................................................................................................................
Schreiben ungültiger Werte ..................................................................................................................
Inbetriebnahme ..........................................................................................................................................
Referenzspannung................................................................................................................................
Abweichung zur Referenzspannung .....................................................................................................
Uhrzeit einstellen ..................................................................................................................................
Fronius Register.........................................................................................................................................
Fronius Register....................................................................................................................................
Status-Code des Wechselrichters.........................................................................................................
Löschen der Event Flags und des Status-Codes..................................................................................
Neustart der Modbus Card....................................................................................................................
Firmware-Update .......................................................................................................................................
Allgemeines ..........................................................................................................................................
Übertragungsdauer ...............................................................................................................................
Übertragungssicherheit.........................................................................................................................
Übertragungsmodus .............................................................................................................................
Firmware-Update durchführen ..............................................................................................................
Baudrate einstellen ....................................................................................................................................
Allgemeines ..........................................................................................................................................
Baudrate und/oder Parität einstellen.....................................................................................................
Common & Inverter Model .........................................................................................................................
Common & Inverter Register ................................................................................................................
Modbus Geräte-ID einstellen .....................................................................................................................
Allgemeines ..........................................................................................................................................
Modbus Geräte-ID einstellen ................................................................................................................
Nameplate Model (IC120) ..........................................................................................................................
Allgemeines ..........................................................................................................................................
Nameplate Register ..............................................................................................................................
Basic Settings Model (IC121) ....................................................................................................................
Basic Settings Register.........................................................................................................................
Referenzspannung................................................................................................................................
Abweichung zur Referenzspannung .....................................................................................................
Abschaltgrenzen ...................................................................................................................................
Extended Measurements & Status Model (IC122).....................................................................................
Extended Measurements & Status Register .........................................................................................
Allgemeines ..........................................................................................................................................
Immediate Controls Model (IC123) ............................................................................................................
Allgemeines ..........................................................................................................................................
Immediate Controls Register ................................................................................................................
Standby.................................................................................................................................................
Leistungsreduktion................................................................................................................................
Beispiel: Leistungsreduktion einstellen .................................................................................................
Beispiel: Ändern der Rückkehrzeit bei aktiver Leistungsreduktion .......................................................
Auswirkungen der Blindleistungs-Vorgaben auf die Wirkleistung.........................................................
Konstanter Power Factor ......................................................................................................................
Beispiel: Konstanten Power Factor vorgeben.......................................................................................
Konstante relative Blindleistung............................................................................................................
Beispiel: Konstante Blindleistung vorgeben..........................................................................................
3
3
3
4
4
5
5
6
6
7
8
8
8
8
9
9
9
9
11
11
14
14
14
15
15
15
15
15
16
18
18
18
19
19
22
22
22
23
23
23
25
25
27
28
28
29
29
31
32
32
32
34
34
35
35
35
36
36
37
37
1
Volt-VAr Arrays (IC126) .............................................................................................................................
Allgemeines ..........................................................................................................................................
Kennlinien verwalten.............................................................................................................................
Kennlinien einstellen .............................................................................................................................
Beispiel .................................................................................................................................................
Volt-VAr Arrays Register.......................................................................................................................
Watt-PF Curve (IC131) ..............................................................................................................................
Allgemeines ..........................................................................................................................................
Kennlinien verwalten.............................................................................................................................
Kennlinien einstellen .............................................................................................................................
Beispiel .................................................................................................................................................
Watt-PF Curve Register........................................................................................................................
Volt-Watt Curve (IC132).............................................................................................................................
Allgemeines ..........................................................................................................................................
Kennlinien verwalten.............................................................................................................................
Kennlinien einstellen .............................................................................................................................
Beispiel .................................................................................................................................................
Volt-Watt Curve Register ......................................................................................................................
Event Flags ................................................................................................................................................
SunSpec Event Flags ...........................................................................................................................
Fronius Event Flags ..............................................................................................................................
2
38
38
38
39
40
40
44
44
44
45
46
46
50
50
50
51
52
52
56
56
56
DE
Allgemeines
Verwendete Abkürzungen
Kommunikation
mit dem Modbus
Master
AC
Wechselstrom
DC
Gleichstrom
FW
Firmware
MBC
Fronius Modbus Card
PF
Power Factor (cos )
PV
Photovoltaik
RTC
Echtzeit-Uhr
SF
Skalierungsfaktor
SW
Software
V
Spannung (Volt)
VA
Scheinleistung
VAr
Blindleistung
VMax
Maximale Spannung
VMin
Minimale Spannung
VRef
Referenzspannung
W
Leistung (Watt)
WR
Wechselrichter
Die Kommunikation der Fronius Modbus Card mit dem Modbus-Master erfolgt über Registeradressen entsprechend der SunSpec Spezifikation. Die Zuordnung der Registeradressen zur entsprechenden Funktion ist folgenden Tabellen zu entnehmen:
Fronius Register (Fronius Modbus Card Settings)
Common & Inverter Register (Common Block und Inverter Model)
Inverter Controls:
Nameplate (IC120)
Basic Settings (IC121)
Extended Measurements & Status (IC122)
Immediate Controls (IC123)
Volt-VAR (IC126)
Watt-PF (IC131)
Volt-Watt (IC132)
HINWEIS! Es wird empfohlen, zusammengehörige Werte immer in einer einzigen Modbus-Anfrage auszulesen. Sonst könnte es passieren, dass sich zwischen den Abfragen einer der beiden Werte ändert und die Daten somit nicht
korrekt sind.
zum Beispiel:
DC Leistung (40101, I_DC_Power) immer zusammen mit
Skalierungsfaktor (40102, I_DC_Power_SF)
3
Event Flags
Zustandsänderungen und Fehler des Wechselrichters werden als Event Flags dargestellt.
Die Zuordnung zu Ereignissen (engl. “Event“) oder zu den State Codes des Wechselrichters ist folgenden Tabellen zu entnehmen:
SunSpec Event Flags
Fronius Event Flags
HINWEIS! Es können auch mehrere State Codes zu einem Ereignis zusammengefasst sein.
Eine genaue Beschreibung der State Codes ist in der Bedienungsanleitung des betreffenden Wechselrichters zu finden.
Wenn der Wechselrichter einen State Code erzeugt, wird in der Fronius Modbus Card das
entsprechende Event Flag gesetzt.
Zusätzlich wird der entsprechende State Code auch in Register
INV_Active_State_Code (214) angezeigt.
Event Flag und State Code bleiben so lange aktiv, wie auch der State Code am Wechselrichter anliegt. Tritt ein weiterer State Code auf, wird dieser ebenfalls in den Event Flags
dargestellt. In diesem Fall kann es passieren, dass das vorherige Event Flag nicht gelöscht
wird.
Daher ist es möglich, die Event Flags und den State Code manuell zu löschen:
durch Schreiben von 0xFFFF1) in Register INV_Reset_All_Event_Flags (215).
1) Das
Register auslesen
Prefix "0x" steht für hexadezimale Zahlen
Um ein Register auszulesen muss in der Modbus-Anfrage die Startadresse des Registers
angegeben werden.
HINWEIS! Diese Adresse ist entsprechend der SunSpec Spezifikation immer um
1 geringer als die Registernummer.
Beispiel: Abfrage von 4 Registern ab Register 40005 (C_Manufacturer)
Senden (Bytes in Hexadezimal)
01
03
Geräte- Function
ID
Code
9C
44
00
04
Adresse 40004 Anzahl der aus(entspricht
zulesenden ReRegister 40005)
gister
2A
4C
Checksumme
Low
High
Byte
Byte
Empfangen (Bytes in Hexadezimal)
01
03
Geräte- Function
ID
Code
4
08
46
72
6F
6E
69
75
73
00
8A
2A
Anzahl Adresse 40005 Adresse 40006 Adresse 40007 Adresse 40008 Checksumme
Low
High
der By“F“ und “r“
“o“ und “n“
“i“ und “u“
“s“ und 0
Byte
Byte
tes
Fronius Wechselrichter können nicht immer alle Daten, die in den SunSpec-Datenmodellen spezifiziert sind, zur Verfügung stellen. Diese Daten werden je nach Datentyp laut
SunSpec Spezifikation durch folgende Werte dargestellt:
-
int16:
uint16:
acc16:
int32:
uint32:
acc32:
Strings:
enum16:
bitfield16:
pad:
1) Das
Function Code
0x11
(Report Slave ID)
0x80001)
0xFFFF
0x0000
0x80000000
0xFFFFFFFF
0x00000000
immer 0
0xFFFF
0xFFFF
0x8000
Prefix "0x" steht für hexadezimale Zahlen
Der Function Code 0x11 dient zum schnellen Auslesen der wichtigsten WechselrichterDaten.
1
0x11 an die entsprechende Fronius Modbus Card senden
2
Antwort kommt nicht als Registeradresse sondern in Form eines Paketes mit 24 Byte
Byte (Position)
Beschreibung
1. Datenbyte
Anzahl der Bytes = 21
entspricht der Anzahl der Datenbytes ab dem 4. Byte
2. Datenbyte
ID des Wechselrichters
3. Datenbyte
Status des Wechselrichters:
0xFF wenn WR läuft
0x00 wenn WR ausgeschaltet ist
Datenbyte 4 - 24
Hersteller und Wechselrichter-Typ als String mit
21 Zeichen (21 Bytes)
z. B.
"Fronius IG+150V"
der Rest auf die 21 Bytes wird mit 0x00 aufgefüllt
5
DE
Nicht vorhandene
Datensätze
Verfügbare Modelle
HINWEIS! Die Verwendung der SunSpec Inverter Control Models ist ab der Softwareversion 2.1.16 der Fronius Modbus Card möglich. Die tatsächliche Verfügbarkeit der verschiedenen Betriebsarten hängt jedoch vom Wechselrichter ab
(Software- und Hardwareversion).
Zur Verwendung des Modbus SunSpec Inverter Control Models mit der Fronius Modbus
Card ist ein Brain 2.0 notwendig, der bei folgenden Wechselrichtern eingebaut ist:
Fronius CL ab Seriennummer 24033431
mit Setup SI oder IT BT
Fronius IG Plus V ab Seriennummer 24031463
mit Setup IT BT, EXC EU, EU, EXC Int., SI
Fronius IG Plus Advanced (USA)
Folgende Modelle sind unabhängig von den Fähigkeiten des WR auf jeden Fall ab Softwareversion 2.1.16 der Fronius Modbus Card verfügbar:
Nameplate
Basic Settings
Extended Measurements & Status
Immediate Controls
Wenn der Wechselrichter die anderen Modelle (Volt-VAR, Watt-PF, Volt-Watt) nicht unterstützt, werden beim Auslesen die von der SunSpec Alliance spezifizierten "not implemented"-Werte zurückgeliefert.
Sollte ein Wechselrichter durch ein Update die Fähigkeit erhalten, auch die zusätzlichen
Betriebsarten anbieten zu können, so ist für die Fronius Modbus Card kein Update durchzuführen. Es muss jedoch ein Neustart der Fronius Modbus Card durchgeführt werden.
Für den Neustart der Fronius Modbus Card gibt es mehrere Möglichkeiten
durch Trennen der AC-Spannungsversorgung
durch das entsprechende Fronius-Register MBC_Reset (230)
Zeitverhalten der
unterstützten Betriebsarten
Zeitverhalten am Beispiel einer Leistungsreduktion
Das Zeitverhalten des Wechselrichters in einer Betriebsart kann durch mehrere Zeitwerte
festgelegt werden.
In der Abbildung “Zeitverhalten am Beispiel einer Leistungsreduktion“ sind die drei möglichen Zeitwerte dargestellt:
WinTms 0 - 300 [Sekunden]
gibt ein Zeitfenster an, in dem die Betriebsart zufällig gestartet wird. Das Zeitfenster
beginnt mit dem Startbefehl der Betriebsart (z.B. OutPFSet_Ena = 1).
6
-
HINWEIS! Die Daten aller unterstützten Betriebsarten werden auf der Fronius
Modbus Card gespeichert und sind auch nach einem AC-Reset der Fronius Modbus Card (Trennen oder Ausfall der AC-Spannungsversorgung) noch verfügbar.
Um ein korrektes Zeitverhalten auch nach einem AC-Reset gewährleisten zu können, muss unbedingt die Echtzeituhr (RTC = Real Time Clock) auf der Fronius
Modbus Card einmal eingestellt werden.
Die Echtzeituhr kann über folgende Register eingestellt werden:
40225 - 40226 => Abschnitt “Extended Measurements & Status Model (IC122)“
23 - 28 => Abschnitt “Fronius Register“
(+kVAr, +kVArh)
90°
Reactive Power
Exported/Received (W)
Power factor sign
convention
EEI: +
(Leading, capacitive)
(-kW, -kWh)
Reactive Power
Exported/Received (W)
180°
Quadrant 1
Power factor sign
convention
EEI: (Lagging, inductive)
Ap
pa
re
nt
Po
r
we
w
er
(V
A)
Ap
ϕ
p
e
ar
nt
Reactive Power
Exported/Received (W)
Quadrant 2
A)
(V
Po
ϕ
Active Power
Exported/Received (W)
Active Power
Exported/Received (W)
Active Power
Exported/Received (W)
Active Power
Exported/Received (W)
ϕ
er
nt
Ap
A)
(V
re
nt
w
Po
re
Po
we
r(
VA
)
pa
Ap
Power factor sign
convention
EEI: (Lagging, inductive)
Quadrant 3
ϕ
pa
(+kW, +kWh)
0°
Reactive Power
Exported/Received (W)
Vorzeichenkonvention für den
Power Factor
Power factor sign
convention
EEI: +
(Leading, capacitive)
270°
(-kVAr, -kVArh)
Quadrant 4
Die EEI-Vorzeichenkonvention1) für den Power Factor entspricht der SunSpec Spezifikation, und basiert auf den Angaben aus dem “Handbook for Electricity Metering“ und der
IEC 61557-12 (2007).
Der Power Factor ist:
negativ bei positiver Blindleistung (übererregt, Quadrant 1)
positiv bei negativer Blindleistung (untererregt, Quadrant 4)
7
DE
-
Mit WinTms kann verhindert werden, dass alle Wechselrichter in der Anlage die Änderungen gleichzeitig übernehmen. Bei 0 (Standardwert) startet die Betriebsart sofort.
RmpTms 0 (30) - 600 [Sekunden]
gibt vor, wie schnell die Änderungen durchgeführt werden sollen. Der entsprechende
Wert wird in der angegebenen Zeit schrittweise vom alten zum neuen Wert hin verändert.
Ist RmpTms = 0 (Standardwert) oder kleiner als 30 wird sofort auf den neuen Wert gesprungen.
RvrtTms 0 - 28800 [Sekunden]
bestimmt, wie lange die Betriebsart aktiv sein soll. Nach Ablauf der Zeit wird die Betriebsart automatisch beendet. Ist RvrtTms = 0 (Standardwert) bleibt die Betriebsart
so lange aktiv, bis er manuell über das entsprechende Register wieder deaktiviert
wird.
1)
EEI = Edison Electrical Institute
Auf der Karte gespeicherte Werte
Einige Daten für die verschiedenen Inverter Control Models, wie z. B. Abschaltgrenzen und
Kennlinienwerte, können nicht am Wechselrichter gespeichert werden. Diese Aufgabe
übernimmt die Fronius Modbus Card.
Einige dieser Werte sind speziell nur für den Wechselrichter, in dem die Fronius Modbus
Card verbaut ist, geeignet (z. B. Abschaltgrenzen). Diese Werte werden gelöscht, wenn
die Fronius Modbus Card in einem anderen Wechselrichter eingebaut wird, und neu vom
Wechselrichter ausgelesen.
Skalierungsfaktoren
Alle verwendeten Skalierungsfaktoren sind unveränderbare Werte und durch den Wechselrichter oder die Fronius Modbus Card vorgegeben. Daher sollte vor dem Schreiben von
Registerwerten der dazugehörige Skalierungsfaktor entweder aus der Anleitung entnommen oder direkt aus dem entsprechenden Register ausgelesen werden.
Nicht beschreibbare Register
Folgende Register können nicht beschrieben werden:
Read-Only (R) Register
aktuell nicht unterstützte Register
HINWEIS! Wird versucht solche Register zu beschreiben, gibt die Fronius Modbus Card keinen Exception Code zurück!
Die in diese Register geschriebenen Werte werden ohne Fehlermeldung von der
Fronius Modbus Card ignoriert.
Schreiben ungültiger Werte
8
Einige Register lassen nur bestimmte Werte zu. Die gültigen Werte sind der jeweiligen Register-Tabelle zu entnehmen.
Wird ein ungültiger Wert in ein Register geschrieben, so gibt die Fronius Modbus Card den
Exception Code 3 (Illegal Data Value) zurück. Der ungültige Wert wird ignoriert.
Werden mehrere Register auf einmal beschrieben, werden alle gültigen Werte bis zu dem
Register mit dem ungültigen Wert geschrieben. Anschließend wird der Schreibvorgang abgebrochen.
DE
Inbetriebnahme
Referenzspannung
VRef (40153)
Die Referenzspannung ist die Spannung an jenem gemeinsamen Anschlusspunkt, an welchem das lokale Netz mit dem öffentlichen Stromnetz verknüpft ist, und entspricht der
Nennspannung des Wechselrichters.
=> siehe Abbildung “Gemeinsamer Anschlusspunkt“
Bei der ersten Inbetriebnahme ermittelt die Fronius Modbus Card die Referenzspannung
automatisch aus den Spannungswerten der einzelnen Phasen des Wechselrichters.
Diese Methode ist jedoch ungenau und kann durch Schwankungen der Netzspannung
oder Spannungsabweichungen am Anschlusspunkt, z.B. bei einem 240 V Netz zu einer
VRef von 230 V führen.
Daher ist es notwendig, die korrekte Referenzspannung manuell an die Fronius Modbus
Card zu übergeben.
Die Angabe erfolgt in Volt im Bereich 0x00 (0) bis 0x190 (400)
Dieser Wert wird auf der Fronius Modbus Card gespeichert. Der Wert wird gelöscht, wenn
die Fronius Modbus Card in einen anderen Wechselrichter eingebaut wird.
Example Settings
= Electrical Connection Point (ECP)
VRefOfs = 4V
VRefOfs = 2V
Utility Power System
Local Bus
VRefOfs = 3V
Local Power
System with
Line Resistors
Point of Common
Coupling (PCC)
VRef = 120V
DER interconnections
Gemeinsamer Anschlusspunkt
Abweichung zur
Referenzspannung
VRefOfs (40154)
Je nach Verschaltung des lokalen Netzes kann es am Anschlusspunkt jedes einzelnen
Wechselrichters an das lokale Netz zu einer Abweichung zur Referenzspannung kommen
(siehe Abbildung “Gemeinsamer Anschlusspunkt“).
Wenn diese Abweichung bekannt ist, sollte sie angegeben werden. Bei den Betriebsarten
“Volt-Watt“ und “Volt-VAr“ werden dann die Spannungswerte von der Fronius Modbus
Card entsprechend angepasst.
Die Angabe erfolgt in Volt im Bereich 0xFFEC (-20) bis 0x14 (20). Das entspricht einer
möglichen Abweichung von -20 V bis +20 V.
Uhrzeit einstellen
Um ein korrektes Verhalten der zeitgesteuerten Betriebsarten auch nach einem AC-Reset
gewährleisten zu können, muss die Echtzeituhr (RTC = Real Time Clock) auf der Fronius
Modbus Card einmal eingestellt werden.
9
Die Echtzeituhr kann über folgende Register eingestellt werden:
Tms (40223 – 40224) im Extended Measurements & Status Model
Angabe von aktuellem Datum und Uhrzeit in Sekunden vom 1. Jänner 2000 00:00
(UTC) bis zur aktuellen Zeit
Wertebereich 0x00 (0) bis 0xFFFFFFF (4294967295)
-
10
MBC_Clock_Year (23) bis MBC_Clock_Seconds (28) in den Fronius Registern
MBC_Clock_Year (23)
Angabe des Jahres im Bereich 0x00 (2000) bis 0x63 (2099)
MBC_Clock_Month (24)
Angabe des Moats im Bereich 0x01 (1 = Jänner) bis 0x0C (12 = Dezember)
MBC_Clock_Day (25)
Angabe des Tages im Bereich 0x01 (1) bis 0x1F (31)
MBC_Clock_Hours (26)
Angabe der Stunde im Bereich 0x00 (0) bis 0x17 (23)
MBC_Clock_Minutes (27)
Angabe der Minuten im Bereich 0x00 (0) bis 0x3B (59)
MBC_Clock_Seconds (28)
Angabe der Sekunden im Bereich 0x00 (0) bis 0x3B (59)
DE
Fronius Register
String
(32)
1
16
16 R
0x03 MBC_ID
Modbus Card ID
17
17
1
R
0x03 MBC_FW_Ver- uint16
sion_Major
Firmware version of
MBC, major
18
18
1
R
0x03 MBC_FW_Ver- uint16
sion_Minor
Firmware version of
MBC, minor
19
19
1
R
0x03 MBC_FW_Ver- uint16
sion_Release
Firmware version of
MBC, release
20
21
2
RW 0x03 MBC_Baudrate uint32
0x06
0x10
22
22
1
RW 0x03 MBC_Parity
0x06
0x10
23
23
1
24
24
25
Baud
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Fronius Register
"Fronius Modbus-Card"
Baud rate
9600, 19200
uint16
Parity
0x00 Gerade
0x01 Ungerade
0x02 Keine
RW 0x03 MB0x06 C_Clock_Year
0x10
uint16
Date and Time: Year
0x00 (2000)
bis 0x63
(2099)
1
RW 0x03 MBC_Clock_0x06 Month
0x10
uint16
Date and Time: Month
0x01 (Jänner) bis
0x0C (Dezember)
25
1
RW 0x03 MB0x06 C_Clock_Day
0x10
uint16
Date and Time: Day
0x01 bis
0x1F
26
26
1
RW 0x03 MBuint16
0x06 C_Clock_Hours
0x10
Date and Time: Hours
0x00 bis
0x17
27
27
1
RW 0x03 MBC_Clock_0x06 Minutes
0x10
uint16
Date and Time: Minutes 0x00 bis
0x3B
28
28
1
RW 0x03 MBC_Clock_0x06 Seconds
0x10
uint16
Date and Time: Seconds
29
29
1
R
0x03 MBC_HW_Ver- uint16
sion_Major
Hardware version of
MBC, major
30
30
1
R
0x03 MBC_HW_Ver- uint16
sion_Minor
Hardware version of
MBC, minor
31
31
1
R
0x03 MBC_HW_Ver- uint16
sion_Assembly
Hardware version of
MBC, assembly
32
32
1
R
0x03 MBC_UID
uint16
Unique ID
33
33
1
R
0x03 MBC_Serial_1
uint16
Serial number of MBC
0x00 bis
0x3B
11
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
34
1
R
0x03 MBC_Serial_2
uint16
Serial number of MBC
35
35
1
R
0x03 MBC_Serial_3
uint16
Serial number of MBC
36
36
1
R
0x03 MBC_Serial_4
uint16
Serial number of MBC
37
37
1
R
0x03 MBC_Serial_5
uint16
Serial number of MBC
38
38
1
R
0x03 MBC_Common_Block_Major
uint16
SunSpec Common
Block version, major
derzeit 1
39
39
1
R
0x03 MBC_Common_Block_Minor
uint16
SunSpec Common
Block version, minor
derzeit 4
40
40
1
R
0x03 MBC_Inverter_- uint16
Model_Major
SunSpec Inverter Model derzeit 1
version, major
41
41
1
R
0x03 MBC_Inverter_- uint16
Model_Minor
SunSpec Inverter Model derzeit 1
version, minor
50
65
16 RW 0x03 Inverter_Seri0x10 al_Number
String
(32)
Serial number of inverter
100
101
2
RW 0x03 FW_CRC32
0x10
uint32
Checksumme über das
Update-File (bin) nach
CRC-32 (IEEE802.3)
102
103
2
RW 0x03 FW_Size
0x10
uint32
104
104
1
RW 0x03 FW_BlockNum- uint16
0x10 ber
Current block number
105
105
1
RW 0x03 FW_By0x10 tes_in_Block
uint16
Number of bytes in current block
106
106
1
RW 0x03 FW_Data_01
0x10
uint16
Firmware data
107
107
1
RW 0x03 FW_Data_02
0x10
uint16
Firmware data
108
108
1
RW 0x03 FW_Data_03
0x10
uint16
Firmware data
109
109
1
RW 0x03 FW_Data_04
0x10
uint16
Firmware data
110
110
1
RW 0x03 FW_Data_05
0x10
uint16
Firmware data
111
111
1
RW 0x03 FW_Data_06
0x10
uint16
Firmware data
112
112
1
RW 0x03 FW_Data_07
0x10
uint16
Firmware data
113
113
1
RW 0x03 FW_Data_08
0x10
uint16
Firmware data
114
114
1
RW 0x03 FW_Data_09
0x10
uint16
Firmware data
115
115
1
RW 0x03 FW_Data_10
0x10
uint16
Firmware data
End
Size
Start
34
12
Byte
Size of update file
1
RW 0x03 FW_Data_11
0x10
uint16
Firmware data
117
117
1
RW 0x03 FW_Data_12
0x10
uint16
Firmware data
118
118
1
RW 0x03 FW_Data_13
0x10
uint16
Firmware data
119
119
1
RW 0x03 FW_Data_14
0x10
uint16
Firmware data
120
120
1
RW 0x03 FW_Data_15
0x10
uint16
Firmware data
121
121
1
RW 0x03 FW_Data_16
0x10
uint16
Firmware data
122
122
1
RW 0x03 FW_Data_17
0x10
uint16
Firmware data
123
123
1
RW 0x03 FW_Data_18
0x10
uint16
Firmware data
124
124
1
RW 0x03 FW_Data_19
0x10
uint16
Firmware data
125
125
1
RW 0x03 FW_Data_20
0x10
uint16
Firmware data
126
126
1
RW 0x03 FW_Data_21
0x10
uint16
Firmware data
127
127
1
RW 0x03 FW_Data_22
0x10
uint16
Firmware data
128
128
1
RW 0x03 FW_Data_23
0x10
uint16
Firmware data
129
129
1
RW 0x03 FW_Data_24
0x10
uint16
Firmware data
130
130
1
RW 0x03 FW_Data_25
0x10
uint16
Firmware data
131
131
1
RW 0x03 FW_Data_26
0x10
uint16
Firmware data
132
132
1
RW 0x03 FW_Data_27
0x10
uint16
Firmware data
133
133
1
RW 0x03 FW_Data_28
0x10
uint16
Firmware data
134
134
1
RW 0x03 FW_Data_29
0x10
uint16
Firmware data
135
135
1
RW 0x03 FW_Data_30
0x10
uint16
Firmware data
136
136
1
RW 0x03 FW_Data_31
0x10
uint16
Firmware data
137
137
1
RW 0x03 FW_Data_32
0x10
uint16
Firmware data
138
138
1
R
uint16
Update status
0x03 FW_UpdateStatus
DE
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
116
End
Size
Start
116
see Firmware Update
13
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
214
1
R
215
215
1
RW 0x03 INV_Re0x06 set_All_E0x10 vent_Flags
uint16
Write 0xFFFF to reset all 0xFFFF
event flags and active
state code.
230
230
1
RW 0x03 Reset_MBC
0x06
0x10
uint16
Restart of MBC. First
write 0x002A, then immediately 0x0006.
End
Size
Start
214
0x03 INV_Actiuint16
ve_State_Code
Current active state
code of inverter - Description can be found in
inverter manual
Status-Code des
Wechselrichters
Das Register INV_Active_State_Code (214) zeigt den Status-Code des Wechselrichter
an der gerade aufgetreten ist. Dieser wird eventuell auch am Display des Wechselrichter
angezeigt. Dieser Code wird auch als Event Flag in den Registern 40110 bis 40021 dargestellt. Der angezeigte Code bleibt so lange aktiv bis der entsprechende Status nicht
mehr am Wechselrichter anliegt. Alternativ kann der Status auch per Register INV_Reset_All_Event_Flags gelöscht werden.
Löschen der
Event Flags und
des Status-Codes
Event Flags bleiben so lange aktiv bis der entsprechende Status nicht mehr am Wechselrichter anliegt. Es gibt einige wenige Ausnahmen, wo die Event Flags nicht mehr gelöscht
werden. Daher können die Event Flags und der angezeigte Status-Code per Modbus-Befehl zurückgesetzt werden.
1
0xFFFF in das Register INV_Reset_All_Event_Flags (215) schreiben
Der Inhalt folgender Register wird gelöscht:
INV_Active_State_Code (214)
I_Event_1 (40110)
I_Event_2 (40112)
I_Event_1_Vendor (40114) bis I_Event_4_Vendor (40120)
Neustart der Modbus Card
Über das Register Reset_MBC (230) kann ein Neustart der Fronius Modbus Card durchgeführt werden, ohne dass die AC-Versorgung unterbrochen werden muss.
1
0x002A ("*") in das Register Reset_MBC (230) schreiben
2
Innerhalb von 10 Sekunden danach 0x0006 ("ACK") in das selbe Register schreiben
Kurz darauf führt die Fronius Modbus Card einen Neustart durch. Daten gehen dabei nicht
verloren (z.B. gerade aktivierte Wechselrichter-Betriebsarten).
14
DE
Firmware-Update
Allgemeines
Ein Firmware-Update der Fronius Modbus Card kann über die Modbus-Schnittstelle durchgeführt werden. Die Register 100 bis 138 sind für das Firmware-Update spezifiziert.
Die neue Firmware wird als Binär-Datei (bin) ausgeliefert und beim Update zyklisch in Blöcken zu je 64 Bytes in die Register geschrieben.
Für das Update werden noch folgende Informationen benötigt
die Checksumme (CRC32) über die Datei
(muss nicht extra berechnet werden sondern wird im Dateinamen mitgeliefert)
die Größe der Datei in Bytes
Fronius bietet auf www.fronius.com ein Microsoft Windows-Tool für das Firmware-Update an.
Bei Verwendung des Update-Tools werden folgende Komponenten benötigt:
Ein Umsetzer von RS485 auf RS232 oder von RS485 auf USB
Die entsprechende Update-Datei (ebenfalls unter www.fronius.com erhältlich)
Übertragungsdauer
Die Übertragungsdauer der Firmware-Daten ist abhängig von der gewählten Baudrate und
beträgt bei 19200 Baud ca. 1 Minute.
Anschließend werden noch ca. 15 Sekunden benötigt, um die neue Firmware in den Mikrocontroller zu schreiben, diese zu prüfen und einen Neustart durchzuführen.
Danach ist die Fronius Modbus Card wieder einsatzbereit.
Übertragungssicherheit
Da die Fronius Modbus Card die empfangenen Firmware-Daten zuerst in ihrem externen
Flash-Speicher zwischenspeichert, kann eine fehlerhafte Übertragung nicht zu einem
Funktionsausfall der Karte führen. Im schlimmsten Fall müssen die Daten komplett neu
übertragen werden.
VORSICHT! Dauerhafte Fehlfunktion der Fronius Modbus Card möglich.
Das Schreiben des letzten Datenblocks vom externen Flash-Speicher in den Mikrocontroller darf nicht unterbrochen werden.
Diese kritische Phase dauert nur wenige Millisekunden. In diesem Zeitraum darf
die Spannungsversorgung nicht ausfallen.
Übertragungsmodus
Das Update kann nicht als Broadcast durchgeführt werden. Die Fronius Modbus Card antwortet auf jeden Schreibbefehl. Erhält der Master eine normale Modbus-Antwort, so bedeutet dies, dass die Daten korrekt verarbeitet wurden und der nächste Schreibbefehl
ausgeführt werden kann.
Schreibbefehle sind immer mit Function Code 0x101) durchzuführen.
Gibt es Probleme beim Schreiben der Daten, wird der Exception Code 4 zurückgesendet.
In diesem Fall muss das Update neu gestartet werden.
Bei Pausen von mehr als 30 Sekunden zwischen den Datenblöcken wird das Update automatisch abgebrochen und muss neu gestartet werden.
1)
Das Prefix "0x" steht für hexadezimale Zahlen
15
Firmware-Update
durchführen
1
Größe der Firmware-Datei in Bytes bestimmen
2
In die Register 102 und 103 (FW_Size) die Anzahl der Bytes schreiben
Beispiel: Bei 78080 Bytes wird 0x0001 in Register 102 und 0x3100 in Register
103 geschrieben
3
Auf Antwort warten
Normale Modbus-Antwort bedeutet, dass Daten korrekt geschrieben wurden und
nun die Firmware-Daten gesendet werden können.
Antwort mit Exception Code 4 bedeutet
Problem beim Schreiben der Register oder
zu sendende Firmware-Datei ist zu groß oder zu klein
In diesem Fall ist der Update-Vorgang ab Schritt 2 neu zu starten
4
In die Register 104 bis 137 schreiben
HINWEIS! Die Register 104 bis 137 sind mit einem einzigen Befehl zu beschreiben
–
–
In Register 104 (FW_BlockNumber) die Nummer des aktuellen Datenblocks
schreiben (beginnend bei 0 für den ersten)
In Register 105 (FW_Bytes_in_Block) die Anzahl der Bytes im aktuellen Block
schreiben
1
–
5
6
HINWEIS! Die Anzahl der Bytes kann im letzten Block von den üblichen
64 Bytes abweichen
Die Firmware-Daten in Blöcken zu 64 Bytes in die Register 106 bis 137 (FW_Data_01 bis FW_Data_32) schreiben
Auf Antwort warten
Normale Modbus-Antwort bedeutet, dass die Daten korrekt empfangen und zwischengespeichert wurden. Danach kann die Blocknummer um eins erhöht werden.
Antwort mit Exception Code 4 bedeutet
Problem beim Schreiben der Register oder
Anzahl der Bytes im Block stimmt nicht
In diesem Fall ist der Update-Vorgang ab Schritt 2 neu zu starten
HINWEIS! Wenn der Master keine Antwort erhält weil z. B. die Übertragung
zur Fronius Modbus Card fehlerhaft war, kann derselbe Block mit derselben
Blocknummer noch einmal gesendet werden
Schritte 4 und 5 wiederholen bis alle Datenblöcke korrekt übertragen wurden
7
Nach Erhalt der korrekten Antwort auf den letzten Datenblock die CRC32 Checksumme in die Register 100 und 101 (FW_CRC32) schreiben.
8
Auf Antwort warten
Normale Modbus-Antwort bedeutet, dass die Checksumme korrekt geschrieben
wurde und mit jener Checksumme übereinstimmt, die von der Fronius Modbus
Card über die Firmware-Daten berechnet wurde
Antwort mit Exception Code 4 bedeutet
Problem beim Schreiben der Register oder
Checksummen sind nicht gleich
In diesem Fall ist der Update-Vorgang ab Schritt 2 neu zu starten
9
Bei übereinstimmenden Checksummen beginnt die Fronius Modbus Card die neue
Firmware in den Mikrocontroller zu schreiben und führt anschließend einen Neustart
durch
HINWEIS! Der Kopiervorgang und der Neustart dauern ca. 15 Sekunden.
Während dieser Zeit ist die Fronius Modbus Card per Modbus nicht erreichbar.
Nach erfolgreich durchgeführtem Neustart ist die Fronius Modbus Card wieder einsatzbereit.
Der Update-Status kann über Register 138 (FW_UpdateStatus) abgefragt werden. Dieser
Status bleibt allerdings nur bis zu einem Reset der Fronius Modbus Card aufrecht. Alter16
Wert
Beschreibung
0x0000
Kein Update
0x0001
Update erfolgreich
0x0002
FW zu groß oder zu klein
0x0003
Falsche CRC
0x0004
Allgemeiner Fehler
0x0005
FW ist bereits die aktuellste
0x0006
FW nicht für Gerätetyp geeignet
0x0007
Länge des Datenblocks nicht korrekt
0x0008
Blocknummer zu hoch
0x0009
Blockreihenfolge nicht korrekt
0x000A
Kein Update-Vorgang, aber trotzdem Daten erhalten
0x000B
Kein Update-Vorgang, aber trotzdem CRC erhalten
0x000C
Letzten Block erwartet, aber nicht erhalten
0x000D
CRC des Copiers beim Schreiben falsch
0x000E
CRC des Copiers nach dem Schreiben falsch
0x000F
Falsche Version
0x0010
CRC nicht in der richtigen Reihenfolge erhalten
0x0011
Falsches CRC Format
0x0012
Flasches Image Size Format
0x0013
Falsches Datenblockformat
0x00FF
Update-Vorgang
17
DE
nativ kann auch die Version der Firmware abgefragt werden.
Die möglichen Werte des Registers 138 (FW_UpdateStatus) sind in der folgenden Tabelle
aufgelistet.
Baudrate einstellen
Allgemeines
Für die Baudrate der Fronius Modbus Card sind folgende Einstellungen möglich:
9600 Baud (Werkseinstellung)
19200 Baud
Für die Parität der Fronius Modbus Card sind folgende Einstellungen möglich:
gerade
ungerade
deaktiviert (Werkseinstellung)
Baudrate und/
oder Parität einstellen
Normalerweise wird für die Umstellung von Baudrate und/oder Parität eine Broadcast-Nachricht verwendet.
In diesem Fall werden die Einstellungen ohne Antwort von den Modbus-Teilnehmern
geändert
Innerhalb von 30 Sekunden müssen die neuen Werte bestätigt werden, indem dieselben Nachrichten noch einmal mit den neuen Einstellungen gesendet werden
Werden die Einstellungen nicht bestätigt, fallen alle beteiligten Fronius Modbus
Cards nach Ablauf der 30 Sekunden auf ihre ursprünglichen Einstellungen zurück
Werden die Einstellungen bestätigt, sind die neuen Werte auch im externen
Flash-Speicher abgelegt und somit auch nach einem Neustart der Fronius Modbus Card gültig
In Einzelfällen kann es auch notwendig sein Baudrate und/oder Parität für eine einzelne
Fronius Modbus Card zu ändern.
In diesem Fall wird die Antwort in der ursprünglichen Baudrate/Parität zurückgesendet. Erst danach werden die Einstellungen geändert.
Innerhalb von 30 Sekunden müssen die neuen Werte bestätigt werden, indem dieselben Nachrichten noch einmal mit den neuen Einstellungen gesendet werden
Werden die Einstellungen nicht bestätigt, fällt die Fronius Modbus Card nach Ablauf der 30 Sekunden auf ihre ursprünglichen Einstellungen zurück
Werden die Einstellungen bestätigt, sind die neuen Werte auch im externen
Flash-Speicher abgelegt und somit auch nach einem Neustart der Fronius Modbus Card gültig
Beispiel:
Eingestellt sind 9600 Baud und keine Parität
Ändern auf 19200 Baud und gerade Parität
1
19200 in Register MBC_Baudrate schreiben
2
0 (für gerade Parität) in Register MBC_Parity schreiben
3
Nach korrekter Antwort auf die neuen Einstellungen wechseln (19200, gerade) und
19200 und 0 noch einmal schreiben
Bei normaler Antwort wurden die Einstellungen übernommen.
18
DE
Common & Inverter Model
Type
Einheiten
0x03
C_SunSpec_ID
uint32
N/A
gibt an, dass es sich um eine
N/A gültige SunSpec Modbus Map 0x53756e53
handelt
40003 40003
1
RO
0x03
C_SunSpec_DID
uint16
N/A
gibt an, dass es sich um einen
N/A gültigen SunSpec Common
0x0001
Model Blockhandelt
40004 40004
1
RO
0x03
C_SunSpec_Length
uint16
Registers
40005 40020
16
RO
0x03
C_Manufacturer
String(32)
40021 40036
16
RO
0x03
C_Model
40037 40044
8
RO
0x03
40045 40052
8
RO
40053 40068
16
RO
40069 40069
Wertebereich
Beschreibung
Funktions Codes
RO
Name
R/W
2
Ende
40001 40002
Start
Größe
Skalierungs Faktor
Common & Inverter Register
N/A Länge des Models
65
N/A
N/A Herstellerbezeichnung
"Fronius"
String(32)
N/A
N/A Wechselrichter Type
z. B. "IG+150V"
C_Options
String(16)
N/A
N/A SW Version of Modbus Card
0x03
C_Version
String(16)
N/A
N/A Herstellerspezifischer Wert
0x03
C_SerialNumber
String(32)
N/A
N/A Herstellerspezifischer Wert
uint16
N/A
N/A Modbus ID
gibt an, dass es sich um eine
gültige SunSpec Inverter Modbus Map handelt
N/A
101, 102, 103
101: single phase
102: split phase
103: three phase
0x03
1 R/W 0x06
0x10
C_DeviceAddress
40070 40070
1
RO
0x03
C_SunSpec_DID
uint16
N/A
40071 40071
1
RO
0x03
C_SunSpec_Length
uint16
Registers
N/A Länge des Models
40072 40072
1
RO
0x03
I_AC_Current
uint16
A
_SF Summe AC Strom
40073 40073
1
RO
0x03
I_AC_CurrentA
uint16
A
_SF AC Strom Phase A
40074 40074
1
RO
0x03
I_AC_CurrentB
uint16
A
_SF AC Strom Phase B
40075 40075
1
RO
0x03
I_AC_CurrentC
uint16
A
_SF AC Strom Phase C
40076 40076
1
RO
0x03
I_AC_Current_SF
int16
SF
40077 40077
1
RO
0x03
I_AC_VoltageAB
uint16
V
_SF AC Spannung Phase AB
40078 40078
1
RO
0x03
I_AC_VoltageBC
uint16
V
_SF AC Spannung Phase BC
40079 40079
1
RO
0x03
I_AC_VoltageCA
uint16
V
_SF AC Spannung Phase CA
40080 40080
1
RO
0x03
I_AC_VoltageAN
uint16
V
_SF
AC Spannung Phase A-Nullleiter
40081 40081
1
RO
0x03
I_AC_VoltageBN
uint16
V
_SF
AC Spannung Phase B-Nullleiter
40082 40082
1
RO
0x03
I_AC_VoltageCN
uint16
V
_SF
AC Spannung Phase C-Nullleiter
40083 40083
1
RO
0x03
I_AC_Voltage_SF
int16
SF
N/A
Skalierungsfaktor AC Spannung
N/A Skalierungsfaktor AC Strom
SW Version of
Inverter
50
-10 bis +10
-10 bis +10
19
Type
Einheiten
Skalierungs Faktor
int16
W
_SF AC Einpeiseleistung
40085 40085
1
RO
0x03
I_AC_Power_SF
int16
SF
N/A
40086 40086
1
RO
0x03
I_AC_Frequency
uint16
Hz
_SF AC Frequenz
40087 40087
1
RO
0x03
I_AC_Frequency_SF
int16
SF
N/A Skalierungsfaktor
40088 40088
1
RO
0x03
I_AC_VA
int16
VA
_SF Scheinleistung
40089 40089
1
RO
0x03
I_AC_VA_SF
int16
SF
N/A Skalierungsfaktor
40090 40090
1
RO
0x03
I_AC_VAR
int16
Var
_SF Blindleistung
40091 40091
1
RO
0x03
I_AC_VAR_SF
int16
SF
N/A Skalierungsfaktor
40092 40092
1
RO
0x03
I_AC_PF
int16
%
_SF Leistungsfaktor
40093 40093
1
RO
0x03
I_AC_PF_SF
int16
SF
N/A Skalierungsfaktor
40094 40095
2
RO
0x03
I_AC_Energy_WH
uint32
Wh
_SF Gesamt eingespeiste Energie
40096 40096
1
RO
0x03
I_AC_Energy_WH_SF
int16
SF
N/A Skalierungsfaktor
40097 40097
1
RO
0x03
I_DC_Current
uint16
A
40098 40098
1
RO
0x03
I_DC_Current_SF
int16
SF
40099 40099
1
RO
0x03
I_DC_Voltage
uint16
V
40100 40100
1
RO
0x03
I_DC_Voltage_SF
int16
SF
N/A Skalierungsfaktor
40101 40101
1
RO
0x03
I_DC_Power
int16
W
_SF DC Leistung
40102 40102
1
RO
0x03
I_DC_Power_SF
int16
SF
N/A Skalierungsfaktor
40103 40103
1
RO
0x03
I_Temp_Cab
int16
°C
_SF Gehäuse Temperatur
40104 40104
1
RO
0x03
I_Temp_Sink
int16
°C
_SF Kühlkörper Temperatur
40105 40105
1
RO
0x03
I_Temp_Trans
int16
°C
_SF Trafo Temperatur
40106 40106
1
RO
0x03
I_Temp_Other
int16
°C
_SF Andere Temperatur
40107 40107
1
RO
0x03
I_Temp_SF
int16
SF
N/A Skalierungsfaktor
40108 40108
1
RO
0x03
I_Status
uint16
Name
20
Skalierungsfaktor AC Einpeiseleistung
-10 bis +10
-10 bis +10
-10 bis +10
-10 bis +10
-10 bis +10
-10 bis +10
_SF DC Strom
N/A Skalierungsfaktor
-10 bis +10
_SF DC Spannung
EnumeraN/A Betriebszustand
ted
Value
Wertebereich
Funktions Codes
I_AC_Power
Beschreibung
R/W
0x03
Name
Größe
RO
Ende
1
Start
40084 40084
Description
I_STATUS_OFF
1
Aus
I_STATUS_SLEEPING
2
In Betrieb (keine Einspeisung)
I_STATUS_STARTING
3
Hochlaufphase
I_STATUS_MPPT
4
Normalbetrieb
I_STATUS_THROTTLED
5
Leistungsreduktion
I_STATUS_SHUTTING_DOWN
6
Abschaltphase
I_STATUS_FAULT
7
Fehler vorhanden
I_STATUS_STANDBY
8
Standby
-10 bis +10
-10 bis +10
-10 bis +10
I_Status_Vendor
uint16
Name
DE
Wertebereich
Beschreibung
Skalierungs Faktor
0x03
Einheiten
Funktions Codes
RO
Type
R/W
1
Name
Größe
Ende
Start
40109 40109
EnumeraVendor Defined Operating
N/A
ted
State
Value
Description
I_STATUS_OFF
1
Aus
I_STATUS_SLEEPING
2
In Betrieb (keine Einspeisung)
I_STATUS_STARTING
3
Hochlaufphase
I_STATUS_MPPT
4
Normalbetrieb
I_STATUS_THROTTLED
5
Leistungsreduktion
I_STATUS_SHUTTING_DOWN
6
Abschaltphase
I_STATUS_FAULT
7
Fehler vorhanden
I_STATUS_STANDBY
8
Standby
I_STATUS_NO_BUSINIT
9
Keine Fronius Solar Net Kommunikation
I_STATUS_NO_COMM_INV
10
Keine Kommunikation mit Wechselrichter
I_STATUS_SN_OVERCURRENT
11
Überstrom am Fronius Solar Net Stecker erkannt
I_STATUS_BOOTLOAD
12
Wechselrichter-Update wird durchgeführt
I_STATUS_AFCI
13
AFCI Ereignis
40110 40111
2
RO
0x03
I_Event_1
uint32
Bitfield
N/A Event Flags (bits 0-31)
40112 40113
2
RO
0x03
I_Event_2
uint32
Bitfield
N/A Event Flags (bits 32-63)
40114 40115
2
RO
0x03
I_Event_1_Vendor
uint32
Bitfield
N/A
Vendor Defined Event Flags
(bits 0-31)
40116 40116
2
RO
0x03
I_Event_2_Vendor
uint32
Bitfield
N/A
Vendor Defined Event Flags
(bits 32-63)
40118 40119
2
RO
0x03
I_Event_3_Vendor
uint32
Bitfield
Vendor Defined Event Flags
N/A
(bits 64-95)
40120 40121
2
RO
0x03
I_Event_4_Vendor
uint32
Bitfield
N/A
siehe „SunSpec
Event Flags“
siehe „Fronius
Event Flags“
Vendor Defined Event Flags
(bits 96-127)
21
Modbus Geräte-ID einstellen
Allgemeines
Es gibt zwei Möglichkeiten, die Modbus Geräte-ID einer Fronius Modbus Card einzustellen:
mit den beiden Hexadezimal-Drehschaltern auf der Fronius Modbus Card
per Modbus mit Register 40069
HINWEIS! Für einen störungsfreien Betrieb muss die Modbus Geräte-ID auf einen Wert von 1 bis 247 (01 bis F7 hex) eingestellt sein.
Jede Modbus Geräte-ID darf in einem Modbus-System nur einmal vorkommen!
Modbus GeräteID einstellen
1
In Register 40069 (C_DeviceAddress) die neue Modbus Geräte-ID schreiben
2
Die Antwort der Fronius Modbus Card erfolgt noch über die ursprüngliche Modbus Geräte-ID
Normale Modbus-Antwort bedeutet, dass die Daten korrekt geschrieben wurden
und nun die neue Modbus Geräte-ID verwendet werden kann.
Wurde eine ungültige ID zugewiesen, wird eine Antwort mit Exception Code 3 zurückgeliefert. Die ID bleibt unverändert.
HINWEIS! Die neue Modbus Geräte-ID wird im externen Flash-Speicher abgelegt und ist auch nach einem Neustart gültig.
Bei einer Änderung an den Einstellrädern wird jedoch die dort eingestellte Modbus Geräte-ID wirksam.
22
DE
Nameplate Model (IC120)
Allgemeines
Dieses Modell entspricht einem Leistungsschild. Folgende Daten können ausgelesen werden:
DERType (40123)
Art des Geräts. Das Register liefert den Wert 4 zurück (PV-Gerät)
WRtg (40125)
Nennleistung des Wechselrichters
VARtg (40127)
Nenn-Scheinleistung des Wechselrichters
VArRtgQ1 (40129) - VArRtgQ4 (40132)
Nenn-Blindleistungswerte für die vier Quadranten
ARtg (40134)
Nennstrom des Wechselrichters
PFRtgQ1 (40136) – PFRtgQ4 (40139)
Minimale Werte für den Power Factor für die vier Quadranten
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Nameplate Register
40122 40122 1
R
0x03 ID
uint16
A well-known value 120. 120
Uniquely identifies this
as a SunSpec Nameplate Mode
40123 40123 1
R
0x03 L
uint16
40124 40124 1
R
0x03 DERTyp
enum16
40125 40125 1
R
0x03 WRtg
uint16
40126 40126 1
R
0x03 WRtg_SF
sunssf
40127 40127 1
R
0x03 VARtg
uint16
40128 40128 1
R
0x03 VARtg_SF
sunssf
40129 40129 1
R
0x03 VArRtgQ1
int16
var
VArRtg_SF
Continuous VAR capability of the inverter in
quadrant 1.
40130 40130 1
R
0x03 VArRtgQ2
int16
var
VArRtg_SF
Continuous VAR capability of the inverter in
quadrant 2.
Not supported
40131 40131 1
R
0x03 VArRtgQ3
int16
var
VArRtg_SF
Continuous VAR capability of the inverter in
quadrant 3.
Not supported
Registers
Length of Nameplate
Model
26
Type of DER device.
4
Default value is 4 to indicate PV device
W
WRtg_SF
Continuous power output capability of the inverter.
Scalefactor
VA
VARtg_SF
0
Continuous Volt-Ampere capability of the inverter.
Scale factor
0
23
Range of values
0x03 VArRtgQ4
int16
40133 40133 1
R
0x03 VArRtg_SF
sunssf
40134 40134 1
R
0x03 ARtg
uint16
40135 40135 1
R
0x03 ARtg_SF
sunssf
40136 40136 1
R
0x03 PFRtgQ1
int16
cos()
PFRtg_SF
Minimum power factor
capability of the inverter
in quadrant 1.
40137 40137 1
R
0x03 PFRtgQ2
int16
cos()
PFRtg_SF
Minimum power factor
Not supporcapability of the inverter ted
in quadrant 2.
40138 40138 1
R
0x03 PFRtgQ3
int16
cos()
PFRtg_SF
Minimum power factor
Not supporcapability of the inverter ted
in quadrant 3.
40139 40139 1
R
0x03 PFRtgQ4
int16
cos()
PFRtg_SF
Minimum power factor
capability of the inverter
in quadrant 4.
40140 40140 1
R
0x03 PFRtg_SF
sunssf
40141 40141 1
R
0x03 WHRtg
uint16
40142 40142 1
R
0x03 WHRtg_SF
sunssf
40143 40143 1
R
0x03 AhrRtg
uint16
40144 40144 1
R
0x03 AhrRtg_SF
sunssf
40145 40145 1
R
0x03 MaxChaRte
uint16
40146 40146 1
R
0x03 MaxChaRte_SF
sunssf
40147 40147 1
R
0x03 MaxDisChaRte uint16
40148 40148 1
R
0x03 MaxDisChaRte_SF
40149 40149 1
R
0x03 Pad
24
VArRtg_SF
Description
R
sunssf
var
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40132 40132 1
Continuous VAR capability of the inverter in
quadrant 4.
Scale factor
A
ARtg_SF
Maximum RMS AC current level capability of
the inverter.
Scale factor
Scale factor
Wh
WHRtg_SF
AhrRtg_SF
MaxCh
aRte_SF
Not supported
Not supported
Maximum rate of energy Not supportransfer into the storage ted
device.
Scale factor
W
-3
The useable capacity of Not supporthe battery. Maximum ted
charge minus minimum
charge from a technology capability perspective (Amp-hour capacity
rating).
Scale factor for amphour rating.
W
-2
Nominal energy rating of Not supporstorage device.
ted
Scale factor
AH
1
Not supported
Maximum rate of energy Not supporMaxDisCha transfer out of the stora- ted
Rte_SF ge device.
Scale factor
Pad register
Not supported
DE
Basic Settings Model (IC121)
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Basic Settings
Register
40150 40150 1
R
0x03 ID
uint16
A well-known value 121. 121
Uniquely identifies this
as a SunSpec Basic
Settings Model
40151 40151 1
R
0x03 L
uint16
Registers
40152 40152 1
R
0x03 WMax
uint16
W
VAMax_S
F
Setting for maximum power output. Default to
WRtg.
40153 40153 1
RW 0x03 VRef
0x06
0x10
uint16
V
VAMax_S
F
Voltage at the PCC.
40154 40154 1
RW 0x03 VRefOfs
0x06
0x10
int16
V
VRefOfs_S
F
Offset from PCC to inverter.
40155 40155 1
RW 0x03 VMax
0x06
0x10
uint16
V
VMinMax_S
F
Setpoint for maximum
voltage.
40156 40156 1
RW 0x03 VMin
0x06
0x10
uint16
V
VMinMax_S
F
Setpoint for minimum
voltage.
40157 40157 1
R
0x03 VAMax
uint16
VA
VAMax_S
F
Setpoint for maximum
apparent power. Default
to VARtg.
40158 40158 1
R
0x03 VARMaxQ1
int16
var
VARMax_S
F
Setting for maximum reactive power in quadrant
1. Default to VArRtgQ1.
40159 40159 1
R
0x03 VARMaxQ2
int16
var
VARMax_S
F
Setting for maximum re- Not supporactive power in quadrant ted
2. Default to VArRtgQ2.
40160 40160 1
R
0x03 VARMaxQ3
int16
var
VARMax_S
F
Setting for maximum re- Not supporactive power in quadrant ted
3 Default to VArRtgQ3.
40161 40161 1
R
0x03 VARMaxQ4
int16
var
VARMax_S
F
Setting for maximum reactive power in quadrant
4 Default to VArRtgQ4.
40162 40162 1
R
0x03 WGra
uint16
%
WMax/
min
WGra_
SF
Default ramp rate of ch- Not supporange of active power
ted
due to command or internal action.
Length of Basic Settings 30
Model
25
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40163 40163 1
R
0x03 PFMinQ1
int16
cos()
PFSetpoint for minimum
Min_SF power factor value in
quadrant 1. Default to
PFRtgQ1.
40164 40164 1
R
0x03 PFMinQ2
int16
cos()
PFSetpoint for minimum
Min_SF power factor value in
quadrant 2. Default to
PFRtgQ2.
Not supported
40165 40165 1
R
0x03 PFMinQ3
int16
cos()
PFSetpoint for minimum
Min_SF power factor value in
quadrant 3. Default to
PFRtgQ3.
Not supported
40166 40166 1
R
0x03 PFMinQ4
int16
cos()
PFSetpoint for minimum
Min_SF power factor value in
quadrant 4. Default to
PFRtgQ4.
40167 40167 1
R
0x03 VArAct
enum16
VAR action on change Not supporbetween charging and
ted
discharging: 1=switch
2=maintain VAR characterization.
40168 40168 1
R
0x03 ClcTotVA
enum16
Calculation method for
total apparent power.
1=vector 2=arithmetic.
40169 40169 1
R
0x03 MaxRmpRte
uint16
%
WGra
MaxRm Setpoint for maximum
Not supporpRramp rate as percentage ted
te_SF
of nominal maximum
ramp rate. This setting
will limit the rate that
watts delivery to the grid
can increase or decrease in response to intermittent PV generation.
40170 40170 1
R
0x03 ECPNomHz
uint16
Hz
ECPNomHz_SF
40171 40171 1
R
0x03 ConnPh
enum16
Identity of connected
Not supporphase for single phase ted
inverters. A=1 B=2 C=3.
40172 40172 1
R
0x03 WMax_SF
sunssf
Scale factor for maximum power output.
0
40173 40173 1
R
0x03 VRef_SF
sunssf
Scale factor for voltage
at the PCC.
0
40174 40174 1
R
0x03 VRefOfs_SF
sunssf
Scale factor for offset
voltage.
0
40175 40175 1
R
0x03 VMinMax_SF
sunssf
Scale factor for min/max 0
voltages.
40176 40176 1
R
0x03 VAMax_SF
sunssf
Scale factor for voltage
at the PCC.
26
Not supported
Setpoint for nominal fre- Not supporquency at the ECP.
ted
0
DE
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40177 40177 1
R
0x03 VARMax_SF
sunssf
Scale factor for reactive 1
power.
40178 40178 1
R
0x03 WGra_SF
sunssf
Scale factor for default
ramp rate.
Not supported
40179 40179 1
R
0x03 PFMin_SF
sunssf
Scale factor for minimum power factor.
-3
40180 40180 1
R
0x03 MaxRmpRte_SF
sunssf
Scale factor for maximum ramp percentage.
Not supported
40181 40181 1
R
0x03 ECPNomHz_SF
sunssf
Scale factor for nominal Not supporfrequency.
ted
Referenzspannung
VRef (40153)
Die Referenzspannung ist die Spannung an jenem gemeinsamen Anschlusspunkt, an welchem das lokale Netz mit dem öffentlichen Stromnetz verknüpft ist, und entspricht der
Nennspannung des Wechselrichters.
=> siehe Abbildung “Gemeinsamer Anschlusspunkt“
Bei der ersten Inbetriebnahme ermittelt die Fronius Modbus Card die Referenzspannung
automatisch aus den Spannungswerten der einzelnen Phasen des Wechselrichters.
Diese Methode ist jedoch ungenau und kann durch Schwankungen der Netzspannung
oder Spannungsabweichungen am Anschlusspunkt, z.B. bei einem 240 V Netz zu einer
VRef von 230 V führen.
Daher ist es notwendig, die korrekte Referenzspannung manuell an die Fronius Modbus
Card zu übergeben.
Die Angabe erfolgt in Volt im Bereich 0x00 (0) bis 0x190 (400)
Dieser Wert wird auf der Fronius Modbus Card gespeichert. Der Wert wird gelöscht, wenn
die Fronius Modbus Card in einen anderen Wechselrichter eingebaut wird.
Example Settings
= Electrical Connection Point (ECP)
VRefOfs = 4V
VRefOfs = 2V
Utility Power System
Local Bus
VRefOfs = 3V
Local Power
System with
Line Resistors
Point of Common
Coupling (PCC)
VRef = 120V
DER interconnections
Gemeinsamer Anschlusspunkt
27
Abweichung zur
Referenzspannung
VRefOfs (40154)
Je nach Verschaltung des lokalen Netzes kann es am Anschlusspunkt jedes einzelnen
Wechselrichters an das lokale Netz zu einer Abweichung zur Referenzspannung kommen
(siehe Abbildung “Gemeinsamer Anschlusspunkt“).
Wenn diese Abweichung bekannt ist, sollte sie angegeben werden. Bei den Betriebsarten
“Volt-Watt“ und “Volt-VAr“ werden dann die Spannungswerte von der Fronius Modbus
Card entsprechend angepasst.
Die Angabe erfolgt in Volt im Bereich 0xFFEC (-20) bis 0x14 (20). Das entspricht einer
möglichen Abweichung von -20 V bis +20 V.
Abschaltgrenzen
28
VMax (40155) und VMin (40156)
Mit diesen beiden Registern können die Abschaltgrenzen des Wechselrichters verändert
werden.
Die Ursprungswerte des Wechselrichters werden bei der ersten Inbetriebnahme von der
Fronius Modbus Card automatisch als Referenz gespeichert. Diese Werte stellen das
mögliche Maximum und Minimum dar.
Bei Einbau der Fronius Modbus Card in einen anderen Wechselrichter, werden diese Werte gelöscht und vom neuen Wechselrichter erneut automatisch eingelesen.
DE
Extended Measurements & Status Model (IC122)
40182 40182 1
R
0x03 ID
uint16
40183 40183 1
R
0x03 L
uint16
40184 40184 1
R
0x03 PVConn
40185 40185 1
R
40186 40186 1
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Extended Measurements & Status
Register
A well-known value 122. 122
Uniquely identifies this
as a SunSpec Measurements_Status Model
Registers
Length of Measurements_Status Model
44
bitfield16
PV inverter present/
available status. Enumerated value.
Bit 0:
Connected
Bit 1: Available
Bit 2: Operating
Bit 3: Test
0x03 StorConn
bitfield16
Storage inverter present/available status.
Enumerated value.
Not supported
R
0x03 ECPConn
bitfield16
ECP connection status: 0: Disdisconnected=0
connected
connected=1.
1: Connected
40187 40190 4
R
0x03 ActWh
acc64
Wh
AC lifetime active (real)
energy output.
40191 40194 4
R
0x03 ActVAh
acc64
VAh
AC lifetime apparent
energy output.
Not supported
40195 40198 4
R
0x03 ActVArhQ1
acc64
varh
AC lifetime reactive
energy output in quadrant 1.
Not supported
40199 40202 4
R
0x03 ActVArhQ2
acc64
varh
AC lifetime reactive
energy output in quadrant 2.
Not supported
40203 40206 4
R
0x03 ActVArhQ3
acc64
varh
AC lifetime negative
energy output in quadrant 3.
Not supported
40207 40210 4
R
0x03 ActVArhQ4
acc64
varh
AC lifetime reactive
energy output in quadrant 4.
Not supported
40211 40211 1
R
0x03 VArAval
int16
var
40212 40212 1
R
0x03 VArAval_SF
sunssf
VArAval_SF
Amount of VARs availa- Not supporble without impacting
ted
watts output.
Scale factor for available Not supporVARs.
ted
29
Range of values
0x03 WAval
uint16
40214 40214 1
R
0x03 WAval_SF
sunssf
Scale factor for available Not supporWatts.
ted
40215 40216 2
R
0x03 StSetLimMsk
bitfield32
Bit Mask indicating setpoint limit(s) reached.
Bits are persistent and
must be cleared by the
controller.
Not supported
40217 40218 2
R
0x03 StActCtl
bitfield32
Bit Mask indicating
which inverter controls
are currently active.
Bit 0: FixedW
Bit 1: FixedVAR
Bit 2: FixedPF
Bit 3: VoltVar
Bit 9: WattPF
Bit 10: VoltWatt
40219 40222 4
R
0x03 TmSrc
String (8)
Source of time synchro- RTC
nization.
40223 40224 2
RW 0x03 Tms
0x06
0x10
uint32
40225 40225 1
R
0x03 RtSt
bitfield16
40226 40226 1
R
0x03 Ris
uint16
40227 40227 1
R
0x03 Ris_SF
int16
Secs
WAval_SF
Description
R
30
W
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40213 40213 1
Amount of Watts availa- Not supporble.
ted
Seconds since 01-012000 00:00 UTC
Bit Mask indicating
which voltage ride through modes are currently active.
Ohm
Ris_SF Isolation resistance
Scale factor for Isolation
resistance
0
Dieses Modell liefert einige zusätzliche Mess- und Statuswerte, die das normale Inverter
Model nicht abdeckt:
-
PVConn (40184)
Dieses Bitfeld zeigt den Status des Wechselrichter an
Bit 0: Verbunden
Bit 1: Ansprechbar
Bit 2: Arbeitet (Wechselrichter speist ein)
-
ECPConn (40186)
Dieses Register zeigt den Verbindungsstatus zum Netz an
ECPConn = 1: Wechselrichter speist gerade ein
ECPConn = 0: Wechselrichter speist nicht ein
-
ActWH (40187 – 40190)
Wirkenergiezähler
-
StActCtl (40217 – 40218)
Bitfeld für zurzeit aktive Wechselrichter-Modi
Bit 0: Leistungsreduktion
Bit 1: konstante Blindleistungs-Vorgabe
Bit 2: Vorgabe eines konstanten Power Factors
Bit 3: Volt-VAr-Kennlinie
Bit 9: Watt-PF-Kennlinie
Bit 10: Volt-Watt-Kennlinie
-
TmSrc (40219 – 40222)
Quelle für die Zeitsynchronisation. Das Register liefert den String „RTC“ zurück. Eine
Echtzeituhr (RTC) auf der Fronius Modbus Card stellt dem Wechselrichter Uhrzeit und
Datum zur Verfügung
-
Tms (40223 – 40224)
Aktuelle Uhrzeit und Datum der RTC
Angegeben werden die Sekunden vom 1. Jänner 2000 00:00 (UTC) bis zur aktuellen
Zeit
HINWEIS! Datum und Uhrzeit können jedoch auch über die von Fronius eigens definierten Register 23 bis 28 eingestellt werden.
-
Ris (40226)
Isolationswiderstand
31
DE
Allgemeines
Immediate Controls Model (IC123)
Allgemeines
Mit den Immediate Controls können folgende Einstellungen am Wechselrichter vorgenommen werden:
Unterbrechung des Einspeisebetriebs des Wechselrichters (Standby)
Konstante Reduktion der Ausgangsleistung
Vorgabe eines konstanten Power Factors
Vorgabe einer konstanten relativen Blindleistung
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Immediate Controls Register
40228 40228 1
R
0x03 ID
uint16
40229 40229 1
R
0x03 L
uint16
Registers
Length of Immediate
Controls Model
40230 40230 1
RW 0x03 Conn_WinTms
0x06
0x10
uint16
Secs
Time window for
connect/disconnect.
40231 40231 1
RW 0x03 Conn_RvrtTms uint16
0x06
0x10
Secs
Timeout period for
connect/disconnect.
40232 40232 1
RW 0x03 Conn
0x06
0x10
bitfield16
40233 40233 1
RW 0x03 WMaxLimPct
0x06
0x10
uint16
%
WMax
40234 40234 1
RW 0x03 WMaxLimPc0x06 t_WinTms
0x10
uint16
Secs
Time window for power
limit change.
40235 40235 1
RW 0x03 WMaxLimPc0x06 t_RvrtTms
0x10
uint16
Secs
Timeout period for pow- 0 – 28800
er limit.
40236 40236 1
R
uint16
Secs
Ramp time for moving
from current setpoint to
new setpoint.
0 or 30 –
600
40237 40237 1
RW 0x03 WMaxLim_Ena enum16
0x06
0x10
Enumerated valued.
Throttle enable/disable
control.
0: Disabled
1: Enabled
40238 40238 1
RW 0x03 OutPFSet
0x06
0x10
32
0x03 WMaxLimPct_RmpTms
int16
A well-known value 123. 123
Uniquely identifies this
as a SunSpec Immediate Controls Model
Enumerated valued.
Connection control.
cos()
24
0: Disconnected
1: Connected
WMaxLi Set power output to spemPccified level.
t_SF
OutPF- Set power factor to speSet_SF cific value - cosine of
angle.
0 – 300
40240 40240 1
RW 0x03 OutPFSet_Rv0x06 rtTms
0x10
uint16
Secs
Timeout period for pow- 0 – 28800
er factor.
40241 40241 1
RW 0x03 OutPF0x06 Set_RmpTms
0x10
uint16
Secs
Ramp time for moving
from current setpoint to
new setpoint.
40242 40242 1
RW 0x03 OutPFSet_Ena enum16
0x06
0x10
40243 40243 1
R
40244 40244 1
DE
Range of values
Description
Units
Scale factor
Type
Name
Function codes
Time window for power
factor change.
R/W
Secs
Size
uint16
End
RW 0x03 OutPF0x06 Set_WinTms
0x10
Start
40239 40239 1
0 – 300
0 or 30 –
600
Enumerated valued. Fi- 0: Disabled
xed power factor enable/ 1: Enabled
disable control.
int16
%
WMax
VArW- Reactive power in
MaxPc- percent of WMax.
t_SF
RW 0x03 VArMaxPct
0x06
0x10
int16
% VArMax
VArPct_SF
Reactive power in
percent of VArMax.
40245 40245 1
R
int16
% VArAval
VArPct_SF
Reactive power in
percent of VArAval.
40246 40246 1
RW 0x03 VArPct_WinT0x06 ms
0x10
uint16
Secs
Time window for VAR li- 0 – 300
mit change.
40247 40247 1
RW 0x03 VArPct_RvrtT0x06 ms
0x10
uint16
Secs
Timeout period for VAR 0 – 28800
limit.
40248 40248 1
RW 0x03 VArPct_RmpT- uint16
0x06 ms
0x10
Secs
Ramp time for moving
from current setpoint to
new setpoint.
40249 40249 1
R
0x03 VArPct_Mod
enum16
Enumerated value. VAR 2: VAR limit
limit mode.
as a % of
VArMax
40250 40250 1
RW 0x03 VArPct_Ena
0x06
0x10
enum16
Enumerated valued. Fi- 0: Disabled
xed VAR enable/disable 1: Enabled
control.
40251 40251 1
R
0x03 WMaxLimPct_SF
sunssf
Scale factor for power
output percent.
0
40252 40252 1
R
0x03 OutPFSet_SF
sunssf
Scale factor for power
factor.
-3
40253 40253 1
R
0x03 VArPct_SF
sunssf
Scale factor for reactive 0
power.
0x03 VArWMaxPct
0x03 VArAvalPct
Not supported
Not supported
0 or 30 –
600
33
Standby
Conn_WinTms (40230) bis Conn (40232)
Diese Register dienen zur Steuerung des Standby Modus (kein Einspeisebetrieb) des
Wechselrichters.
Conn_WinTms (40230) und Conn_RvrtTms (40231)
Mit diesen Registern kann das Verhalten des Wechselrichters zeitlich gesteuert werden.
=> siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist für alle Register 0 vorgegeben.
Conn (40232)
Register Conn zeigt an, ob der Wechselrichter aktuell einspeist (0 = Standby, 1 = Einspeisebetrieb).
Um den Wechselrichter in den Standby zu schalten schreibt man in dieses Register
den Wert 0
Um den Wechselrichter wieder zu aktivieren schreibt man in dieses Register den Wert
1
HINWEIS! Ob der Wechselrichter einspeist oder nicht kann auch über das Register ECPConn aus dem Extended Measurements and Status Model ausgelesen
werden.
Leistungsreduktion
WMaxLimPct (40233) bis WMaxLim_Ena (40237)
Über diese Register kann beim Wechselrichter eine Reduktion der Ausgangsleistung eingestellt werden.
WMaxLimPct (40233)
In Register WMaxLimPct können Werte zwischen 0% und 100% eingetragen werden. Abhängig von der Software-Version des Wechselrichters können Werte kleiner als 10 zu einem erzwungenen Standby des Wechselrichters führen (kein Einspeisebetrieb).
Die Werte beschränken die maximal mögliche Ausgangsleistung des Gerätes, und haben
daher nicht unbedingt eine Auswirkung auf die aktuelle Leistung.
WMaxLimPct_WinTms (40234), WMaxLimPct_RvrtTms (40235) und WMaxLimPct_RmpTms (40236)
Mit diesen Registern kann das Verhalten des Wechselrichters für diese Betriebsart zeitlich
gesteuert werden. => siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist für alle Register 0 vorgegeben.
WMaxLim_Ena (40237)
Zum Starten und Beenden diese Betriebsart
Wert 1 in das Register WMaxLim_Ena schreiben = Betriebsart starten
Wert 0 in das Register WMaxLim_Ena schreiben = Betriebsart beenden
HINWEIS! Um bei einer aktiven Betriebsart Werte zu verändern (z. B. ein anderes Leistungslimit oder eine andere Rückkehrzeit einstellen), folgendermaßen
vorgehen:
neuen Wert in das entsprechende Register schreiben
die Betriebsart über Register WMaxLim_Ena erneut starten
34
1
Wert für die Reduktion der Ausgangsleistung in Register WMaxLimPct schreiben
(z. B. 30 für 30%)
2
Optional die Start- und Rückkehrzeit über Register WMaxLimPct_WinTms und
WMaxLimPct_RvrtTms einstellen
3
Optional die Übergangszeit über Register WMaxLimPct_RmpTms einstellen
=> siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“
4
Durch Schreiben von 1 in Register WMaxLim_Ena die Betriebsart starten
DE
Beispiel:
Leistungsreduktion einstellen
Beispiel:
Ändern der Rückkehrzeit bei aktiver
Leistungsreduktion
Leistungsreduktion ursprünglich mit WMaxLimPct_RvrtTms = 0 gestartet, das heißt die
Betriebsart muss manuell beendet werden.
Auswirkungen
der Blindleistungs-Vorgaben
auf die Wirkleistung
Die Abbildung “Blindleistung und Power Factor“ zeigt, welchen Einfluss die Einstellungen
an Blindleistung und Power Factor (cos phi) auf die Wirkleistung haben.
1
WMaxLimPct_RvrtTms auf z.B. 30 setzen
2
Durch Schreiben von 1 in Register WMaxLim_Ena Änderung übernehmen
– Betriebsart wird nach 30 Sekunden selbständig beendet.
Blindleistung und Power Factor
Legende:
W
Leistung
Wmax
Nennleistung
VAr
Blindleistung
VArmax
Nenn-Blindleistung
VArrel
relative Blindleistung (VAr/VArmax)
35
Konstanter Power
Factor
OutPFSet (40238) bis OutPFSet_Ena (40242)
Über diese Register kann beim Wechselrichter ein konstanter Power Factor vorgegeben
werden.
OutPFSet (40238)
In Register OutPFSet können positive und negative Werte für den Power Factor eingegeben werden
Die Werte sind mit Faktor 1000 zu skalieren
z.B. Power Factor 0,95 = Register-Wert 950
Die minimal möglichen Werte hängen vom Wechselrichter-Typ ab und können dem
Nameplate Model entnommen werden
HINWEIS! Der Wert für den Power Factor muss mit dem korrekten Vorzeichen
eingegeben werden => siehe Abschnitt “Vorzeichenkonvention für den Power
Factor“
positiv für untererregt
negativ für übererregt
Standardmäßig ist übererregt eingestellt.
OutPFSet_WinTms (40239), OutPFSet_RvrtTms (40240) und OutPFSet_RmpTms
(40241)
Mit diesen Registern kann das Verhalten des Wechselrichters für diese Betriebsart zeitlich
gesteuert werden. => siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist für alle Register 0 vorgegeben.
OutPFSet_Ena (40242)
Zum Starten und Beenden dieser Betriebsart
Wert 1 in das Register OutPFSet_Ena schreiben = Betriebsart starten
Wert 0 in das Register OutPFSet_Ena schreiben = Betriebsart beenden
HINWEIS! Um bei einer aktiven Betriebsart Werte zu verändern (z. B. ein anderen Power Factor oder eine andere Rückkehrzeit einstellen), folgendermaßen
vorgehen:
neuen Wert in das entsprechende Register schreiben
die Betriebsart über Register OutPFSet_Ena erneut starten
Beispiel:
Konstanten Power Factor vorgeben
36
1
Wert für den Power Factor in Register OutPFSet schreiben
(z. B. 950 für 0,95)
2
Optional die Start- und Rückkehrzeit über Register OutPFSet_WinTms und OutPFSet_RvrtTms einstellen
3
Optional die Übergangszeit über Register OutPFSet_RmpTms einstellen
=> siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“
4
Durch Schreiben von 1 in Register OutPFSet_Ena die Betriebsart starten
VArMaxPct (40244) bis VArPct_Ena (40250)
Über diese Register kann am Wechselrichter ein konstanter Wert für die Blindleistung eingestellt werden, die der Wechselrichter liefern soll.
HINWEIS! Im praktischen Betrieb wird die tatsächlich verfügbare Blindleistung
durch die Betriebsgrenzen des Wechselrichters vorgegeben. Deshalb kann die
Blindleistungs-Vorgabe nur dann erreicht werden, wenn ausreichend Wirkleistung eingespeist wird.
Wird zu wenig Wirkleistung eingespeist, arbeitet der Wechselrichter an der Betriebsgrenze.
VArMaxPct (40244)
zum Einstellen eines Wertes für die konstante Blindleistung
Die minimal und maximal möglichen Werte hängen vom Wechselrichter-Typ ab
VArPct_WinTms (40246), VArPct_RvrtTms (40247) und VArPct_RmpTms (40248)
Mit diesen Registern kann das Verhalten des Wechselrichters für diese Betriebsart zeitlich
gesteuert werden. => siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist für alle Register 0 vorgegeben.
VArPct_Mod (40249)
dieses Register kann nicht verändert werden
liefert die (derzeit) unterstützte Betriebsart zurück
Blindleistung in Prozent der maximal möglichen Blindleistung
VArPct_Ena (40250)
Zum Starten und Beenden dieser Betriebsart
Wert 1 in das Register VArPct_Ena schreiben = Betriebsart starten
Wert 0 in das Register VArPct_Ena schreiben = Betriebsart beenden
HINWEIS! Um bei einer aktiven Betriebsart Werte zu verändern (z. B. ein andere
Blindleistung oder eine andere Rückkehrzeit einstellen), folgendermaßen vorgehen:
neuen Wert in das entsprechende Register schreiben
die Betriebsart über Register VArPct_Ena erneut starten
Beispiel:
Konstante Blindleistung vorgeben
1
Wert für die relative Blindleistung in Register VArMaxPct schreiben
(z. B. 80 für 80%)
2
Optional die Start- und Rückkehrzeit über Register VArPct_WinTms und VArPct_RvrtTms einstellen
3
Optional die Übergangszeit über Register VArPct_RmpTms einstellen
=> siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“
4
Durch Schreiben von 1 in Register VArPct_Ena den Betriebsart starten
37
DE
Konstante relative Blindleistung
Volt-VAr Arrays (IC126)
Allgemeines
Die Volt-VAr-Kennlinie beeinflusst die relative Blindleistung (VAr) des Wechselrichters in
Abhängigkeit von der lokal gemessenen Netzspannung (V).
Von der Fronius Modbus Card werden 4 Kennlinien mit jeweils 4 Punkten unterstützt.
Zusätzlich kann die Änderung der Blindleistung über die Zeit definiert werden (VAr pro Minute), um sprunghafte Wechsel zwischen unterschiedlichen Betriebszuständen zu vermeiden.
VAr/VArmax
[%]
+ 100
60%
80
90
100
93
-60%
107 110
120
V/VRef
[%]
Die Abbildung zeigt eine beispielhafte
Kennlinie für die Betriebsart Volt-VAr.
In diesem Beispiel erfolgt in einem Bereich von +/- 7% der Nennspannung
kein Blindleistungs-Austausch.
Außerhalb dieses Bereiches ändert
sich die relative Blindleistung VAr/VArmax proportional zur Spannung bis ihr
Betrag bei +/-10% der Nennspannung
einen Betrag von 60% erreicht hat.
Im Spannungsbereich von +/-10% bis
zu den Abschaltgrenzen (-20% bzw.
+15% der Nennspannung) verharrt der
Blindleistungswert auf der letzten
Stützstelle.
- 100
HINWEIS! Im praktischen Betrieb wird die tatsächlich verfügbare Blindleistung
durch die Betriebsgrenzen des Wechselrichters vorgegeben. Deshalb kann die
Blindleistungs-Vorgabe aus der Volt-VAr-Kennlinie nur dann erreicht werden,
wenn ausreichend Wirkleistung eingespeist wird.
Wird zu wenig Wirkleistung eingespeist, arbeitet der Wechselrichter an der Betriebsgrenze.
Kennlinien verwalten
ActCrv (40256) bis RvrtTms (40259)
Über diese Register werden die Kennlinien verwaltet.
ActCrv (40256)
Mit diesem Register wird die aktive Volt-VAr-Kennlinie ausgewählt. Das ist jene Kennlinie, die beim Aktivieren der Betriebsart an den Wechselrichter übermittelt wird.
Gültige Werte sind 0 (keine Kennlinie) bis 4.
HINWEIS! Um die Volt-VAr-Betriebsart starten zu können, muss zuerst eine
Kennlinie ausgewählt werden.
ModEna (40257)
Zum Starten und Beenden dieser Betriebsart
Wert 1 in das Register ModEna schreiben = Betriebsart starten
Wert 0 in das Register ModEna schreiben = Betriebsart beenden
HINWEIS! Um bei einer aktiven Betriebsart Werte zu verändern (z. B. eine andere Kennlinie oder eine andere Rückkehrzeit einstellen), folgendermaßen vorgehen:
neuen Wert in das entsprechende Register schreiben
die Betriebsart über Register ModEna erneut starten
38
Kennlinien einstellen
Die Einstellung einer der 4 Kennlinien erfolgt über folgende Register:
Für Kennlinie 1
1_V1 (40268) bis 1_VAr4 (40275)
1_RmpDecTmm (40317)
1_RmpIncTmm (40318)
Für Kennlinie 2
2_V1 (40322) bis 2_VAr4 (40329)
2_RmpDecTmm (40371)
2_RmpIncTmm (40372)
Für Kennlinie 3
3_V1 (40376) bis 3_VAr4 (40383)
3_RmpDecTmm (40425)
3_RmpIncTmm (40426)
Für Kennlinie 4
4_V1 (40430) bis 4_VAr4 (40437)
4_RmpDecTmm (40479)
4_RmpIncTmm (40480)
HINWEIS! Zwischen den gleichbedeutenden Registern der einzelnen Kennlinien
liegen jeweils 54 Register.
Stellvertretend für die anderen einstellbaren Kennlinien wird hier nur Kennlinie 1
beschrieben.
1_V1 (40268) bis 1_VAr4 (40275)
1_V1, 1_V2, 1_V3 und 1_V4 = Spannungswerte in Prozent der Referenzspannung
VRef
1_VAr1, 1_VAr2, 1_VAr3 und 1_VAr4 = Blindleistungs-Werte in Prozent der maximalen Blindleistung VArMax
HINWEIS! Über das Register 1_DeptRef (Wert =2) ist definiert, dass die Blindleistung in Prozent der maximalen Blindleistung anzugegeben ist. Dieses Register ist schreibgeschützt.
1_RmpDecTmm (40317) und 1_RmpIncTmm (40318)
Diese Register definieren wie schnell der Wechselrichter bei Spannungsänderungen die
Blindleistung anpasst (Änderungsgeschwindigkeit der Blindleistung)
Die Angabe erfolgt in Prozent der max. Blindleistung pro Minute
1_RmpDec_Tmm für Reduzierung der Blindleistung
1_RmpInc_Tmm für Steigerung der Blindleistung
HINWEIS! In beide Register muss der selbe Wert geschrieben werden, da der
Wechselrichter in dieser Betriebsart immer den selben Wert für Steigerung und
Reduzierung verwendet.
39
DE
WinTms (40258) und RvrtTms (40259)
Mit diesen Registern kann das Verhalten des Wechselrichters für diese Betriebsart zeitlich
gesteuert werden. => siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist für alle Register 0 vorgegeben.
Beispiel
Im diesem Beispiel werden folgende Schritte behandelt:
Punkte der Kennlinie 1 verändern (entsprechend den Werten in der Abbildung)
Änderungsgeschwindigkeit der Blindleistung für Kennlinie 1 einstellen auf
50-fache max. Blindleistung pro Minute (5000% VArmax/Min)
VAr/VArmax
[%]
+ 100
1
Werte für die Spannung [% von VRef]
in folgende Register schreiben:
1_V1 (40268) = 90
1_V2 (40270) = 93
1_V3 (40272) = 107
1_V4 (40274) = 110
2
Werte für die Blindleistung [% von VArmax] in folgende Register schreiben:
1_VAr1 (40269) = 60
1_VAr2 (40271) = 0
1_VAr3 (40273) = 0
1_VAr4 (40275) = -60
60%
80
90
100
107 110
120
V/VRef
[%]
93
-60%
- 100
3
Werte für die Änderungsgeschwindigkeit in folgende Register schreiben:
1_RmpDecTmm (40317) = 5000
1_RmpIncTmm (40318) = 5000
4
Optional die Start- und Rückkehrzeit über Register WinTms (40258) und RvrtTms
(40259) einstellen
5
Durch Schreiben von 1 in Register ActCrv (40256) Kennlinie 1 auswählen
6
Durch Schreiben von 1 in Register ModEna (40257) die Betriebsart starten
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Volt-VAr Arrays
Register
40254 40254 1
R
0x03 ID
uint16
40255 40255 1
R
0x03 L
uint16
40256 40256 1
RW 0x03 ActCrv
0x06
0x10
uint16
Index of active curve.
0=no active curve.
40257 40257 1
RW 0x03 ModEna
0x06
0x10
bitfield16
Is Volt-VAR control acti- 0: Disabled
ve.
1: Enabled
40258 40258 1
RW 0x03 WinTms
0x06
0x10
uint16
40
A well-known value 126. 126
Uniquely identifies this
as a SunSpec Static
Volt-VAR Model
Registers
Secs
Length of Volt-VAR Mo- 226
del
Time window for voltVAR change.
0-4
0 – 300
DE
Range of values
Description
Units
Scale factor
Type
Name
Function codes
Timeout period for voltVAR curve selection.
40260 40260 1
R
0x03 RmpTms
uint16
Secs
The time of the PT1 in
Not supporseconds (time to accom- ted
plish a change of 95%).
40261 40261 1
R
0x03 NCrv
uint16
Number of curves supported.
4
40262 40262 1
R
0x03 NPt
uint16
Maximum number of
points in array.
4
40263 40263 1
R
0x03 V_SF
sunssf
Scale factor for percent
VRef.
0
40264 40264 1
R
0x03 DeptRef_SF
sunssf
Scale factor for dependent variable.
0
40265 40265 1
R
0x03 RmpIncDec_SF sunssf
Scale factor for in0
crement and decrement
ramps.
40266 40266 1
R
0x03 1_ActPt
uint16
Curve 1. Number of acti- 4
ve points in array.
40267 40267 1
R
0x03 1_DeptRef
enum16
Curve 1. Meaning of de- 2: % of VArpendent variable.
Max
40268 40268 1
RW 0x03 1_V1
0x06
0x10
uint16
% VRef V_SF
40269 40269 1
RW 0x03 1_VAr1
0x06
0x10
int16
% VArMax
40270 40270 1
RW 0x03 1_V2
0x06
0x10
uint16
% VRef V_SF
40271 40271 1
RW 0x03 1_VAr2
0x06
0x10
int16
% VArMax
40272 40272 1
RW 0x03 1_V3
0x06
0x10
uint16
% VRef V_SF
40273 40273 1
RW 0x03 1_VAr3
0x06
0x10
int16
% VArMax
40274 40274 1
RW 0x03 1_V4
0x06
0x10
uint16
% VRef V_SF
40275 40275 1
RW 0x03 1_VAr4
0x06
0x10
int16
% VArMax
40276 40276 1
R
uint16
% VRef V_SF
R/W
Secs
Size
uint16
End
RW 0x03 RvrtTms
0x06
0x10
Start
40259 40259 1
0x03 1_V5
0 – 28800
Curve 1, Point 1 Volts.
DeptRe Curve 1, Point 1 VARs.
f_SF
Curve 1, Point 2 Volts.
DeptRe Curve 1, Point 2 VARs.
f_SF
Curve 1, Point 2 Volts.
DeptRe Curve 1, Point 3 VARs.
f_SF
Curve 1, Point 4 Volts.
DeptRe Curve 1, Point 4 VARs.
f_SF
Curve 1, Point 5 Volts.
Not supported
41
R
0x03 1_VAr5
int16
% VArMax
40278 40278 1
R
0x03 1_V6
uint16
% VRef V_SF
40279 40279 1
R
0x03 1_VAr6
int16
% VArMax
40280 40280 1
R
0x03 1_V7
uint16
% VRef V_SF
40281 40281 1
R
0x03 1_VAr7
int16
% VArMax
40282 40282 1
R
0x03 1_V8
uint16
% VRef V_SF
40283 40283 1
R
0x03 1_VAr8
int16
% VArMax
40284 40284 1
R
0x03 1_V9
uint16
% VRef V_SF
40285 40285 1
R
0x03 1_VAr9
int16
% VArMax
40286 40286 1
R
0x03 1_V10
uint16
% VRef V_SF
40287 40287 1
R
0x03 1_VAr10
int16
% VArMax
40288 40288 1
R
0x03 1_V11
uint16
% VRef V_SF
40289 40289 1
R
0x03 1_VAr11
int16
% VArMax
40290 40290 1
R
0x03 1_V12
uint16
% VRef V_SF
40291 40291 1
R
0x03 1_VAr12
int16
% VArMax
40292 40292 1
R
0x03 1_V13
uint16
% VRef V_SF
40293 40293 1
R
0x03 1_VAr13
int16
% VArMax
40294 40294 1
R
0x03 1_V14
uint16
% VRef V_SF
40295 40295 1
R
0x03 1_VAr14
int16
% VArMax
40296 40296 1
R
0x03 1_V15
uint16
% VRef V_SF
40297 40297 1
R
0x03 1_VAr15
int16
% VArMax
40298 40298 1
R
0x03 1_V16
uint16
% VRef V_SF
40299 40299 1
R
0x03 1_VAr16
int16
% VArMax
42
DeptRe Curve 1, Point 5 VARs.
f_SF
Curve 1, Point 6 Volts.
DeptRe Curve 1, Point 6 VARs.
f_SF
Curve 1, Point 7 Volts.
DeptRe Curve 1, Point 7 VARs.
f_SF
Curve 1, Point 8 Volts.
DeptRe Curve 1, Point 8 VARs.
f_SF
Curve 1, Point 9 Volts.
DeptRe Curve 1, Point 9 VARs.
f_SF
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40277 40277 1
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Curve 1, Point 10 Volts. Not supported
DeptRe Curve 1, Point 10 VARs. Not supporf_SF
ted
Curve 1, Point 11 Volts. Not supported
DeptRe Curve 1, Point 11 VARs. Not supporf_SF
ted
Curve 1, Point 12 Volts. Not supported
DeptRe Curve 1, Point 12 VARs. Not supporf_SF
ted
Curve 1, Point 13 Volts. Not supported
DeptRe Curve 1, Point 13 VARs. Not supporf_SF
ted
Curve 1, Point 14 Volts. Not supported
DeptRe Curve 1, Point 14 VARs. Not supporf_SF
ted
Curve 1, Point 15 Volts. Not supported
DeptRe Curve 1, Point 15 VARs. Not supporf_SF
ted
Curve 1, Point 16 Volts. Not supported
DeptRe Curve 1, Point 16 VARs. Not supporf_SF
ted
DE
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40300 40300 1
R
0x03 1_V17
uint16
% VRef V_SF
40301 40301 1
R
0x03 1_VAr17
int16
% VArMax
40302 40302 1
R
0x03 1_V18
uint16
% VRef V_SF
40303 40303 1
R
0x03 1_VAr18
int16
% VArMax
40304 40304 1
R
0x03 1_V19
uint16
% VRef V_SF
40305 40305 1
R
0x03 1_VAr19
int16
% VArMax
40306 40306 1
R
0x03 1_V20
uint16
% VRef V_SF
40307 40307 1
R
0x03 1_VAr20
int16
% VArMax
40308 40315 8
R
0x03 1_CrvNam
String
(16)
40316 40316 1
R
0x03 1_RmpTms
uint16
Secs
40317 40317 1
RW 0x03 1_RmpDecT0x06 mm
0x10
uint16
% VArMax /
min
RmpIn- Curve 1. The maximum 60-12000
cDec_S rate at which the VAR
0: as fast as
F
value may be reduced in possible
response to changes in
the voltage value.
40318 40318 1
RW 0x03 1_RmpIncTmm uint16
0x06
0x10
% VArMax /
min
RmpIn- Curve 1. The maximum 60-12000
cDec_S rate at which the VAR
0: as fast as
F
value may be increased possible
in response to changes
in the voltage value.
40319 40319 1
R
0x03 1_ReadOnly
enum16
Curve 1, Point 17 Volts. Not supported
DeptRe Curve 1, Point 17 VARs. Not supporf_SF
ted
Curve 1, Point 18 Volts. Not supported
DeptRe Curve 1, Point 18 VARs. Not supporf_SF
ted
Curve 1, Point 19 Volts. Not supported
DeptRe Curve 1, Point 19 VARs. Not supporf_SF
ted
Curve 1, Point 20 Volts. Not supported
DeptRe Curve 1, Point 20 VARs. Not supporf_SF
ted
Curve 1. Optional deNot supporscription for curve. (Max ted
16 chars)
Curve 1. The time of the Not supporPT1 in seconds (time to ted
accomplish a change of
95%).
Boolean flag indicates if 0: ReadWricurve is read-only or can te
be modified.
1: ReadOnly
40320 40373 Values of curve 2
Register offset 54 to curve 1
Name with prefix “2_“
40374 40427 Values of curve 3
Register offset 108 to curve 1
Name with prefix “3_“
40428 40481 Values of curve 4
Register offset 162 to curve 1
Name with prefix “4_“
43
Watt-PF Curve (IC131)
Allgemeines
Die Watt-PF-Kennlinie beeinflusst das Blindleistungs-Verhalten des Wechselrichters über
den Power Factor (PF) in Abhängigkeit von der Wirkleistung.
Von der Fronius Modbus Card werden 4 Kennlinien mit jeweils 4 Punkten unterstützt.
Zusätzlich kann die Änderung des Verschiebungsfaktors über die Zeit definiert werden,
um sprunghafte Wechsel zwischen unterschiedlichen Betriebszuständen zu vermeiden.
PF
0.9
Overexcited
20
40
80
60
100
1
46
-0.9
Underexcited
Kennlinien verwalten
74
W/Wmax
[%]
Die Abbildung zeigt eine beispielhafte
Kennlinie für die Betriebsart Watt-PF.
In diesem Beispiel erfolgt bis zu 40 %
der Nennwirkleistung ein Blindleistungs-Austausch mit einem PF von 0,9
übererregt.
Darüber nimmt der PF linear zu.
Zwischen 46% und 74% der NennWirkleistung erfolgt kein Blindleistungsaustausch (Totband, PF = 1).
Darüber nimmt der PF linear ab, bis er
bei 80% der Nenn-Wirkleistung einen
Wert von 0,9 untererregt erreicht hat.
ActCrv (40484 bis RvrtTms (40487)
Über diese Register werden die Kennlinien verwaltet.
ActCrv (40484)
Mit diesem Register wird die aktive Watt-PF-Kennlinie ausgewählt. Das ist jene Kennlinie, die beim Aktivieren der Betriebsart an den Wechselrichter übermittelt wird.
Gültige Werte sind 0 (keine Kennlinie) bis 4.
HINWEIS! Um den Watt-PF-Betriebsart starten zu können, muss zuerst eine
Kennlinie ausgewählt werden.
ModEna (40485)
Zum Starten und Beenden dieser Betriebsart
Wert 1 in das Register ModEna schreiben = Betriebsart starten
Wert 0 in das Register ModEna schreiben = Betriebsart beenden
HINWEIS! Um bei einer aktiven Betriebsart Werte zu verändern (z. B. eine andere Kennlinie oder eine andere Rückkehrzeit einstellen), folgendermaßen vorgehen:
neuen Wert in das entsprechende Register schreiben
die Betriebsart über Register ModEna erneut starten
WinTms (40486) und RvrtTms (40487)
Mit diesen Registern kann das Verhalten des Wechselrichters für diese Betriebsart zeitlich
gesteuert werden. => siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist für alle Register 0 vorgegeben.
44
Die Einstellung einer der 4 Kennlinien erfolgt über folgende Register:
Für Kennlinie 1
1_W1 (40495) bis 1_PF4 (40502)
1_RmpDecTmm (40544)
1_RmpIncTmm (40545)
Für Kennlinie 2
2_W1 (40549) bis 2_PF4 (40556)
2_RmpDecTmm (40598)
2_RmpIncTmm (40599)
Für Kennlinie 3
3_W1 (40603) bis 3_PF4 (40610)
3_RmpDecTmm (40652)
3_RmpIncTmm (40653)
Für Kennlinie 4
4_W1 (40657) bis 4_PF4 (40664)
4_RmpDecTmm (40706)
4_RmpIncTmm (40707)
DE
Kennlinien einstellen
HINWEIS! Zwischen den gleichbedeutenden Registern der einzelnen Kennlinien
liegen jeweils 54 Register.
Stellvertretend für die anderen einstellbaren Kennlinien wird hier nur Kennlinie 1
beschrieben.
1_W1 (40495) bis 1_PF4 (40502)
1_W1, 1_W2, 1_W3 und 1_W4 = Leistungswerte in Prozent der Nennleistung
1_PF1, 1_PF2, 1_PF3 und 1_PF4 = Power Factor Werte
HINWEIS! Der Wert für den Power Factor muss mit dem korrekten Vorzeichen
eingegeben werden => siehe Abschnitt “Vorzeichenkonvention für den Power
Factor“
1_RmpDecTmm (40544) und 1_RmpIncTmm (40545)
Diese Register definieren wie schnell der Wechselrichter bei Leistungsänderungen den
Power Factor anpasst (Änderungsgeschwindigkeit des Power Factor)
Die Angabe erfolgt in Prozent des max. Power Factor pro Minute
1_RmpDec_Tmm für Reduzierung des Power Factor
1_RmpInc_Tmm für Steigerung des Power Factor
HINWEIS! In beide Register muss der selbe Wert geschrieben werden, da der
Wechselrichter in dieser Betriebsart immer den selben Wert für Steigerung und
Reduzierung verwendet.
45
Beispiel
Im diesem Beispiel werden folgende Schritte behandelt:
Punkte der Kennlinie 1 verändern (entsprechend den Werten in der Abbildung)
HINWEIS! Der Wert für den Power Factor muss mit dem korrekten Vorzeichen eingegeben werden => siehe Abschnitt “Vorzeichenkonvention für den
Power Factor“
Änderungsgeschwindigkeit des Power Factor für Kennlinie 1 einstellen auf
0,2 pro Minute
PF
1
Werte für die Leistung [% von Wmax] in
folgende Register schreiben:
1_W1 (40495) = 40
1_W2 (40497) = 46
1_W3 (40499) = 74
1_W4 (40501) = 80
2
Werte für den Power Factor (multipliziert mit Faktor 1000) in folgende Register schreiben:
1_PF1 (40496) = -900
1_PF2 (40498) = 1000
1_PF3 (40500) = 1000
1_PF4 (40502) = 900
0.9
Overexcited
20
40
80
60
100
1
W/Wmax
[%]
74
46
-0.9
Underexcited
3
Werte für die Änderungsgeschwindigkeit in folgende Register schreiben:
1_RmpDecTmm (40544) = 200
1_RmpIncTmm (40545) = 200
4
Optional die Start- und Rückkehrzeit über Register WinTms (40486) und RvrtTms
(40487) einstellen
5
Durch Schreiben von 1 in Register ActCrv (40484) Kennlinie 1 auswählen
6
Durch Schreiben von 1 in Register ModEna (40485) die Betriebsart starten
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Watt-PF Curve
Register
40482 40482 1
R
0x03 ID
uint16
A well-known value 131. 131
Uniquely identifies this
as a SunSpec Watt-PF
Model
40483 40483 1
R
0x03 L
uint16
Length of Watt-PF Model
226
40484 40484 1
RW 0x03 ActCrv
0x06
0x10
uint16
Index of active curve.
0=no active curve.
0-4
40485 40485 1
RW 0x03 ModEna
0x06
0x10
bitfield16
Is watt-PF mode active. 0: Disabled
1: Enabled
46
DE
Range of values
Description
Units
Scale factor
Type
Name
Function codes
Time window for watt-pf 0 – 300
change.
40487 40487 1
RW 0x03 RvrtTms
0x06
0x10
uint16
Secs
Timeout period for watt- 0 – 28800
pf curve selection.
40488 40488 1
R
0x03 RmpTms
uint16
Secs
Ramp time for moving
from current mode to
new mode.
Not supported
40489 40489 1
R
0x03 NCrv
uint16
Number of curves supported.
4
40490 40490 1
R
0x03 NPt
uint16
40491 40491 1
R
0x03 W_SF
sunssf
Scale factor for percent
WMax.
0
40492 40492 1
R
0x03 PF_SF
sunssf
Scale factor for PF.
-3
40493 40493 1
R
0x03 RmpIncDec_SF sunssf
Scale factor for in0
crement and decrement
ramps.
40494 40494 1
R
0x03 1_ActPt
Curve 1. Number of acti- 4
ve points in array.
40495 40495 1
RW 0x03 1_W1
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 1 Watts.
40496 40496 1
RW 0x03 1_PF1
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 1 PF.
40497 40497 1
RW 0x03 1_W2
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 2 Watts.
40498 40498 1
RW 0x03 1_PF2
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 2 PF.
40499 40499 1
RW 0x03 1_W3
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 3 Watts.
40500 40500 1
RW 0x03 1_PF3
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 3 PF.
40501 40501 1
RW 0x03 1_W4
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 4 Watts.
40502 40502 1
RW 0x03 1_PF4
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 4 PF.
40503 40503 1
R
int16
%
WMax
W_SF
Curve 1, Point 5 Watts.
R/W
Secs
Size
uint16
End
RW 0x03 WinTms
0x06
0x10
Start
40486 40486 1
0x03 1_W5
Registers
Max number of points in 4
array.
uint16
Not supported
47
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40504 40504 1
R
0x03 1_PF5
int16
Cos()
PF_SF
Curve 1, Point 5 PF.
Not supported
40505 40505 1
R
0x03 1_W6
int16
%
WMax
W_SF
Curve 1, Point 6 Watts.
Not supported
40506 40506 1
R
0x03 1_PF6
int16
Cos()
PF_SF
Curve 1, Point 6 PF.
Not supported
40507 40507 1
R
0x03 1_W7
int16
%
WMax
W_SF
Curve 1, Point 7 Watts.
Not supported
40508 40508 1
R
0x03 1_PF7
int16
Cos()
PF_SF
Curve 1, Point 7 PF.
Not supported
40509 40509 1
R
0x03 1_W8
int16
%
WMax
W_SF
Curve 1, Point 8 Watts.
Not supported
40510 40510 1
R
0x03 1_PF8
int16
Cos()
PF_SF
Curve 1, Point 8 PF.
Not supported
40511 40511 1
R
0x03 1_W9
int16
%
WMax
W_SF
Curve 1, Point 9 Watts.
Not supported
40512 40512 1
R
0x03 1_PF9
int16
Cos()
PF_SF
Curve 1, Point 9 PF.
Not supported
40513 40513 1
R
0x03 1_W10
int16
%
WMax
W_SF
Curve 1, Point 10 Watts. Not supported
40514 40514 1
R
0x03 1_PF10
int16
Cos()
PF_SF
40515 40515 1
R
0x03 1_W11
int16
%
WMax
W_SF
Curve 1, Point 11 Watts. Not supported
40516 40516 1
R
0x03 1_PF11
int16
Cos()
PF_SF
Curve 1, Point 1 1PF.
40517 40517 1
R
0x03 1_W12
int16
%
WMax
W_SF
Curve 1, Point 12 Watts. Not supported
40518 40518 1
R
0x03 1_PF12
int16
Cos()
PF_SF
Curve 1, Point 12 PF.
40519 40519 1
R
0x03 1_W13
int16
%
WMax
W_SF
Curve 1, Point 13 Watts. Not supported
40520 40520 1
R
0x03 1_PF13
int16
Cos()
PF_SF
Curve 1, Point 13 PF.
40521 40521 1
R
0x03 1_W14
int16
%
WMax
W_SF
Curve 1, Point 14 Watts. Not supported
40522 40522 1
R
0x03 1_PF14
int16
Cos()
PF_SF
Curve 1, Point 14 PF.
40523 40523 1
R
0x03 1_W15
int16
%
WMax
W_SF
Curve 1, Point 15 Watts. Not supported
40524 40524 1
R
0x03 1_PF15
int16
Cos()
PF_SF
Curve 1, Point 15 PF.
40525 40525 1
R
0x03 1_W16
int16
%
WMax
W_SF
Curve 1, Point 16 Watts. Not supported
40526 40526 1
R
0x03 1_PF16
int16
Cos()
PF_SF
Curve 1, Point 16 PF.
48
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
DE
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40527 40527 1
R
0x03 1_W17
int16
%
WMax
W_SF
Curve 1, Point 17 Watts. Not supported
40528 40528 1
R
0x03 1_PF17
int16
Cos()
PF_SF
Curve 1, Point 17 PF.
40529 40529 1
R
0x03 1_W18
int16
%
WMax
W_SF
Curve 1, Point 18 Watts. Not supported
40530 40530 1
R
0x03 1_PF18
int16
Cos()
PF_SF
Curve 1, Point 18 PF.
40531 40531 1
R
0x03 1_W19
int16
%
WMax
W_SF
Curve 1, Point 19 Watts. Not supported
40532 40532 1
R
0x03 1_PF19
int16
Cos()
PF_SF
Curve 1, Point 19 PF.
40533 40533 1
R
0x03 1_W20
int16
%
WMax
W_SF
Curve 1, Point 20 Watts. Not supported
40534 40534 1
R
0x03 1_PF20
int16
Cos()
PF_SF
Curve 1, Point 20 PF.
Not supported
40535 40542 8
R
0x03 1_CrvNam
String
(16)
Curve 1. Optional description for curve.
Not supported
40543 40543 1
R
0x03 1_RmpPT1Tms uint16
40544 40544 1
RW 0x03 1_RmpDecT0x06 mm
0x10
uint16
% PF/
min
RmpIn- Curve 1. The maximum 1200-65535
cDec_S rate at which the power 0: as fast as
F
factor may be reduced in possible
response to changes in
the power value.
40545 40545 1
RW 0x03 1_RmpIncTmm uint16
0x06
0x10
% PF/
min
RmpIn- Curve 1. The maximum 1200-65535
cDec_S rate at which the power 0: as fast as
F
factor may be increased possible
in response to changes
in the power value.
40546 40546 1
R
40547 40547 1
RW 0x03 1_Pad
0x06
0x10
0x03 1_ReadOnly
Secs
Not supported
Not supported
Not supported
Curve 1. The time of the Not supporPT1 in seconds (time to ted
accomplish a change of
95%).
enum16
Curve 1. Enumerated
value indicates if curve
is read-only or can be
modified.
pad
Curve 1. Pad register.
0: ReadWrite
1: ReadOnly
40548 40601 Values of curve 2
Register offset 54 to curve 1
Name with prefix “2_“
40601 40655 Values of curve 3
Register offset 108 to curve 1
Name with prefix “3_“
40655 40709 Values of curve 4
Register offset 162 to curve 1
Name with prefix “4_“
49
Volt-Watt Curve (IC132)
Allgemeines
Die Volt-Watt-Kennlinie beeinflusst die Wirkleistungs-Einspeisung in Abhängigkeit von der
lokal gemessenen Spannung. Im Sinne der statischen Spannungshaltung erfolgt die Reduktion der Wirkleistung bei höheren Spannungen entlang einer statisch vorgegebenen
Kennlinie.
Von der Fronius Modbus Card werden 4 Kennlinien mit jeweils 3 Punkten unterstützt.
Zusätzlich kann die Änderung der Wirkleistung über die Zeit definiert werden (in Prozent
der Nennwirkleistung pro Minute), um sprunghafte Wechsel zwischen unterschiedlichen
Betriebszuständen zu vermeiden.
110 (253 V)
(264.5 V) 115
100
ΔW = 33.3%
111 112
113
(259.9 V)
V/Vref
[%]
ΔU = 0.01∙Vref
≙ 2.3 V
0
ΔW/Wavail
[%]
ΔW/Wavail
= 33.3% per 0.01·Vref
14.5% per Volt
Die dargestellte Beispiel-Kennlinie beschreibt zwischen 110% (253 V) und 113%
(259,9 V) der Nennspannung eine lineare
Reduktion der Wirkleistung um 100%. Die
Reduktion bezieht sich auf den Wert der
Wirkleistung zum Zeitpunkt der Überschreitung der unteren Spannungsgrenze (253
V).
Das entspricht einem Gradient von 14,5%
je Volt Spannungsänderung.
Für den Wechselrichter bedeuten diese
Vorgaben, dass die Wirkleistungs-Einspeisung im Spannungsbereich von 253 V bis
259,9 V permanent der Kennlinie folgt.
Sinkt die Spannung wieder unter 253 V ab,
wird die Betriebsart beendet.
HINWEIS! Aktivierung und Deaktivierung dieser Kennlinie können am Wechselrichter nur durchgeführt werden, wenn dieser im Standby-Modus ist.
Der Standby-Modus wird von der Fronius Modbus Card automatisch gestartet
und beendet.
Kennlinien verwalten
ActCrv (40712 bis RvrtTms (40715)
Über diese Register werden die Kennlinien verwaltet.
ActCrv (40712)
Mit diesem Register wird die aktive Volt-Watt-Kennlinie ausgewählt. Das ist jene
Kennlinie, die beim Aktivieren der Betriebsart an den Wechselrichter übermittelt wird.
Gültige Werte sind 0 (keine Kennlinie) bis 4.
HINWEIS! Um die Volt-Watt-Betriebsart starten zu können, muss zuerst eine
Kennlinie ausgewählt werden.
ModEna (40713)
Zum Starten und Beenden dieser Betriebsart
Wert 1 in das Register ModEna schreiben = Betriebsart starten
Wert 0 in das Register ModEna schreiben = Betriebsart beenden
HINWEIS! Um bei einer aktiven Betriebsart Werte zu verändern (z. B. eine andere Kennlinie oder eine andere Rückkehrzeit einstellen), folgendermaßen vorgehen:
neuen Wert in das entsprechende Register schreiben
die Betriebsart über Register ModEna erneut starten
50
Kennlinien einstellen
Die Einstellung einer der 4 Kennlinien erfolgt über folgende Register:
Für Kennlinie 1
1_V1 (40724) bis 1_W3 (40729)
1_RmpDecTmm (40773)
1_RmpIncTmm (40774)
Für Kennlinie 2
2_V1 (40778) bis 2_W3 (40783)
2_RmpDecTmm (40827)
2_RmpIncTmm (40828)
Für Kennlinie 3
3_V1 (40832) bis 3_W3 (40837)
3_RmpDecTmm (40881)
3_RmpIncTmm (40882)
Für Kennlinie 4
4_V1 (40886) bis 4_W3 (40891)
4_RmpDecTmm (40935)
4_RmpIncTmm (40936)
HINWEIS! Zwischen den gleichbedeutenden Registern der einzelnen Kennlinien
liegen jeweils 54 Register.
Stellvertretend für die anderen einstellbaren Kennlinien wird hier nur Kennlinie 1
beschrieben.
1_V1 (40724) bis 1_W3 (40729)
1_V1, 1_V2 und 1_V3 = Spannungswerte in Promille der Referenzspannung VRef
1_W1, 1_W2 und 1_W3 = Leistungswerte in Prozent der tatsächlich verfügbaren Leistung
1_RmpDecTmm (40544) und 1_RmpIncTmm (40545)
Diese Register definieren wie schnell der Wechselrichter bei Spannungsänderungen die
Ausgangsleistung anpasst (Änderungsgeschwindigkeit der Ausgangsleistung)
Die Angabe erfolgt in Prozent der max. Ausgangsleistung pro Minute
1_RmpDec_Tmm für Reduzierung der Ausgangsleistung
1_RmpInc_Tmm für Steigerung der Ausgangsleistung
HINWEIS! Die Werte für 1_W1 und 1_W2 müssen mit 100 angegeben werden.
51
DE
RvrtTms (40487)
Mit diesem Register kann das Verhalten des Wechselrichters für diese Betriebsart zeitlich
gesteuert werden. => siehe Abschnitt “Zeitverhalten der unterstützten Betriebsarten“.
Als Standard ist 0 vorgegeben.
Beispiel
Im diesem Beispiel werden folgende Schritte behandelt:
Punkte der Kennlinie 1 verändern (entsprechend den Werten in der Abbildung)
Änderungsgeschwindigkeit der Wirkleistung für Kennlinie 1 einstellen auf
40-fache max. Ausgangsleistung pro Minute (4000% Wmax/Min)
110 (253 V)
(264.5 V) 115
1
Werte für die Spannung [‰ von V] in
folgende Register schreiben:
1_V1 (40724) = 1080
1_V2 (40726) = 1100
1_V3 (40728) = 1130
2
Werte für die Blindleistung [% von VArmax] in folgende Register schreiben:
1_W1 (40725) = 100
1_W2 (40727) = 100
1_W3 (40729) = 0
100
ΔW = 33.3%
111 112
113
(259.9 V)
V/Vref
[%]
ΔU = 0.01∙Vref
≙ 2.3 V
0
ΔW/Wavail
[%]
ΔW/Wavail
= 33.3% per 0.01·Vref
14.5% per Volt
3
Werte für die Änderungsgeschwindigkeit in folgende Register schreiben:
1_RmpDecTmm (40773) = 4000
1_RmpIncTmm (40774) = 4000
4
Optional die Rückkehrzeit über Register RvrtTms (40715) einstellen
5
Durch Schreiben von 1 in Register ActCrv (40712) Kennlinie 1 auswählen
6
Durch Schreiben von 1 in Register ModEna (40713) die Betriebsart starten
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Volt-Watt Curve
Register
40710 40710 1
R
0x03 ID
uint16
40711 40711 1
R
0x03 L
uint16
40712 40712 1
RW 0x03 ActCrv
0x06
0x10
uint16
Index of active curve.
0=no active curve.
40713 40713 1
RW 0x03 ModEna
0x06
0x10
bitfield16
Is Volt-Watt control acti- 0: Disabled
ve.
1: Enabled
40714 40714 1
R
uint16
52
0x03 WinTms
A well-known value 132. 132
Uniquely identifies this
as a SunSpec Volt-Watt
Model
Registers
Secs
Length of Volt-Watt Mo- 226
del.
Time window for voltwatt change.
0-4
Not supported
DE
Range of values
Description
Units
Scale factor
Type
Name
Function codes
Timeout period for voltwatt curve selection.
0 – 28800
40716 40716 1
R
0x03 RmpTms
uint16
Secs
Ramp time for moving
from current mode to
new mode.
Not supported
40717 40717 1
R
0x03 NCrv
uint16
Number of curves supported.
4
40718 40718 1
R
0x03 NPt
uint16
Number of points in array.
3
40719 40719 1
R
0x03 V_SF
sunssf
Scale factor for percent
VRef.
-1
40720 40720 1
R
0x03 DeptRef_SF
sunssf
Scale factor for percent
DeptRef.
0
40721 40721 1
R
0x03 RmpIncDec_SF sunssf
Scale factor for in0
crement and decrement
ramps.
40722 40722 1
R
0x03 1_ActPt
uint16
Curve 1. Number of acti- 3
ve points in array.
40723 40723 1
R
0x03 1_DeptRef
enum16
40724 40724 1
RW 0x03 1_V1
0x06
0x10
uint16
% VRef V_SF
Curve 1, Point 1 Volts.
40725 40725 1
RW 0x03 1_W1
0x06
0x10
int16
%
WMax
Curve 1, Point 1 Watts.
40726 40726 1
RW 0x03 1_V2
0x06
0x10
uint16
% VRef V_SF
Curve 1, Point 2 Volts.
40727 40727 1
RW 0x03 1_W2
0x06
0x10
int16
%
WMax
Curve 1, Point 2 Watts.
40728 40728 1
RW 0x03 1_V3
0x06
0x10
uint16
% VRef V_SF
Curve 1, Point 3 Volts.
40729 40729 1
RW 0x03 1_W3
0x06
0x10
int16
%
WMax
Curve 1, Point 3 Watts.
40730 40730 1
R
0x03 1_V4
uint16
% VRef V_SF
Curve 1, Point 4 Volts.
Not supported
40731 40731 1
R
0x03 1_W4
int16
%
WMax
Curve 1, Point 4 Watts.
Not supported
40732 40732 1
R
0x03 1_V5
uint16
% VRef V_SF
Curve 1, Point 5 Volts.
Not supported
40733 40733 1
R
0x03 1_W5
int16
%
WMax
Curve 1, Point 5 Watts.
Not supported
R/W
Secs
Size
uint16
End
RW 0x03 RvrtTms
0x06
0x10
Start
40715 40715 1
DeptRe Curve 1. Meaning of de- 2: % of Waf_SF
pendent variable.
val
W_SF
W_SF
W_SF
W_SF
W_SF
53
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40734 40734 1
R
0x03 1_V6
uint16
% VRef V_SF
Curve 1, Point 6 Volts.
Not supported
40735 40735 1
R
0x03 1_W6
int16
%
WMax
Curve 1, Point 6 Watts.
Not supported
40736 40736 1
R
0x03 1_V7
uint16
% VRef V_SF
Curve 1, Point 7 Volts.
Not supported
40737 40737 1
R
0x03 1_W7
int16
%
WMax
Curve 1, Point 7 Watts.
Not supported
40738 40738 1
R
0x03 1_V8
uint16
% VRef V_SF
Curve 1, Point 8 Volts.
Not supported
40739 40739 1
R
0x03 1_W8
int16
%
WMax
Curve 1, Point 8 Watts.
Not supported
40740 40740 1
R
0x03 1_V9
uint16
% VRef V_SF
Curve 1, Point 9 Volts.
Not supported
40741 40741 1
R
0x03 1_W9
int16
%
WMax
Curve 1, Point 9 Watts.
Not supported
40742 40742 1
R
0x03 1_V10
uint16
% VRef V_SF
Curve 1, Point 10 Volts. Not supported
40743 40743 1
R
0x03 1_W10
int16
%
WMax
W_SF
Curve 1, Point 10 Watts. Not supported
40744 40744 1
R
0x03 1_V11
uint16
% VRef V_SF
Curve 1, Point 11 Volts. Not supported
40745 40745 1
R
0x03 1_W11
int16
%
WMax
W_SF
Curve 1, Point 11 Watts. Not supported
40746 40746 1
R
0x03 1_V12
uint16
% VRef V_SF
Curve 1, Point 12 Volts. Not supported
40747 40747 1
R
0x03 1_W12
int16
%
WMax
W_SF
Curve 1, Point 12 Watts. Not supported
40748 40748 1
R
0x03 1_V13
uint16
% VRef V_SF
Curve 1, Point 13 Volts. Not supported
40749 40749 1
R
0x03 1_W13
int16
%
WMax
W_SF
Curve 1, Point 13 Watts. Not supported
40750 40750 1
R
0x03 1_V14
uint16
% VRef V_SF
Curve 1, Point 14 Volts. Not supported
40751 40751 1
R
0x03 1_W14
int16
%
WMax
W_SF
Curve 1, Point 14 Watts. Not supported
40752 40752 1
R
0x03 1_V15
uint16
% VRef V_SF
Curve 1, Point 15 Volts. Not supported
40753 40753 1
R
0x03 1_W15
int16
%
WMax
W_SF
Curve 1, Point 15 Watts. Not supported
40754 40754 1
R
0x03 1_V16
uint16
% VRef V_SF
Curve 1, Point 16 Volts. Not supported
40755 40755 1
R
0x03 1_W16
int16
%
WMax
W_SF
Curve 1, Point 16 Watts. Not supported
40756 40756 1
R
0x03 1_V17
uint16
% VRef V_SF
Curve 1, Point 17 Volts. Not supported
54
W_SF
W_SF
W_SF
W_SF
DE
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40757 40757 1
R
0x03 1_W17
int16
%
WMax
W_SF
Curve 1, Point 17 Watts. Not supported
40758 40758 1
R
0x03 1_V18
uint16
% VRef V_SF
Curve 1, Point 18 Volts. Not supported
40759 40759 1
R
0x03 1_W18
int16
%
WMax
W_SF
Curve 1, Point 18 Watts. Not supported
40760 40760 1
R
0x03 1_V19
uint16
% VRef V_SF
Curve 1, Point 19 Volts. Not supported
40761 40761 1
R
0x03 1_W19
int16
%
WMax
W_SF
Curve 1, Point 19 Watts. Not supported
40762 40762 1
R
0x03 1_V20
uint16
% VRef V_SF
Curve 1, Point 20 Volts. Not supported
40763 40763 1
R
0x03 1_W20
int16
%
WMax
Curve 1, Point 20 Watts. Not supported
40764 40771 8
R
0x03 1_CrvNam
String
(16)
40772 40772 1
R
0x03 1_RmpPt1Tms uint16
40773 40773 1
RW 0x03 1_RmpDecT0x06 mm
0x10
uint16
%
WMax/
min
RmpIn- Curve 1. The maximum 60-12000
0: as fast as
cDec_S rate at which the watt
F
value may be reduced in possible
response to changes in
the voltage value.
40774 40774 1
RW 0x03 1_RmpIncTmm uint16
0x06
0x10
%
WMax/
min
RmpIn- Curve 1. The maximum 12-1200
cDec_S rate at which the watt
0: as fast as
F
value may be increased possible
in response to changes
in the voltage value.
40775 40775 1
R
0x03 1_ReadOnly
W_SF
Curve 1. Optional description for curve.
Secs
Not supported
Curve 1. The time of the Not supporPT1 in seconds (time to ted
accomplish a change of
95%).
enum16
Curve 1. Enumerated
value indicates if curve
is read-only or can be
modified.
0: ReadWrite
1: ReadOnly
Identifies this as End
block
0xFFFF
Length of model block
0
40776 40829 Values of curve 2
Register offset 54 to curve 1
Name with prefix “2_“
40830 40883 Values of curve 3
Register offset 108 to curve 1
Name with prefix “3_“
40884 40937 Values of curve 4
Register offset 162 to curve 1
Name with prefix “4_“
40938 40938 1
R
0x03 ID
uint16
40939 40939 1
R
0x03 L
uint16
Registers
55
Event Flags
SunSpec
Event Flags
Ereignis
Event
Flags 1
Event
Flags 2
I_EVENT_GROUND_FAULT
0x00000001 0x00000000 Erdungsfehler
I_EVENT_DC_OVER_VOLT
0x00000002 0x00000000 DC Überspannung
I_EVENT_AC_DISCONNECT
0x00000004 0x00000000 AC getrennt
I_EVENT_DC_DISCONNECT
0x00000008 0x00000000 DC getrennt
I_EVENT_GRID_DISCONNECT
0x00000010 0x00000000 Netzabschaltung
I_EVENT_CABINET_OPEN
0x00000020 0x00000000 Gehäuse offen
I_EVENT_MANUAL_SHUTDOWN
0x00000040 0x00000000 Manuelle Abschaltung
I_EVENT_OVER_TEMP
0x00000080 0x00000000 Übertemperatur
I_EVENT_OVER_FREQUENCY
0x00000100 0x00000000
Frequenz über Grenzwert
105, 115, 125, 135, 560
I_EVENT_UNDER_FREQUENCY
0x00000200 0x00000000
Frequenz unter Grenzwert
106, 116, 126, 136
I_EVENT_AC_OVER_VOLT
0x00000400 0x00000000
AC-Spannung über
Grenzwert
102, 112, 122, 132
I_EVENT_AC_UNDER_VOLT
0x00000800 0x00000000
AC-Spannung unter
Grenzwert
103, 113, 123, 133
I_EVENT_BLOWN_STRING_FUSE
0x00001000 0x00000000 Strangsicherung defekt
I_EVENT_UNDER_TEMP
0x00002000 0x00000000 Untertemperatur
Status
Status Codes
471, 472, 474, 475, 502
107, 117, 127, 137
303, 304, 531, 561
0x00004000 0x00000000
I_EVENT_HW_TEST_FAILURE
0x00008000 0x00000000 Hardwaretest Fehler
104, 203, 204 *)
101, 201, 202 *)
Interner Speicher- oder
Kommunikationsfehler
I_EVENT_MEMORY_LOSS
spezielle
Status Codes
550, 551
402, 404, 405, 414, 416,
417, 419, 421, 425, 431,
451, 452, 453, 454, 460,
461, 464, 465, 466, 467,
504, 505, 506, 507, 508,
510, 511, 514, 516, 517,
541, 553, 558
401, 403, 406, 407, 457,
469, 515, 532, 533, 535,
555
*) beide Flags müssen gesetzt sein
Fronius
Event Flags
Ereignis
Event
Flags 1
I_EVENT_INSULATION_FAULT
0x00000001 0x00000000 0x00000000 0x00000000 474, 475, 502
I_EVENT_GRID_ERROR
0x00000002 0x00000000 0x00000000 0x00000000
I_EVENT_AC_OVERCURRENT
0x00000004 0x00000000 0x00000000 0x00000000 301
I_EVENT_DC_OVERCURRENT
0x00000008 0x00000000 0x00000000 0x00000000 302
I_EVENT_OVER_TEMP
0x00000010 0x00000000 0x00000000 0x00000000 303, 304
56
Event
Flags 2
Event
Flags 3
Event
Flags 4
Status Code
am Wechselrichter
101, 104, 107, 117, 127, 137, 108,
109, 205, 206, 305
Event
Flags 1
Event
Flags 2
Event
Flags 3
Event
Flags 4
Status Code
am Wechselrichter
I_EVENT_POWER_LOW
0x00000020 0x00000000 0x00000000 0x00000000 306, 309
I_EVENT_DC_LOW
0x00000040 0x00000000 0x00000000 0x00000000 307, 310
I_EVENT_INTERMED_VOLT_HIGH
0x00000080 0x00000000 0x00000000 0x00000000 308
I_EVENT_FREQUENCY_HIGH
0x00000100 0x00000000 0x00000000 0x00000000 105, 115, 125, 135, 203
I_EVENT_FREQUENCY_LOW
0x00000200 0x00000000 0x00000000 0x00000000 106, 116, 126, 136, 204
I_EVENT_AC_VOLTAGE_HIGH
0x00000400 0x00000000 0x00000000 0x00000000 102, 112, 122, 132, 201
I_EVENT_AC_VOLTAGE_LOW
0x00000800 0x00000000 0x00000000 0x00000000 103, 113, 123, 133, 202
I_EVENT_DIRECT_CURRENT
0x00001000 0x00000000 0x00000000 0x00000000 408
I_EVENT_RELAY_FAULT
0x00002000 0x00000000 0x00000000 0x00000000 207, 208, 457
I_EVENT_POWER_STAGE_FAULT
0x00004000 0x00000000 0x00000000 0x00000000
I_EVENT_CONTROL_FAULT
0x00008000 0x00000000 0x00000000 0x00000000 409, 413
I_EVENT_GRID_VOLT_REC
0x00010000 0x00000000 0x00000000 0x00000000 453
I_EVENT_GRID_FREQU_REC
0x00020000 0x00000000 0x00000000 0x00000000 454
I_EVENT_ENERGY_TRANSFER_FAULT
0x00040000 0x00000000 0x00000000 0x00000000 443
I_EVENT_REF_POWER_SOURCE_AC
0x00080000 0x00000000 0x00000000 0x00000000 455
I_EVENT_ANTI_ISLANDING_FAULT
0x00100000 0x00000000 0x00000000 0x00000000 456
I_EVENT_FIXED_VOLTAGE_FAULT
0x00200000 0x00000000 0x00000000 0x00000000 412
I_EVENT_EEPROM_FAULT
0x00400000 0x00000000 0x00000000 0x00000000
I_EVENT_DISPLAY_FAULT
0x00800000 0x00000000 0x00000000 0x00000000 464, 465, 466, 467
I_EVENT_COMMUNICATION_FAULT
0x01000000 0x00000000 0x00000000 0x00000000 401, 402, 416, 425, 452
I_EVENT_TEMP_SENSORS_FAULT
0x02000000 0x00000000 0x00000000 0x00000000 406, 407, 533
I_EVENT_DSP_FAULT
0x04000000 0x00000000 0x00000000 0x00000000 460, 461
I_EVENT_ENS_FAULT
0x08000000 0x00000000 0x00000000 0x00000000 405, 415
I_EVENT_FAN_FAULT
0x10000000 0x00000000 0x00000000 0x00000000
I_EVENT_DEFECTIVE_FUSE
0x20000000 0x00000000 0x00000000 0x00000000 471, 551
I_EVENT_OUTPUT_CHOKE_FAULT
0x40000000 0x00000000 0x00000000 0x00000000 469
I_EVENT_CONVERTER_RELAY_FAULT
0x80000000 0x00000000 0x00000000 0x00000000 470
I_EVENT_NO_SOLARNET_COMM
0x00000000 0x00000001 0x00000000 0x00000000 504
I_EVENT_INV_ADDRESS_FAULT
0x00000000 0x00000002 0x00000000 0x00000000 508
I_EVENT_NO_FEED_IN_24H
0x00000000 0x00000004 0x00000000 0x00000000 509
I_EVENT_PLUG_FAULT
0x00000000 0x00000008 0x00000000 0x00000000 410, 515
I_EVENT_PHASE_ALLOC_FAULT
0x00000000 0x00000010 0x00000000 0x00000000 473
I_EVENT_GRID_CONDUCTOR_OPEN
0x00000000 0x00000020 0x00000000 0x00000000 210
I_EVENT_FEATURE_DEACTIVATED
0x00000000 0x00000040 0x00000000 0x00000000 558
I_EVENT_CHANGE_OF_MASTER
0x00000000 0x00000080 0x00000000 0x00000000 517
I_EVENT_JUMPER_INCORRECT
0x00000000 0x00000100 0x00000000 0x00000000 550
I_EVENT_LOW_VOLT_RIDE_THROUGH
0x00000000 0x00000200 0x00000000 0x00000000 559
I_EVENT_VENTS_BLOCKED
0x00000000 0x00000400 0x00000000 0x00000000 501
I_EVENT_POWER_REDUCTION_ERROR
0x00000000 0x00000800 0x00000000 0x00000000 560, 561
I_EVENT_ARC_DETECTED
0x00000000 0x00001000 0x00000000 0x00000000 240
I_EVENT_AFCI_SELF_TEST_FAILED
0x00000000 0x00002000 0x00000000 0x00000000 245
DE
Ereignis
417, 419, 421, 431, 439, 442, 445,
450, 512, 513, 514, 516, 553
403, 414, 451, 505, 506, 507, 510,
511
530, 531, 534, 535, 536, 537, 540,
541, 555, 557
57
Ereignis
Event
Flags 1
I_EVENT_CURRENT_SENSOR_ERROR
0x00000000 0x00004000 0x00000000 0x00000000 247
I_EVENT_ENS_JUMPERS_WRONG
0x00000000 0x00008000 0x00000000 0x00000000 248
I_EVENT_AFCI_DEFECTIVE
0x00000000 0x00010000 0x00000000 0x00000000 249
I_EVENT_AFCI_MANUAL_TEST_OK
0x00000000 0x00020000 0x00000000 0x00000000 250
I_EVENT_AFCI_COMM_ERROR
0x00000000 0x00040000 0x00000000 0x00000000 476
I_EVENT_AFCI_NO_COMM
0x00000000 0x00080000 0x00000000 0x00000000 477
I_EVENT_AFCI_MANUAL_TEST_FAILED
0x00000000 0x00100000 0x00000000 0x00000000 478
58
Event
Flags 2
Event
Flags 3
Event
Flags 4
Status Code
am Wechselrichter
General ......................................................................................................................................................
Abbreviations Used...............................................................................................................................
Communication with the Modbus Master..............................................................................................
Event Flags ...........................................................................................................................................
Reading Registers ................................................................................................................................
Unavailable Data Records ....................................................................................................................
Function code 0x11 (Report Slave ID)..................................................................................................
Available Models...................................................................................................................................
Time Response of the Supported Operating Modes.............................................................................
Sign Convention for the Power Factor ..................................................................................................
Values Saved on the Card ....................................................................................................................
Scale Factors ........................................................................................................................................
Non-Writable Registers.........................................................................................................................
Entering Invalid Values .........................................................................................................................
Commissioning ..........................................................................................................................................
Reference voltage.................................................................................................................................
Deviation from Reference Voltage ........................................................................................................
Setting the Time....................................................................................................................................
Fronius Registers .......................................................................................................................................
Fronius Registers..................................................................................................................................
Inverter Status Code .............................................................................................................................
Deleting Event Flags and Status Codes ...............................................................................................
Restarting the Modbus Card .................................................................................................................
Firmware update ........................................................................................................................................
General .................................................................................................................................................
transmission time ..................................................................................................................................
Transmission Security...........................................................................................................................
Transmission Mode...............................................................................................................................
Performing Firmware Updates ..............................................................................................................
Setting the Baud Rate................................................................................................................................
General .................................................................................................................................................
Setting Baud Rate and/or Parity ...........................................................................................................
Common & Inverter Model .........................................................................................................................
Common & Inverter Register ................................................................................................................
Setting the Modbus Device ID ...................................................................................................................
General .................................................................................................................................................
Setting the Modbus Device ID ..............................................................................................................
Nameplate model (IC120) ..........................................................................................................................
General .................................................................................................................................................
Nameplate Registers ............................................................................................................................
Basic Settings Model (IC121) ....................................................................................................................
Basic Settings Register.........................................................................................................................
Reference voltage.................................................................................................................................
Deviation from Reference Voltage ........................................................................................................
Switch-off Limits....................................................................................................................................
Extended Measurements & Status Model (IC122).....................................................................................
Extended Measurements & Status Register .........................................................................................
General .................................................................................................................................................
Immediate Control Model (IC123) ..............................................................................................................
General .................................................................................................................................................
Immediate Controls Register ................................................................................................................
Standby.................................................................................................................................................
Power Reduction...................................................................................................................................
Example: Setting a Power Reduction ...................................................................................................
Example: Changing the Return Time When Power Reduction Has Been Activated ............................
Effects of Reactive Power Specifications on Effective Power...............................................................
Constant Power Factor .........................................................................................................................
Example: Setting a Constant Power Factor ..........................................................................................
Constant Relative Reactive Power .......................................................................................................
Example: Setting Constant Reactive Power .........................................................................................
61
61
61
62
62
63
63
64
64
65
66
66
66
66
67
67
67
67
69
69
72
72
72
73
73
73
73
73
73
76
76
76
77
77
80
80
80
81
81
81
83
83
85
86
86
87
87
89
90
90
90
92
92
93
93
93
94
94
95
95
59
EN-US
Contents
Volt-VAr Arrays (IC126) .............................................................................................................................
General .................................................................................................................................................
Managing Characteristic Curves...........................................................................................................
Setting Characteristic Curves ...............................................................................................................
Example ................................................................................................................................................
Volt-VAr Arrays Register.......................................................................................................................
Watt-PF Curve (IC131) ..............................................................................................................................
General .................................................................................................................................................
Managing Characteristic Curves...........................................................................................................
Setting Characteristic Curves ...............................................................................................................
Example ................................................................................................................................................
Watt-PF Curve Register........................................................................................................................
Volt-Watt Curve (IC132).............................................................................................................................
General .................................................................................................................................................
Managing Characteristic Curves...........................................................................................................
Setting Characteristic Curves ...............................................................................................................
Example ................................................................................................................................................
Volt-Watt Curve Register ......................................................................................................................
Event Flags ................................................................................................................................................
SunSpec Event Flags ...........................................................................................................................
Fronius Event Flags ..............................................................................................................................
60
96
96
96
97
98
98
102
102
102
103
104
104
108
108
108
109
110
110
114
114
114
Abbreviations
Used
Communication
with the Modbus
Master
AC
Alternating current
DC
Direct current
FW
Firmware
MBC
Fronius Modbus Card
PF
Power factor (cos )
PV
Photovoltaics
RTC
Real-time clock
SF
Scale factor
SW
Software
V
Voltage (volts)
VA
Apparent power
VAr
Reactive power
VMax
Maximum voltage
VMin
Minimum voltage
VRef
Reference voltage
W
Power (watts)
IN
Inverter
EN-US
General
The Fronius Modbus Card communicates with the Modbus Master using register addresses in accordance with the SunSpec specification. The allocation of register addresses to
the corresponding function can be found in the following tables:
Fronius Register (Fronius Modbus Card Settings)
Common & Inverter Register (Common Block and Inverter Model)
Inverter Controls:
Nameplate (IC120)
Basic Settings (IC121)
Extended Measurements & Status (IC122)
Immediate Controls (IC123)
Volt-VAR (IC126)
Watt-PF (IC131)
Volt-Watt (IC132)
NOTE! We recommend that associated values should always be read in a single
Modbus request. Otherwise there is a chance that one of the two values will
change in between requests and the data will therefore not be correct.
For example:
DC power (40101, I_DC_Power) always together with
Scale factor (40102, I_DC_Power_SF)
61
Event Flags
Changes in status and inverter errors are displayed as event flags. In the following tables,
you can find out which event flags correspond to which events or inverter state codes:
SunSpec Event Flags
Fronius Event Flags
NOTE! It is also possible to combine several state codes for one event.
An accurate description of the state codes can be found in the operating instructions of the
relevant inverter.
If the inverter generates a state code, the relevant event flag is set in the Fronius Modbus
Card.
In addition, the relevant state code is also displayed in register
INV_Active_State_Code (214).
The event flag and state code will remain active for as long as the state code is displayed
on the inverter. If another state code is generated, it will also be displayed in the event
flags. In this case, there is a chance that the previous event flag will not be deleted.
It is therefore possible to manually delete the event flags and the state code
by entering 0xFFFF1) in register INV_Reset_All_Event_Flags (215).
1)
Reading Registers
The prefix "0x" stands for hexadecimal numbers
To read a register, the register's start address must be specified in the Modbus request.
NOTE! This address is always 1 less than the register number in accordance with
the SunSpec specification.
Example: Request for 4 registers starting from register 40005 (C_Manufacturer)
Send (bytes in hexadecimal)
01
Device
ID
03
9C
44
00
04
Function Address 40004 Number of regcode
(corresponds to isters to be read
register 40005)
2A
4C
Checksum
Low
High
byte
byte
Receive (bytes in hexadecimal)
62
01
03
08
Device
ID
Function
code
Number of
bytes
46
72
6F
6E
69
75
73
00
Address 40005 Address 40006 Address 40007 Address 40008
"F" and "r"
"o" and "n"
"i" and "u"
"s" and 0
8A
2A
Checksum
Low
High
byte
byte
Fronius inverters cannot always provide all the data specified in the SunSpec data models. Depending on the data type, this data is represented by the following values in accordance with the SunSpec specification:
1)
Function code
0x11
(Report Slave ID)
int16:
uint16:
acc16:
int32:
uint32:
acc32:
Strings:
enum16:
bitfield16:
pad:
0x80001)
0xFFFF
0x0000
0x80000000
0xFFFFFFFF
0x00000000
always 0
0xFFFF
0xFFFF
0x8000
EN-US
Unavailable Data
Records
The prefix "0x" stands for hexadecimal numbers
The function code 0x11 is used for fast reading of the most important inverter data.
1
Send 0x11 to the corresponding Fronius Modbus Card
2
Reply does not come as register address but rather in the form of a 24 byte packet
Byte (position)
Description
1st data byte
Number of bytes = 21
Corresponds to the number of data bytes from the 4th
byte
2nd data byte
Inverter ID
3rd data byte
Inverter status
0xFF if inverter is running
0x00 if inverter is switched off
Data bytes 4 - 24
Manufacturer and inverter type as string of
21 characters (21 bytes)
For example:"Fronius IG+150V"
The rest of the 21 bytes are filled with 0x00
63
Available Models
NOTE! SunSpec inverter control models can be used for software version 2.1.16
of the Fronius Modbus Card or higher. The actual availability of the various operating modes depends, however, on the inverter (software and hardware version).
For using the Modbus SunSpec Inverter Control Models with the Fronius Modbus Card a
Brain 2.0 is necessary, which is part of the following inverters:
Fronius CL ab Seriennummer 24033431
mit Setup SI oder IT BT
Fronius IG Plus V ab Seriennummer 24031463
mit Setup IT BT, EXC EU, EU, EXC Int., SI
Fronius IG Plus Advanced (USA)
The following models are always available for software version 2.1.16 or higher, irrespective of the inverter's abilities:
Nameplate
Basic Settings
Extended Measurements & Status
Immediate Controls
If the inverter does not support the other models (Volt-VAR, Watt-PF, Volt-Watt), the "not
implemented" values specified by SunSpec Alliance will be returned when they are read.
If an update gives an inverter the ability to provide additional operating modes, no update
needs to be performed for the Fronius Modbus Card. The Fronius Modbus Card will however need to be restarted.
There are several ways to restart the Fronius Modbus Card
By disconnecting the AC voltage supply
By using the corresponding Fronius register MBC_Reset (230)
Time Response of
the Supported
Operating Modes
Time response illustrated by power reduction
The inverter's time response in an operating mode can be defined by several time values.
Three possible time values are shown in the figure "Time Response Illustrated by power
reduction":
WinTms 0-300 [seconds]
specifies a time window in which the operating mode is randomly started. The time
window starts when the start command for the operating mode is issued (e.g., OutPFSet_Ena = 1).
WinTms can be used to prevent all the inverters in the system from applying the
64
-
-
NOTE! The data of all the supported operating modes is saved on the Fronius
Modbus Card and will still be available after an AC reset on the Fronius Modbus
Card (disconnection or failure in the AC voltage supply).
The RTC on the Fronius Modbus Card must be set once in order to ensure correct
time response after an AC reset.
The RTC can be set using the following registers:
40225-40226 => Section "Extended Measurements & Status Model (IC122)"
23-28 => Section "Fronius Register"
(+kVAr, +kVArh)
90°
Reactive Power
Exported/Received (W)
Power factor sign
convention
EEI: +
(Leading, capacitive)
(-kW, -kWh)
Reactive Power
Exported/Received (W)
180°
Quadrant 1
Power factor sign
convention
EEI: (Lagging, inductive)
Ap
pa
re
nt
Po
r
we
w
er
(V
A)
Ap
ϕ
p
e
ar
nt
Reactive Power
Exported/Received (W)
Quadrant 2
A)
(V
Po
ϕ
Active Power
Exported/Received (W)
Active Power
Exported/Received (W)
Active Power
Exported/Received (W)
Active Power
Exported/Received (W)
ϕ
er
nt
Ap
A)
(V
re
nt
w
Po
re
Po
we
r(
VA
)
pa
Ap
Power factor sign
convention
EEI: (Lagging, inductive)
Quadrant 3
ϕ
pa
(+kW, +kWh)
0°
Reactive Power
Exported/Received (W)
Sign Convention
for the Power
Factor
Power factor sign
convention
EEI: +
(Leading, capacitive)
270°
(-kVAr, -kVArh)
Quadrant 4
The EEI sign convention1) for the power factor is in line with the SunSpec specification and
is based on the information contained in the "Handbook for Electricity Metering" and IEC
61557-12 (2007).
The power factor is:
negative if the reactive power is positive (over-excited, quadrant 1)
positive if the reactive power is negative (under-excited, quadrant 4)
1)
EEI = Edison Electrical Institute
65
EN-US
changes at the same time. If the time window is set to 0 (the default value), the operating mode will start immediately.
RmpTms 0 (30)-600 [seconds]
specifies how quickly the changes are to be made. The corresponding value gradually
changes during the specified time period from the old to the new value.
If the RmpTms is 0 (the default value) or less than 30, the new value will immediately
be applied.
RvrtTms 0-28800 [seconds]
determines how long the operating mode will be active. After the time expires, the operating mode is automatically deactivated. If RvrtTms is 0 (the default value), the operating mode remains active until it is manually deactivated via the corresponding
register.
Values Saved on
the Card
Some data for the various inverter control models, e.g., switch-off limits and characteristic
curve values cannot be saved on the inverter. This task is performed by the Fronius Modbus Card.
Some of these values can only be used for the inverter in which the Fronius Modbus Card
is fitted (e.g., switch-off limits). These values will be deleted if the Fronius Modbus Card is
fitted into another inverter and read again by the inverter.
Scale Factors
All the used scale factors are unchangeable values and set by the inverter or the Fronius
Modbus Card. Before entering register values, you should therefore either look up the associated scale factor in the instructions or read it straight from the corresponding register.
Non-Writable
Registers
The following registers cannot be written:
Read-only (R) registers
Registers which are currently not supported
NOTE! If you try to write these registers, the Fronius Modbus Card will not return
an exception code!
The values entered into these registers will be ignored without any error message
being issued by the Fronius Modbus Card.
Entering Invalid
Values
66
Some registers only permit certain values. The valid values can be found in the relevant
register table.
If an invalid value is entered into a register, the Fronius Modbus Card will return exception
code 3 (illegal data value). The invalid value is ignored.
If several registers are written at the same time, all the valid values will be entered up to
the register containing the invalid value. The write operation will then be canceled.
Reference voltage
VRef (40153)
The reference voltage is the voltage at the point of common coupling where the local grid
is connected to the public grid. The reference voltage is the same as the inverter's nominal
voltage.
=> see figure "Point of common coupling"
During initial start-up, the Fronius Modbus Card automatically determines the reference
voltage from the voltage values of the inverter's individual phases.
This method is however inaccurate and fluctuations in the grid voltage or voltage deviations at the connection point may cause a VRef of 230 V in a 240 V grid.
It is therefore necessary to manually transfer the correct reference voltage to the Fronius
Modbus Card.
The value is given in volts in the range of 0x00 (0) to 0x190 (400)
This value is saved on the Fronius Modbus Card. The value will be deleted if the Fronius
Modbus Card is fitted in another inverter.
Example Settings
= Electrical Connection Point (ECP)
VRefOfs = 4V
VRefOfs = 2V
Utility Power System
Local Bus
VRefOfs = 3V
Local Power
System with
Line Resistors
Point of Common
Coupling (PCC)
VRef = 120V
DER interconnections
Point of common coupling
Deviation from
Reference Voltage
VRefOfs (40154)
Depending on the connection of the local grid, there may be a deviation from the reference
voltage at the point where each individual inverter is connected to the local grid (see figure
"Point of common coupling").
If this deviation is known, it should be specified. When using operating modes "Volt-Watt"
and "Volt'VAr", the voltage values of the Fronius Modbus Card are then adjusted accordingly.
The value is given in volts in the range of 0xFFEC (-20) to 0x14 (20). That corresponds to
a possible deviation of -20 V to +20 V.
Setting the Time
In order to ensure the correct function of the time-controlled operating modes after an AC
reset, the RTC on the Fronius Modbus Card must be set once.
67
EN-US
Commissioning
The RTC can be set using the following registers:
Tms (40223–40224) in the Extended Measurements & Status model
specification of current date and time in seconds from January 1, 2000, 00:00 (UTC)
to the current time
value range 0x00 (0) to 0xFFFFFFF (4294967295)
-
68
MBC_Clock_Year (23) to MBC_Clock_Seconds (28) in the Fronius registers
MBC_Clock_Year (23)
Specification of year in the range 0x00 (2000) to 0x63 (2099)
MBC_Clock_Month (24)
Specification of month in the range 0x01 (1 = January) to 0x0C (12 = December)
MBC_Clock_Day (25)
Specification of day in the range 0x01 (1) to 0x1F (31)
MBC_Clock_Hours (26)
Specification of hour in the range 0x00 (0) to 0x17 (23)
MBC_Clock_Minutes (27)
Specification of minutes in the range 0x00 (0) to 0x3B (59)
MBC_Clock_Seconds (28)
Specification of seconds in the range 0x00 (0) to 0x3B (59)
Fronius Registers
String
(32)
1
16
16 R
0x03 MBC_ID
Modbus Card ID
17
17
1
R
0x03 MBC_FW_Ver- uint16
sion_Major
Firmware version of
MBC, major
18
18
1
R
0x03 MBC_FW_Ver- uint16
sion_Minor
Firmware version of
MBC, minor
19
19
1
R
0x03 MBC_FW_Ver- uint16
sion_Release
Firmware version of
MBC, release
20
21
2
RW 0x03 MBC_Baudrate uint32
0x06
0x10
22
22
1
RW 0x03 MBC_Parity
0x06
0x10
23
23
1
24
24
25
Baud
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Fronius Registers
"Fronius
ModbusCard"
Baud rate
9600, 19200
uint16
Parity
0x00 Even
0x01 Odd
0x02 None
RW 0x03 MBC_Clock_0x06 Year
0x10
uint16
Date and Time: Year
0x00 (2000)
to 0x63
(2099)
1
RW 0x03 MBC_0x06 Clock_Month
0x10
uint16
Date and Time: Month
0x01 (January) to 0x0C
(December)
25
1
RW 0x03 MBC_Clock_0x06 Day
0x10
uint16
Date and Time: Day
0x01 to
0x1F
26
26
1
RW 0x03 MBC_0x06 Clock_Hours
0x10
uint16
Date and Time: Hours
0x00 to 0x17
27
27
1
RW 0x03 MBC_0x06 Clock_Minutes
0x10
uint16
Date and Time: Minutes 0x00 to
0x3B
28
28
1
RW 0x03 MBC_uint16
0x06 Clock_Seconds
0x10
Date and Time: Seconds
29
29
1
R
0x03 MBC_HW_Ver- uint16
sion_Major
Hardware version of
MBC, major
30
30
1
R
0x03 MBC_HW_Ver- uint16
sion_Minor
Hardware version of
MBC, minor
31
31
1
R
0x03 MBC_HW_Ver- uint16
sion_Assembly
Hardware version of
MBC, assembly
32
32
1
R
0x03 MBC_UID
uint16
Unique ID
33
33
1
R
0x03 MBC_Serial_1
uint16
Serial number of MBC
34
34
1
R
0x03 MBC_Serial_2
uint16
Serial number of MBC
0x00 to
0x3B
69
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
35
1
R
0x03 MBC_Serial_3
uint16
Serial number of MBC
36
36
1
R
0x03 MBC_Serial_4
uint16
Serial number of MBC
37
37
1
R
0x03 MBC_Serial_5
uint16
Serial number of MBC
38
38
1
R
0x03 MBC_Common_Block_Major
uint16
SunSpec Common
Block version, major
Currently 1
39
39
1
R
0x03 MBC_Comuint16
mon_Block_Minor
SunSpec Common
Block version, minor
Currently 4
40
40
1
R
0x03 MBC_Inverter_- uint16
Model_Major
SunSpec Inverter Model Currently 1
version, major
41
41
1
R
0x03 MBC_Inverter_- uint16
Model_Minor
SunSpec Inverter Model Currently 1
version, minor
50
65
16 RW 0x03 Inverter_Seri0x10 al_Number
String
(32)
Serial number of inverter
100
101
2
RW 0x03 FW_CRC32
0x10
uint32
Checksum for the update file (bin) as per
CRC-32 (IEEE802.3)
102
103
2
RW 0x03 FW_Size
0x10
uint32
104
104
1
RW 0x03 FW_BlockNum- uint16
0x10 ber
Current block number
105
105
1
RW 0x03 FW_Bytes_in_- uint16
0x10 Block
Number of bytes in current block
106
106
1
RW 0x03 FW_Data_01
0x10
uint16
Firmware data
107
107
1
RW 0x03 FW_Data_02
0x10
uint16
Firmware data
108
108
1
RW 0x03 FW_Data_03
0x10
uint16
Firmware data
109
109
1
RW 0x03 FW_Data_04
0x10
uint16
Firmware data
110
110
1
RW 0x03 FW_Data_05
0x10
uint16
Firmware data
111
111
1
RW 0x03 FW_Data_06
0x10
uint16
Firmware data
112
112
1
RW 0x03 FW_Data_07
0x10
uint16
Firmware data
113
113
1
RW 0x03 FW_Data_08
0x10
uint16
Firmware data
114
114
1
RW 0x03 FW_Data_09
0x10
uint16
Firmware data
115
115
1
RW 0x03 FW_Data_10
0x10
uint16
Firmware data
116
116
1
RW 0x03 FW_Data_11
0x10
uint16
Firmware data
End
Size
Start
35
70
byte
Size of update file
RW 0x03 FW_Data_12
0x10
uint16
Firmware data
118
118
1
RW 0x03 FW_Data_13
0x10
uint16
Firmware data
119
119
1
RW 0x03 FW_Data_14
0x10
uint16
Firmware data
120
120
1
RW 0x03 FW_Data_15
0x10
uint16
Firmware data
121
121
1
RW 0x03 FW_Data_16
0x10
uint16
Firmware data
122
122
1
RW 0x03 FW_Data_17
0x10
uint16
Firmware data
123
123
1
RW 0x03 FW_Data_18
0x10
uint16
Firmware data
124
124
1
RW 0x03 FW_Data_19
0x10
uint16
Firmware data
125
125
1
RW 0x03 FW_Data_20
0x10
uint16
Firmware data
126
126
1
RW 0x03 FW_Data_21
0x10
uint16
Firmware data
127
127
1
RW 0x03 FW_Data_22
0x10
uint16
Firmware data
128
128
1
RW 0x03 FW_Data_23
0x10
uint16
Firmware data
129
129
1
RW 0x03 FW_Data_24
0x10
uint16
Firmware data
130
130
1
RW 0x03 FW_Data_25
0x10
uint16
Firmware data
131
131
1
RW 0x03 FW_Data_26
0x10
uint16
Firmware data
132
132
1
RW 0x03 FW_Data_27
0x10
uint16
Firmware data
133
133
1
RW 0x03 FW_Data_28
0x10
uint16
Firmware data
134
134
1
RW 0x03 FW_Data_29
0x10
uint16
Firmware data
135
135
1
RW 0x03 FW_Data_30
0x10
uint16
Firmware data
136
136
1
RW 0x03 FW_Data_31
0x10
uint16
Firmware data
137
137
1
RW 0x03 FW_Data_32
0x10
uint16
Firmware data
138
138
1
R
uint16
Update status
0x03 FW_UpdateStatus
EN-US
1
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
117
End
Size
Start
117
see Firmware Update
71
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
214
1
R
215
215
1
uint16
RW 0x03 INV_Re0x06 set_All_Event_0x10 Flags
Write 0xFFFF to reset all 0xFFFF
event flags and active
state code.
230
230
1
RW 0x03 Reset_MBC
0x06
0x10
Restart of MBC. First
write 0x002A, then immediately 0x0006.
End
Size
Start
214
0x03 INV_Acuint16
tive_State_Cod
e
uint16
Current active state
code of inverter - Description can be found in
inverter manual
Inverter Status
Code
Register INV_Active_State_Code (214) displays the inverter status code which has just
been generated. This may also be displayed on the inverter's display. This code is also displayed as an event flag in registers 40110 to 40021. The displayed code remains active for
as long the inverter has the corresponding status. Alternatively, the status can also be deleted by using register INV_Reset_All_Event_Flags.
Deleting Event
Flags and Status
Codes
Event flags remain active for as long the inverter has the corresponding status. There are
a few exceptional cases in which the event flags are not deleted. For this reason, it is possible to reset the event flags and the displayed status code by issuing the Modbus command.
1
Enter 0xFFFF in register INV_Reset_All_Event_Flags (215)
The content of the following registers is deleted:
INV_Active_State_Code (214)
I_Event_1 (40110)
I_Event_2 (40112)
I_Event_1_Vendor (40114) to I_Event_4_Vendor (40120)
Restarting the
Modbus Card
You can use register Reset_MBC (230) to restart the Fronius Modbus Card without having
to disconnect the AC power supply.
1
Enter 0x002A ("*") into register Reset_MBC (230)
2
Within 10 seconds of that, enter 0x0006 ("ACK") into the same register
Shortly after that, the Fronius Modbus Card will restart. No data is lost in the process (e.g.,
inverter operating modes which have just been activated).
72
General
A firmware-update for the Fronius Modbus Card can be performed via the Modbus interface. Registers 100 to 138 have been specified for the firmware-update.
The new firmware is supplied as a binary file (bin) and is cyclically entered into the register
in blocks of up to 64 bytes during the update.
The following information is also required for the update
the checksum (CRC32) for the file
(does not have to be calculated separately but is supplied as part of the file name)
the size of the file in bytes
At www.fronius.com, Fronius offers a Microsoft Windows tool for the Firmware update.
The following components are required when using the update tool:
A converter to convert from RS485 to RS232 or from RS485 to USB
The corresponding update file (also available at www.fronius.com)
transmission time
The transmission time for firmware data is dependent on the selected baud rate and is approx. 1 minute at 19200 baud.
After this, approx. 15 seconds are required to write the new firmware to the microcontroller,
check it and perform a restart.
The Fronius Modbus Card is then ready for use again.
Transmission Security
As the Fronius Modbus Card initially buffers the received firmware data in its external flash
memory, it is not possible for faulty transmission to lead to functional failure of the card. In
the worst case, the data must be completely retransmitted.
CAUTION! Permanent malfunction of the Fronius Modbus Card possible.
Writing of the final data block from the external flash memory to the microcontroller must not be interrupted.
This critical phase only lasts a few milliseconds. In this period, the power supply
must not fail.
Transmission
Mode
The update cannot be performed as a broadcast. The Fronius Modbus Card replies to every write command. If the master receives a normal Modbus reply, this means that the data
have been processed correctly and the next write command can be performed.
Write commands must always be executed using function code 0x101).
If there are problems with the writing of data, exception code 4 is sent back. In this case,
the update must be restarted.
In the event of pauses longer than 30 seconds between the data blocks, the update is automatically aborted and must be restarted.
1)
Performing Firmware Updates
1
The prefix "0x" stands for hexadecimal numbers
Determine the size of the firmware file in bytes
73
EN-US
Firmware update
2
Enter the number of bytes into registers 102 and 103 (FW_Size)
Example: For 78080 bytes, 0x0001 is entered into register 102 and 0x3100 is entered into register 103
3
Wait for response
A normal Modbus response means that the data has been correctly entered and
the firmware data can now be sent.
A response with exception code 4 means
a problem writing to the registers or
the firmware file to be sent is too large or too small
In this case, the update process must be restarted from step 2
4
Enter data into registers 104 to 137
NOTE! A single command must be used to write registers 104 to 137
–
–
In register 104 (FW_BlockNumber), enter the number of the current data block
(starting with 0 for the first block)
In register 105 (FW_Bytes_in_Block), enter the number of bytes in the current
block
2
–
5
6
NOTE! The number of bytes in the final block may differ from the usual
64 bytes
Enter the firmware data in blocks of 64 bytes into registers 106 to 137 (FW_Data_01 to FW_Data_32)
Wait for response
A normal Modbus response means that the data has been correctly received and
buffered. The block number can then be increased by one.
A response with exception code 4 means
a problem writing to the registers or
the number of bytes in the block is not correct
In this case, the update process must be restarted from step 2
NOTE! If the master does not receive any response, e.g., because the transmission to the Fronius Modbus Card was faulty, the same block can be sent
again with the same number
Repeat steps 4 and 5 until all data blocks have been transmitted correctly
7
After receiving a correct response for the final data block, enter the CRC32 checksum
into registers 100 and 101 (FW_CRC32).
8
Wait for response
A normal Modbus response means that the checksum has been correctly written
and matches the checksum that was calculated by the Fronius Modbus Card via
the firmware data
A response with exception code 4 means
a problem writing to the registers or
the checksums do not match
In this case, the update process must be restarted from step 2
9
If the checksums match, the Fronius Modbus Card starts to write the new firmware into
the microcontroller and then performs a restart.
NOTE! The copying process and the restart take about 15 seconds. During
this time, the Fronius Modbus Card cannot be accessed via Modbus.
After a successful restart, the Fronius Modbus Card is ready for use again.
The update status can be requested via register 138 (FW_UpdateStatus). However, this
status is retained only until the Fronius Modbus Card is reset. Alternatively, the firmware
version can also be requested.
The possible values of register 138 (FW_UpdateStatus) are listed in the following table.
74
Description
0x0000
No update
0x0001
Update successful
0x0002
FW too great or too small
0x0003
Incorrect CRC
0x0004
General error
0x0005
FW is already up to date
0x0006
FW not suitable for device type
0x0007
Length of data block not correct
0x0008
Block number too high
0x0009
Block sequence incorrect
0x000A
No update process, but data received
0x000B
No update process, but CRC received
0x000C
Final block expected, but not received
0x000D
Incorrect copier CRC during writing
0x000E
Incorrect copier CRC after writing
0x000F
Incorrect version
0x0010
CRC not received in the correct order
0x0011
Incorrect CRC format
0x0012
Incorrect image size format
0x0013
Incorrect data block format
0x00FF
Update process
EN-US
Value
75
Setting the Baud Rate
General
The following settings are possible for the baud rate of the Fronius Modbus Card:
9600 baud (factory setting)
19200 baud
The following settings are possible for the parity of the Fronius Modbus Card:
even
odd
no parity (factory setting)
Setting Baud Rate
and/or Parity
A broadcast-message is normally used to set the baud rate and/or parity.
In this case, the settings are changed without a response from the Modbus participants
The new values must be confirmed within 30 seconds by sending the same messages
again with the new settings
If the settings are not confirmed, all the participating Fronius Modbus Cards will
revert to their original settings after 30 seconds
If the settings are confirmed, the new values will also be stored in the external
flash memory and will therefore also apply after the Fronius Modbus Card is restarted
In individual cases, it may also be necessary to change the baud rate and/or parity of a
Fronius Modbus Card.
In such a case, the response is sent back using the original baud rate/parity. Only then
are the settings changed.
The new values must be confirmed within 30 seconds by sending the same messages
again with the new settings
If the settings are not confirmed, the Fronius Modbus Card will revert to its original
settings after 30 seconds
If the settings are confirmed, the new values will also be stored in the external
flash memory and will therefore also apply after the Fronius Modbus Card is restarted
Example:
9600 Baud and no parity have been set
Change to 19200 Baud and even parity
1
Enter 19200 into register MBC_Baudrate
2
Enter 0 (for even parity) into register MBC_Parity
3
After receiving a correct response, switch to the new settings (19200, even) and reenter 19200 and 0
A normal response means that the settings have been applied.
76
Common & Inverter Model
Type
Units
Scale factor
0x03
C_SunSpec_ID
uint32
N/A
N/A
indicates that it is a valid Sun0x53756e53
Spec Modbus Map
40003 40003
1
RO
0x03
C_SunSpec_DID
uint16
N/A
N/A
indicates that it is a valid Sun0x0001
Spec Common Model block
40004 40004
1
RO
0x03
C_SunSpec_Length
uint16
Registers
40005 40020
16
RO
0x03
C_Manufacturer
String(32)
40021 40036
16
RO
0x03
C_Model
40037 40044
8
RO
0x03
40045 40052
8
RO
40053 40068
16
RO
40069 40069
Description
Value range
Function codes
RO
Name
R/W
2
End
40001 40002
Start
Size
EN-US
Common & Inverter Register
N/A Length of model
65
N/A
N/A Manufacturer name
"Fronius"
String(32)
N/A
N/A Inverter type
e.g.,
"IG+150 V"
C_Options
String(16)
N/A
N/A SW Version of Modbus Card
0x03
C_Version
String(16)
N/A
N/A Manufacturer-specific value
0x03
C_SerialNumber
String(32)
N/A
N/A Manufacturer-specific value
uint16
N/A
N/A Modbus ID
indicates that it is a valid SunSpec Inverter Modbus Map
N/A 101: single phase
101, 102, 103
102: split phase
103: three phase
0x03
1 R/W 0x06
0x10
C_DeviceAddress
40070 40070
1
RO
0x03
C_SunSpec_DID
uint16
N/A
40071 40071
1
RO
0x03
C_SunSpec_Length
uint16
Registers
N/A Length of model
40072 40072
1
RO
0x03
I_AC_Current
uint16
A
_SF Total AC current
40073 40073
1
RO
0x03
I_AC_CurrentA
uint16
A
_SF AC current phase A
40074 40074
1
RO
0x03
I_AC_CurrentB
uint16
A
_SF AC current phase B
40075 40075
1
RO
0x03
I_AC_CurrentC
uint16
A
_SF AC current phase C
40076 40076
1
RO
0x03
I_AC_Current_SF
int16
SF
40077 40077
1
RO
0x03
I_AC_VoltageAB
uint16
V
_SF AC voltage phase AB
40078 40078
1
RO
0x03
I_AC_VoltageBC
uint16
V
_SF AC voltage phase BC
40079 40079
1
RO
0x03
I_AC_VoltageCA
uint16
V
_SF AC voltage phase CA
40080 40080
1
RO
0x03
I_AC_VoltageAN
uint16
V
_SF
AC voltage phase A neutral
wire
40081 40081
1
RO
0x03
I_AC_VoltageBN
uint16
V
_SF
AC voltage phase B neutral
wire
40082 40082
1
RO
0x03
I_AC_VoltageCN
uint16
V
_SF
AC voltage phase C neutral
wire
40083 40083
1
RO
0x03
I_AC_Voltage_SF
int16
SF
N/A Scale factor AC voltage
40084 40084
1
RO
0x03
I_AC_Power
int16
W
_SF AC infeed power
40085 40085
1
RO
0x03
I_AC_Power_SF
int16
SF
N/A Scale factor AC infeed power
40086 40086
1
RO
0x03
I_AC_Frequency
uint16
Hz
_SF AC frequency
N/A Scale factor AC current
SW Version of
Inverter
50
-10 to +10
-10 to +10
-10 to +10
77
Type
Units
Scale factor
int16
SF
N/A Scale factor
40088 40088
1
RO
0x03
I_AC_VA
int16
VA
_SF Apparent power
40089 40089
1
RO
0x03
I_AC_VA_SF
int16
SF
N/A Scale factor
40090 40090
1
RO
0x03
I_AC_VAR
int16
Var
_SF Reactive power
40091 40091
1
RO
0x03
I_AC_VAR_SF
int16
SF
N/A Scale factor
40092 40092
1
RO
0x03
I_AC_PF
int16
%
_SF Power factor
40093 40093
1
RO
0x03
I_AC_PF_SF
int16
SF
N/A Scale factor
40094 40095
2
RO
0x03
I_AC_Energy_WH
uint32
Wh
_SF Total fed-in energy
40096 40096
1
RO
0x03
I_AC_Energy_WH_SF
int16
SF
N/A Scale factor
40097 40097
1
RO
0x03
I_DC_Current
uint16
A
_SF DC current
40098 40098
1
RO
0x03
I_DC_Current_SF
int16
SF
N/A Scale factor
40099 40099
1
RO
0x03
I_DC_Voltage
uint16
V
_SF DC voltage
40100 40100
1
RO
0x03
I_DC_Voltage_SF
int16
SF
N/A Scale factor
40101 40101
1
RO
0x03
I_DC_Power
int16
W
_SF DC power
40102 40102
1
RO
0x03
I_DC_Power_SF
int16
SF
N/A Scale factor
40103 40103
1
RO
0x03
I_Temp_Cab
int16
°C
_SF Housing temperature
40104 40104
1
RO
0x03
I_Temp_Sink
int16
°C
_SF Heat sink temperature
40105 40105
1
RO
0x03
I_Temp_Trans
int16
°C
_SF Transformer temperature
40106 40106
1
RO
0x03
I_Temp_Other
int16
°C
_SF Other temperature
40107 40107
1
RO
0x03
I_Temp_SF
int16
SF
N/A Scale factor
40108 40108
1
RO
0x03
I_Status
uint16
Enumerated
Name
78
Value
N/A Operating mode
Description
I_STATUS_OFF
1
Off
I_STATUS_SLEEPING
2
In operation (no feed-in)
I_STATUS_STARTING
3
Run-up phase
I_STATUS_MPPT
4
Normal operation
I_STATUS_THROTTLED
5
Power Reduction
I_STATUS_SHUTTING_DOWN
6
Switch-off phase
I_STATUS_FAULT
7
Error exists
I_STATUS_STANDBY
8
Standby
Value range
Function codes
I_AC_Frequency_SF
Description
R/W
0x03
Name
Size
RO
End
1
Start
40087 40087
-10 to +10
-10 to +10
-10 to +10
-10 to +10
-10 to +10
-10 to +10
-10 to +10
-10 to +10
-10 to +10
Name
Value
N/A
Value range
Enumerated
Description
uint16
EN-US
I_Status_Vendor
Scale factor
0x03
Units
Function codes
RO
Type
R/W
1
Name
Size
End
Start
40109 40109
Vendor Defined Operating
State
Description
I_STATUS_OFF
1
Off
I_STATUS_SLEEPING
2
In operation (no feed-in)
I_STATUS_STARTING
3
Run-up phase
I_STATUS_MPPT
4
Normal operation
I_STATUS_THROTTLED
5
Power Reduction
I_STATUS_SHUTTING_DOWN
6
Switch-off phase
I_STATUS_FAULT
7
Error exists
I_STATUS_STANDBY
8
Standby
I_STATUS_NO_BUSINIT
9
No Fronius Solar Net communication
I_STATUS_NO_COMM_INV
10
No communication with inverter
I_STATUS_SN_OVERCURRENT
11
Overcurrent identified in Fronius Solar Net plug
I_STATUS_BOOTLOAD
12
Inverter update is being performed
I_STATUS_AFCI
13
AFCI event
40110 40111
2
RO
0x03
I_Event_1
uint32
Bit field
N/A Event Flags (bits 0-31)
40112 40113
2
RO
0x03
I_Event_2
uint32
Bit field
N/A Event Flags (bits 32-63)
40114 40115
2
RO
0x03
I_Event_1_Vendor
uint32
Bit field
N/A
Vendor Defined Event Flags
(bits 0-31)
40116 40116
2
RO
0x03
I_Event_2_Vendor
uint32
Bit field
N/A
Vendor Defined Event Flags
(bits 32-63)
40118 40119
2
RO
0x03
I_Event_3_Vendor
uint32
Bit field
Vendor Defined Event Flags
N/A
(bits 64-95)
40120 40121
2
RO
0x03
I_Event_4_Vendor
uint32
Bit field
N/A
See "SunSpec
Event Flags"
See "Fronius
Event Flags"
Vendor Defined Event Flags
(bits 96-127)
79
Setting the Modbus Device ID
General
There are two options for setting the Modbus device ID of a Fronius Modbus Card:
using the two hexadecimal rotary switches on the Fronius Modbus Card
via Modbus using register 40069
NOTE! To ensure flawless operation, the Modbus device ID needs to be set to a
value between 1 and 247 (01 to F7 hex).
No Modbus device ID may be used more than once in the same Modbus system.
Setting the Modbus Device ID
1
In register 40069 (C_DeviceAddress), enter the new Modbus device ID
2
The response from the Fronius Modbus Card is still sent using the original Modbus device ID
A normal Modbus response means that the data has been correctly written and
the new Modbus device ID can now be used.
If an invalid ID has been assigned, a response is sent back with exception code
3. The ID remains unchanged.
NOTE! The new Modbus device ID is stored in the external flash memory and will
still be valid after a restart.
If a change is made to the setting wheels, the Modbus device ID which has been
set there will become effective though.
80
Nameplate model (IC120)
This model corresponds to a rating plate. The following data can be read:
DERType (40123)
type of device. The register returns the value 4 (PV device)
WRtg (40125)
Nominal power of inverter
VaRtg (40127)
Nominal apparent power of inverter
VArRtgQ1 (40129)-VArRtgQ4 (40132)
Nominal reactive power values for the four quadrants
ARtg (40134)
Nominal current of inverter
PFRtgQ1 (40136)–PFRtgQ4 (40139)
Minimal power factor values for the four quadrants
EN-US
General
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Nameplate Registers
40122 40122 1
R
0x03 ID
uint16
A well-known value 120. 120
Uniquely identifies this
as a SunSpec Nameplate Mode
40123 40123 1
R
0x03 L
uint16
40124 40124 1
R
0x03 DERTyp
enum16
40125 40125 1
R
0x03 WRtg
uint16
40126 40126 1
R
0x03 WRtg_SF
sunssf
40127 40127 1
R
0x03 VARtg
uint16
40128 40128 1
R
0x03 VARtg_SF
sunssf
40129 40129 1
R
0x03 VArRtgQ1
int16
var
VArRtg_SF
Continuous VAR capability of the inverter in
quadrant 1.
40130 40130 1
R
0x03 VArRtgQ2
int16
var
VArRtg_SF
Continuous VAR capability of the inverter in
quadrant 2.
Not supported
40131 40131 1
R
0x03 VArRtgQ3
int16
var
VArRtg_SF
Continuous VAR capability of the inverter in
quadrant 3.
Not supported
Registers
Length of Nameplate
Model
26
Type of DER device.
4
Default value is 4 to indicate PV device
W
WRtg_SF
Continuous power output capability of the inverter.
Scale factor
VA
VARtg_SF
0
Continuous volt-ampere capability of the inverter.
Scale factor
0
81
Range of values
0x03 VArRtgQ4
int16
40133 40133 1
R
0x03 VArRtg_SF
sunssf
40134 40134 1
R
0x03 ARtg
uint16
40135 40135 1
R
0x03 ARtg_SF
sunssf
40136 40136 1
R
0x03 PFRtgQ1
int16
cos()
PFRtg_SF
Minimum power factor
capability of the inverter
in quadrant 1.
40137 40137 1
R
0x03 PFRtgQ2
int16
cos()
PFRtg_SF
Minimum power factor
Not supportcapability of the inverter ed
in quadrant 2.
40138 40138 1
R
0x03 PFRtgQ3
int16
cos()
PFRtg_SF
Minimum power factor
Not supportcapability of the inverter ed
in quadrant 3.
40139 40139 1
R
0x03 PFRtgQ4
int16
cos()
PFRtg_SF
Minimum power factor
capability of the inverter
in quadrant 4.
40140 40140 1
R
0x03 PFRtg_SF
sunssf
40141 40141 1
R
0x03 WHRtg
uint16
40142 40142 1
R
0x03 WHRtg_SF
sunssf
40143 40143 1
R
0x03 AhrRtg
uint16
40144 40144 1
R
0x03 AhrRtg_SF
sunssf
40145 40145 1
R
0x03 MaxChaRte
uint16
40146 40146 1
R
0x03 MaxChaRte_SF
sunssf
40147 40147 1
R
0x03 MaxDisChaRte uint16
40148 40148 1
R
0x03 MaxDisChaRte_SF
40149 40149 1
R
0x03 Pad
82
VArRtg_SF
Description
R
sunssf
var
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40132 40132 1
Continuous VAR capability of the inverter in
quadrant 4.
Scale factor
A
ARtg_SF
Maximum RMS AC current level capability of
the inverter.
Scale factor
Scale factor
Wh
WHRtg_SF
AhrRtg_SF
Not supported
Not supported
MaxMaximum rate of energy Not supportChaRte transfer into the storage ed
_SF
device.
Scale factor
W
-3
The usable capacity of Not supportthe battery. Maximum ed
charge minus minimum
charge from a technology capability perspective (Amp-hour capacity
rating).
Scale factor for amphour rating.
W
-2
Nominal energy rating of Not supportstorage device.
ed
Scale factor
AH
1
Not supported
Maximum rate of energy Not supportMaxtransfer out of the stor- ed
DisChaRte age device.
_SF
Scale factor
Pad register
Not supported
Basic Settings Model (IC121)
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Basic Settings
Register
40150 40150 1
R
0x03 ID
uint16
A well-known value 121. 121
Uniquely identifies this
as a SunSpec basic settings model
40151 40151 1
R
0x03 L
uint16
Registers
40152 40152 1
R
0x03 WMax
uint16
W
VAMax- Setting for maximum
_SF
power output. Default to
WRtg.
40153 40153 1
RW 0x03 VRef
0x06
0x10
uint16
V
VAMax- Voltage at the PCC.
_SF
40154 40154 1
RW 0x03 VRefOfs
0x06
0x10
int16
V
VRefOfs_S
F
Offset from PCC to inverter.
40155 40155 1
RW 0x03 VMax
0x06
0x10
uint16
V
VMinMax_SF
Setpoint for maximum
voltage.
40156 40156 1
RW 0x03 VMin
0x06
0x10
uint16
V
VMinMax_SF
Setpoint for minimum
voltage.
40157 40157 1
R
0x03 VAMax
uint16
VA
VAMax- Setpoint for maximum
_SF
apparent power. Default
to VARtg.
40158 40158 1
R
0x03 VARMaxQ1
int16
var
VARMax_SF
Setting for maximum reactive power in quadrant
1. Default to VArRtgQ1.
40159 40159 1
R
0x03 VARMaxQ2
int16
var
VARMax_SF
Setting for maximum re- Not supportactive power in quadrant ed
2. Default to VArRtgQ2.
40160 40160 1
R
0x03 VARMaxQ3
int16
var
VARMax_SF
Setting for maximum re- Not supportactive power in quadrant ed
3 Default to VArRtgQ3.
40161 40161 1
R
0x03 VARMaxQ4
int16
var
VARMax_SF
Setting for maximum reactive power in quadrant
4 Default to VArRtgQ4.
40162 40162 1
R
0x03 WGra
uint16
%
WMax/
min
WGra_
SF
Default ramp rate of
change of active power
due to command or internal action.
Length of Basic Settings 30
Model
Not supported
83
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40163 40163 1
R
0x03 PFMinQ1
int16
cos()
PFMin_ Setpoint for minimum
SF
power factor value in
quadrant 1. Default to
PFRtgQ1.
40164 40164 1
R
0x03 PFMinQ2
int16
cos()
PFMin_ Setpoint for minimum
SF
power factor value in
quadrant 2. Default to
PFRtgQ2.
Not supported
40165 40165 1
R
0x03 PFMinQ3
int16
cos()
PFMin_ Setpoint for minimum
SF
power factor value in
quadrant 3. Default to
PFRtgQ3.
Not supported
40166 40166 1
R
0x03 PFMinQ4
int16
cos()
PFMin_ Setpoint for minimum
SF
power factor value in
quadrant 4. Default to
PFRtgQ4.
40167 40167 1
R
0x03 VArAct
enum16
VAR action on change Not supportbetween charging and
ed
discharging: 1=switch
2=maintain VAR characterization.
40168 40168 1
R
0x03 ClcTotVA
enum16
Calculation method for
total apparent power.
1=vector 2=arithmetic.
40169 40169 1
R
0x03 MaxRmpRte
uint16
%
WGra
MaxRmpRte_S
F
Setpoint for maximum
Not supportramp rate as percentage ed
of nominal maximum
ramp rate. This setting
will limit the rate that
watts delivery to the grid
can increase or decrease in response to intermittent PV
generation.
40170 40170 1
R
0x03 ECPNomHz
uint16
Hz
ECPNomHz_SF
Setpoint for nominal fre- Not supportquency at the ECP.
ed
40171 40171 1
R
0x03 ConnPh
enum16
Identity of connected
Not supportphase for single phase ed
inverters. A=1 B=2 C=3.
40172 40172 1
R
0x03 WMax_SF
sunssf
Scale factor for maximum power output.
0
40173 40173 1
R
0x03 VRef_SF
sunssf
Scale factor for voltage
at the PCC.
0
40174 40174 1
R
0x03 VRefOfs_SF
sunssf
Scale factor for offset
voltage.
0
40175 40175 1
R
0x03 VMinMax_SF
sunssf
Scale factor for min/max 0
voltages.
84
Not supported
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40176 40176 1
R
0x03 VAMax_SF
sunssf
Scale factor for voltage
at the PCC.
40177 40177 1
R
0x03 VARMax_SF
sunssf
Scale factor for reactive 1
power.
40178 40178 1
R
0x03 WGra_SF
sunssf
Scale factor for default
ramp rate.
Not supported
40179 40179 1
R
0x03 PFMin_SF
sunssf
Scale factor for minimum power factor.
-3
40180 40180 1
R
0x03 MaxRmpRte_SF
sunssf
Scale factor for maximum ramp percentage.
Not supported
40181 40181 1
R
0x03 ECPNomHz_SF
sunssf
Scale factor for nominal Not supportfrequency.
ed
Reference voltage
0
VRef (40153)
The reference voltage is the voltage at the point of common coupling where the local grid
is connected to the public grid. The reference voltage is the same as the inverter's nominal
voltage.
=> see figure "Point of common coupling"
During initial start-up, the Fronius Modbus Card automatically determines the reference
voltage from the voltage values of the inverter's individual phases.
This method is however inaccurate and fluctuations in the grid voltage or voltage deviations at the connection point may cause a VRef of 230 V in a 240 V grid.
It is therefore necessary to manually transfer the correct reference voltage to the Fronius
Modbus Card.
The value is given in volts in the range of 0x00 (0) to 0x190 (400)
This value is saved on the Fronius Modbus Card. The value will be deleted if the Fronius
Modbus Card is fitted in another inverter.
Example Settings
= Electrical Connection Point (ECP)
VRefOfs = 4V
VRefOfs = 2V
Utility Power System
Local Bus
VRefOfs = 3V
Local Power
System with
Line Resistors
Point of Common
Coupling (PCC)
VRef = 120V
DER interconnections
Point of common coupling
85
Deviation from
Reference Voltage
VRefOfs (40154)
Depending on the connection of the local grid, there may be a deviation from the reference
voltage at the point where each individual inverter is connected to the local grid (see figure
"Point of common coupling").
If this deviation is known, it should be specified. When using operating modes "Volt-Watt"
and "Volt'VAr", the voltage values of the Fronius Modbus Card are then adjusted accordingly.
The value is given in volts in the range of 0xFFEC (-20) to 0x14 (20). That corresponds to
a possible deviation of -20 V to +20 V.
Switch-off Limits
86
VMax (40155) and VMin (40156)
These two registers can be used to change the inverter's switch-off limits.
During initial start-up, the inverter's original values will be automatically saved by the Fronius Modbus Card as a reference. These values represent the maximum and minimum limits.
When inserting the Fronius Modbus Card into another inverter, these values will be deleted
and automatically re-read by the new inverter.
Extended Measurements & Status Model (IC122)
40182 40182 1
R
0x03 ID
uint16
40183 40183 1
R
0x03 L
uint16
40184 40184 1
R
0x03 PVConn
40185 40185 1
R
40186 40186 1
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Extended Measurements & Status Register
A well-known value 122. 122
Uniquely identifies this
as a SunSpec Measurements_Status Model
Registers
Length of Measurements_Status Model
44
bitfield16
PV inverter present/
available status. Enumerated value.
Bit 0: Connected
Bit 1: Available
Bit 2: Operating
Bit 3: Test
0x03 StorConn
bitfield16
Storage inverter present/available status.
Enumerated value.
Not supported
R
0x03 ECPConn
bitfield16
ECP connection status: 0: Discondisconnected=0 connected
nected=1.
1: Connected
40187 40190 4
R
0x03 ActWh
acc64
Wh
AC lifetime active (real)
energy output.
40191 40194 4
R
0x03 ActVAh
acc64
VAh
AC lifetime apparent en- Not supportergy output.
ed
40195 40198 4
R
0x03 ActVArhQ1
acc64
varh
AC lifetime reactive energy output in quadrant
1.
Not supported
40199 40202 4
R
0x03 ActVArhQ2
acc64
varh
AC lifetime reactive energy output in quadrant
2.
Not supported
40203 40206 4
R
0x03 ActVArhQ3
acc64
varh
AC lifetime negative en- Not supportergy output in quadrant ed
3.
40207 40210 4
R
0x03 ActVArhQ4
acc64
varh
AC lifetime reactive energy output in quadrant
4.
Not supported
40211 40211 1
R
0x03 VArAval
int16
var
Amount of VARs available without impacting
watts output.
Not supported
40212 40212 1
R
0x03 VArAval_SF
sunssf
VArAval_SF
Scale factor for available Not supportVARs.
ed
87
Range of values
Description
R
0x03 WAval
uint16
40214 40214 1
R
0x03 WAval_SF
sunssf
Scale factor for available Not supportwatts.
ed
40215 40216 2
R
0x03 StSetLimMsk
bitfield32
Bit Mask indicating setpoint limit(s) reached.
Bits are persistent and
must be cleared by the
controller.
Not supported
40217 40218 2
R
0x03 StActCtl
bitfield32
Bit Mask indicating
which inverter controls
are currently active.
Bit 0:
FixedW
Bit 1: FixedVAR
Bit 2: FixedPF
Bit 3: VoltVar
Bit 9: WattPF
Bit 10: VoltWatt
40219 40222 4
R
0x03 TmSrc
String (8)
Source of time synchro- RTC
nization.
40223 40224 2
RW 0x03 Tms
0x06
0x10
uint32
40225 40225 1
R
0x03 RtSt
bitfield16
40226 40226 1
R
0x03 Ris
uint16
40227 40227 1
R
0x03 Ris_SF
int16
88
W
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40213 40213 1
Secs
WAval_ Amount of watts availSF
able.
Not supported
Seconds since 01-012000 00:00 UTC
Bit Mask indicating
0
which voltage ride
through modes are currently active.
Ohm
Ris_SF Isolation resistance
Scale factor for isolation
resistance
This model provides some additional measurement and status values which do not cover
the normal inverter model:
-
PVConn (40184)
This bit field displays the inverter's status
Bit 0: Connected
Bit 1: Responsive
Bit 2: Operating (inverter feeds energy in)
-
ECPConn (40186)
This register displays the status of connection to the grid
ECPConn = 1: Inverter is currently feeding power into the grid
ECPConn = 0: Inverter is not feeding power into the grid
-
ActWH (40187–40190)
active energy meter
-
StActCtl (40217–40218)
Bit field for currently active inverter modes
Bit 0: Power Reduction
Bit 1: specification of constant reactive power
Bit 2: specification of a constant power factor
Bit 3: Volt-VAr characteristic curve
Bit 9: Watt-PF characteristic curve
Bit 10: Volt-Watt characteristic curve
-
TmSrc (40219–40222)
Source for the time synchronization. The register returns the string "RTC". A RTC on
the Fronius Modbus Card provides the inverter with the time and date.
-
Tms (40223–40224)
Current time and date of the RTC
The seconds are given from January 1, 2000, 00:00 (UTC) to the current time
NOTE! The date and time can however also be set using registers 23 to 28,
which have been specially defined by Fronius.
-
Ris (40226)
Insulation resistance
EN-US
General
89
Immediate Control Model (IC123)
General
The immediate controls can be used to make the following settings on the inverter:
deactivation of inverter's grid power feed operation (standby)
constant reduction of output power
specification of a constant power factor
specification of a constant relative reactive power
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Immediate Controls Register
40228 40228 1
R
0x03 ID
uint16
40229 40229 1
R
0x03 L
uint16
Registers
Length of immediate
controls model
40230 40230 1
RW 0x03 Conn_WinTms
0x06
0x10
uint16
Secs
Time window for connect/disconnect.
40231 40231 1
RW 0x03 Conn_RvrtTms uint16
0x06
0x10
Secs
Timeout period for connect/disconnect.
40232 40232 1
RW 0x03 Conn
0x06
0x10
bitfield16
40233 40233 1
RW 0x03 WMaxLimPct
0x06
0x10
uint16
%
WMax
40234 40234 1
RW 0x03 WMax0x06 LimPct_Win0x10 Tms
uint16
Secs
Time window for power
limit change.
40235 40235 1
RW 0x03 WMax0x06 LimPct_RvrtT0x10 ms
uint16
Secs
Timeout period for pow- 0 – 28800
er limit.
40236 40236 1
R
uint16
Secs
Ramp time for moving
from current setpoint to
new setpoint.
0 or 30 –
600
40237 40237 1
RW 0x03 WMaxLim_Ena enum16
0x06
0x10
Enumerated value.
Throttle enable/disable
control.
0: Disabled
1: Enabled
40238 40238 1
RW 0x03 OutPFSet
0x06
0x10
90
0x03 WMaxLimPct_RmpT
ms
int16
A well-known value 123. 123
Uniquely identifies this
as a SunSpec immediate controls model
Enumerated value.
Connection control.
cos()
24
0: Disconnected
1: Connected
WMax- Set power output to
LimPct_ specified level.
SF
OutPF- Set power factor to speSet_SF cific value - cosine of angle.
0 – 300
Range of values
Description
RW 0x03 OutPF0x06 Set_RvrtTms
0x10
uint16
Secs
Timeout period for pow- 0 – 28800
er factor.
40241 40241 1
RW 0x03 OutPF0x06 Set_RmpTms
0x10
uint16
Secs
Ramp time for moving
from current setpoint to
new setpoint.
0 or 30 –
600
40242 40242 1
RW 0x03 OutPFSet_Ena enum16
0x06
0x10
Enumerated value.
Fixed power factor enable/disable control.
0: Disabled
1: Enabled
40243 40243 1
R
40244 40244 1
EN-US
Units
Scale factor
Type
Name
Function codes
40240 40240 1
R/W
Time window for power
factor change.
Size
Secs
End
RW 0x03 OutPFSet_Win- uint16
0x06 Tms
0x10
Start
40239 40239 1
0 – 300
int16
%
WMax
VArW- Reactive power in perMaxcent of WMax.
Pct_SF
RW 0x03 VArMaxPct
0x06
0x10
int16
% VArMax
VArPct
_SF
Reactive power in percent of VArMax.
40245 40245 1
R
int16
% VArAval
VArPct
_SF
Reactive power in percent of VArAval.
Not supported
40246 40246 1
RW 0x03 VArPct_Win0x06 Tms
0x10
uint16
Secs
Time window for VAR
limit change.
0 – 300
40247 40247 1
RW 0x03 VArPct_RvrtT0x06 ms
0x10
uint16
Secs
Timeout period for VAR 0 – 28800
limit.
40248 40248 1
RW 0x03 VArPct_RmpT
0x06 ms
0x10
uint16
Secs
Ramp time for moving
from current setpoint to
new setpoint.
40249 40249 1
R
0x03 VArPct_Mod
enum16
Enumerated value. VAR 2: VAR limit
limit mode.
as a % of
VArMax
40250 40250 1
RW 0x03 VArPct_Ena
0x06
0x10
enum16
Enumerated value.
Fixed VAR enable/disable control.
0: Disabled
1: Enabled
40251 40251 1
R
0x03 WMaxLimPct_SF
sunssf
Scale factor for power
output percent.
0
40252 40252 1
R
0x03 OutPFSet_SF
sunssf
Scale factor for power
factor.
-3
40253 40253 1
R
0x03 VArPct_SF
sunssf
Scale factor for reactive 0
power.
0x03 VArWMaxPct
0x03 VArAvalPct
Not supported
0 or 30 –
600
91
Standby
Conn_WinTms (40230) to Conn (40232)
These registers are used to control the standby mode (no grid power feed operation) of the
inverter.
Conn_WinTms (40230) and Conn_RvrtTms (40231)
These registers can be used to control the inverter's time response. => see section "Time
Response of the Supported Operating Modes".
0 is set as the default for all registers.
Conn (40232)
Register Conn indicates whether or not the inverter is currently feeding power into the grid
(0 = standby, 1 = grid power feed operation).
In order to switch the inverter to standby, enter the value 0 into this register.
In order to reactivate the inverter, enter the value 1 into this register.
NOTE! To find out whether or not the inverter is feeding power into the grid, you
can also use the ECPConn register and check the extended measurements and
status model.
Power Reduction
WMaxLimPct (40233) to WMaxLim_Ena (40237)
These registers can be used to set an output power reduction in the inverter.
WMaxLimPct (40233)
In register WMaxLimPct you can enter values between 0% and 100%. Depending on the
inverter's software version, values below 10 may force the inverter into standby (no grid
power feed operation).
The values limit the device's maximum possible output power and therefore may not necessarily affect the real-time power.
WMaxLimPct_WinTms (40234), WMaxLimPct_RvrtTms (40235) and WMaxLimPct_RmpTms (40236)
These registers can be used to control the time response for this operating mode. => see
section "Time Response of the Supported Operating Modes".
0 is set as the default for all registers.
WMaxLim_Ena (40237)
used to start and end this operating mode
Enter value 1 into register WMaxLim_Ena = start operating mode
Enter value 0 into register WMaxLim_Ena = end operating mode
NOTE! Proceed as follows to change values when an operating mode is active
(e.g., when setting a different power limit or return time):
enter the new value into the relevant register
restart the operating mode using register WMaxLim_Ena
92
1
Enter the value for the output power reduction in register WMaxLimPct
(e.g., 30 for 30%).
2
As an option, you can set the start and return time using registers WMaxLimPct_WinTms and WMaxLimPct_RvrtTms
3
As an option, you can set the transition time using register WMaxLimPct_RmpTms=>
see section "Time Response of the Supported Operating Modes"
4
Start the operating mode by entering 1 in register WMaxLim_Ena
Example:
Changing the Return Time When
Power Reduction
Has Been Activated
If the power reduction was originally started using WMaxLimPct_RvrtTms = 0, the operating mode must be manually deactivated.
Effects of Reactive Power Specifications on
Effective Power
The figure "Reactive Power and Power Factor" shows what effect the reactive power and
power factor (cos phi) settings have on effective power.
1
Set WMaxLimPct_RvrtTms to 30, for example
2
Apply the change by entering 1 in register WMaxLim_Ena
– The operating mode is automatically deactivated after 30 seconds.
Reactive Power and Power Factor
Legend:
W
Effective power
Wmax
Nominal power
VAr
Reactive power
VArmax
Nominal reactive power
VArrel
Relative reactive power (VAr/VArmax)
93
EN-US
Example:
Setting a Power
Reduction
Constant Power
Factor
OutPFSet (40238) to OutPFSet_Ena (40242)
These registers can be used to set a constant power factor in the inverter.
OutPFSet (40238)
In register OutPFSet it is possible to enter both positive and negative values for the
power factor.
The values must be scaled up by a factor of 1000
, e.g., power factor 0.95 = register value 950
The lowest possible values depend on the inverter type and can be found in the nameplate model
NOTE! The power factor value must be entered with the correct sign => see section "Sign Convention for the Power Factor"
positive for under-excited
negative for over-excited
Over-excited is set by default.
OutPFSet_WinTms (40239), OutPFSet_RvrtTms (40240) and OutPFSet_RmpTms
(40241)
These registers can be used to control the inverter's time response for this operating mode.
=> see section "Time Response of the Supported Operating Modes".
0 is set as the default for all registers.
OutPFSet_Ena (40242)
used to start and end this operating mode
Enter value 1 into register OutPFSet_Ena = start operating mode
Enter value 0 into register OutPFSet_Ena = end operating mode
NOTE! Proceed as follows to change values when an operating mode is active
(e.g., when setting a different power factor or return time):
enter the new value into the relevant register
restart the operating mode using register OutPFSet_Ena
Example:
Setting a Constant Power Factor
94
1
Enter the power factor value in register OutPFSet
(e.g., 950 for 0.95%)
2
As an option, you can set the start and return time using registers OutPFSet_WinTms
and OutPFSet_RvrtTms
3
As an option, you can set the transition time using register OutPFSet_RmpTms=> see
section "Time Response of the Supported Operating Modes"
4
Start the operating mode by entering 1 in register OutPFSet_Ena
VArMaxPct (40244) to VArPct_Ena (40250)
These registers can be used to set a constant value for the reactive power to be produced
by the inverter.
NOTE! In practical operation, the reactive power that is actually available is specified by the inverter's operating limits. For this reason, the reactive power specification can only be reached if enough effective power is fed into the grid.
If too little effective power is fed into the grid, the inverter will operate at its operating limit.
VArMaxPct (40244)
used to set a value for constant reactive power
The minimum and maximum limits depend on the type of inverter
VArPct_WinTms (40246), VArPct_RvrtTms (40247) and VArPct_RmpTms (40248)
These registers can be used to control the inverter's time response for this operating mode.
=> see section "Time Response of the Supported Operating Modes".
0 is set as the default for all registers.
VArPct_Mod (40249)
this register cannot be changed
it returns the (currently) supported operating mode
reactive power as a percentage of the maximum possible reactive power
VArPct_Ena (40250)
used to start and end this operating mode
Enter value 1 into register VArPct_Ena = start operating mode
Enter value 0 into register VArPct_Ena = end operating mode
NOTE! Proceed as follows to change values when an operating mode is active
(e.g., when setting a different reactive power value or return time):
enter the new value into the relevant register
restart the operating mode using register VArPct_Ena
Example:
Setting Constant
Reactive Power
1
Enter the relative reactive power value in register VArMaxPct
(e.g., 80 for 80%).
2
As an option, you can set the start and return time using registers VArPct_WinTms
and VArPct_RvrtTms
3
As an option, you can set the transition time using register VArPct_RmpTms
=> see section "Time Response of the Supported Operating Modes"
4
Start the operating mode by entering 1 in register VArPct_Ena
95
EN-US
Constant Relative
Reactive Power
Volt-VAr Arrays (IC126)
General
The Volt-VAr characteristic curve influences the inverter's relative reactive power (VAr) in
accordance with the locally measured grid voltage (V).
Fronius Modbus Card supports 4 characteristic curves, which each have 4 points.
Reactive power changes can also be defined by time (VAr per minute) in order to avoid
erratic changes between various operating states.
VAr/VArmax
[%]
+ 100
60%
80
90
100
93
-60%
107 110
120
V/VRef
[%]
The figure shows an example of a characteristic curve for the operating mode VoltVAr.
In this example, no reactive power
exchange takes place within a range of
+/- 7% of the nominal voltage.
Outside of this range, the relative reactive power (VAr/VArmax) changes in
proportion to the voltage until its value
reaches 60% at +/-10% of the nominal
voltage.
Within the voltage range of +/-10% and
the switch-off limits (-20% or +15% of
the nominal voltage), the reactive power value remains on the last grid point.
- 100
NOTE! In practical operation, the reactive power that is actually available is specified by the inverter's operating limits. For this reason, the reactive power specification taken from the Volt-VAr characteristic curve can only be reached if enough
effective power is fed into the grid.
If too little effective power is fed into the grid, the inverter will operate at its operating limit.
Managing Characteristic Curves
ActCrv (40256) to RvrtTms (40259)
These registers can be used to manage characteristic curves.
ActCrv (40256)
This register is used to select the active Volt-VAr characteristic curve. That is the characteristic curve which is communicated to the inverter when the operating mode is activated.
Valid values are 0 (no characteristic curve) until 4.
NOTE! A characteristic curve must first be selected in order to start the Volt-VAr
operating mode.
ModEna (40257)
Used to start and end this operating mode
Enter value 1 into register ModEna = start operating mode
Enter value 0 into register ModEna = end operating mode
NOTE! Proceed as follows to change values when an operating mode is active
(e.g., when setting a different characteristic curve or return time):
enter the new value into the relevant register
restart the operating mode using register ModEna
96
Setting Characteristic Curves
EN-US
WinTms (40258) and RvrtTms (40259)
These registers can be used to control the time response of the inverter for this operating
mode. => see section "Time Response of the Supported Operating Modes".
0 is set as the default for all registers.
Use the following registers to set one of the 4 characteristic curves:
For characteristic curve 1
1_V1 (40268) to 1_VAr4 (40275)
1_RmpDecTmm (40317)
1_RmpIncTmm (40318)
For characteristic curve 2
2_V1 (40322) to 2_VAr4 (40329)
2_RmpDecTmm (40371)
2_RmpIncTmm (40372)
For characteristic curve 3
3_V1 (40376) to 3_VAr4 (40383)
3_RmpDecTmm (40425)
3_RmpIncTmm (40426)
For characteristic curve 4
4_V1 (40430) to 4_VAr4 (40437)
4_RmpDecTmm (40479)
4_RmpIncTmm (40480)
NOTE! There are 54 registers between each of the equivalent registers.
Only characteristic curve 1 is described here to represent all the other characteristic curves which can be set.
1_V1 (40268) to 1_VAr4 (40275)
1_V1, 1_V2, 1_V3 and 1_V4 = voltage values as a percentage of the reference voltage (VRef)
1_VAr1, 1_VAr2, 1_VAr3 and 1_VAr4 = reactive power values as a percentage of the
maximum reactive power (VArMax)
NOTE! Register 1_DeptRef (value =2) is used to specify that the reactive power
should be specified as a percentage of the maximum reactive power. This register
is write-protected.
1_RmpDecTmm (40317) and 1_RmpIncTmm (40318)
These registers define how fast the inverter adjusts the reactive power as the voltage
changes (reactive power change rate).
The value is specified as a percentage of the maximum reactive power per minute
1_RmpDec_Tmm to reduce the reactive power
1_RmpInc_Tmm to increase the reactive power
NOTE! The same value must be entered into both registers because the inverter
always uses the same value for increases and reductions in this operating mode.
97
Example
This example covers the following steps:
Change the points of characteristic curve 1 (according to the values in the figure)
Set the reactive power change rate for characteristic curve 1 to
50-times the maximum reactive power per minute (5000% VArmax/min)
VAr/VArmax
[%]
+ 100
1
Enter the voltage values [% of VRef]
into the following registers:
1_V1 (40268) = 90
1_V2 (40270) = 93
1_V3 (40272) = 107
1_V4 (40274) = 110
2
Enter the reactive power values [% of
VArmax] into the following registers:
1_VAr1 (40269) = 60
1_VAr2 (40271) = 0
1_VAr3 (40273) = 0
1_VAr4 (40275) = -60
60%
80
90
100
107 110
120
V/VRef
[%]
93
-60%
- 100
3
Enter the change rate values into the following registers:
1_RmpDecTmm (40317) = 5000
1_RmpIncTmm (40318) = 5000
4
As an option, you can set the start and return time using registers WinTms (40258)
and RvrtTms (40259)
5
Select characteristic curve 1 by entering 1 into register ActCrv (40256)
6
Start the operating mode by entering 1 into register ModEna (40257)
40254 40254 1
R
0x03 ID
uint16
40255 40255 1
R
0x03 L
uint16
40256 40256 1
RW 0x03 ActCrv
0x06
0x10
40257 40257 1
40258 40258 1
98
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Volt-VAr Arrays
Register
A well-known value 126. 126
Uniquely identifies this
as a SunSpec Static
Volt-VAR Model
Registers
Length of Volt-VAR
Model
226
uint16
Index of active curve.
0=no active curve.
0-4
RW 0x03 ModEna
0x06
0x10
bitfield16
Is Volt-VAR control active.
0: Disabled
1: Enabled
RW 0x03 WinTms
0x06
0x10
uint16
Time window for voltVAR change.
0 – 300
Secs
Range of values
Description
40260 40260 1
R
0x03 RmpTms
uint16
Secs
The time of the PT1 in
Not supportseconds (time to accom- ed
plish a change of 95%).
40261 40261 1
R
0x03 NCrv
uint16
Number of curves supported.
4
40262 40262 1
R
0x03 NPt
uint16
Maximum number of
points in array.
4
40263 40263 1
R
0x03 V_SF
sunssf
Scale factor for percent
VRef.
0
40264 40264 1
R
0x03 DeptRef_SF
sunssf
Scale factor for dependent variable.
0
40265 40265 1
R
0x03 RmpIncDec_SF sunssf
Scale factor for increment and decrement
ramps.
0
40266 40266 1
R
0x03 1_ActPt
uint16
Curve 1. Number of ac- 4
tive points in array.
40267 40267 1
R
0x03 1_DeptRef
enum16
Curve 1. Meaning of de- 2: % of VArpendent variable.
Max
40268 40268 1
RW 0x03 1_V1
0x06
0x10
uint16
% VRef V_SF
40269 40269 1
RW 0x03 1_VAr1
0x06
0x10
int16
% VArMax
40270 40270 1
RW 0x03 1_V2
0x06
0x10
uint16
% VRef V_SF
40271 40271 1
RW 0x03 1_VAr2
0x06
0x10
int16
% VArMax
40272 40272 1
RW 0x03 1_V3
0x06
0x10
uint16
% VRef V_SF
40273 40273 1
RW 0x03 1_VAr3
0x06
0x10
int16
% VArMax
40274 40274 1
RW 0x03 1_V4
0x06
0x10
uint16
% VRef V_SF
40275 40275 1
RW 0x03 1_VAr4
0x06
0x10
int16
% VArMax
40276 40276 1
R
uint16
% VRef V_SF
0x03 1_V5
EN-US
Units
Scale factor
Type
Name
Function codes
Timeout period for voltVAR curve selection.
R/W
Secs
Size
uint16
End
RW 0x03 RvrtTms
0x06
0x10
Start
40259 40259 1
0 – 28800
Curve 1, Point 1 Volts.
DeptRe Curve 1, Point 1 VARs.
f_SF
Curve 1, Point 2 Volts.
DeptRe Curve 1, Point 2 VARs.
f_SF
Curve 1, Point 2 Volts.
DeptRe Curve 1, Point 3 VARs.
f_SF
Curve 1, Point 4 Volts.
DeptRe Curve 1, Point 4 VARs.
f_SF
Curve 1, Point 5 Volts.
Not supported
99
R
0x03 1_VAr5
int16
% VArMax
40278 40278 1
R
0x03 1_V6
uint16
% VRef V_SF
40279 40279 1
R
0x03 1_VAr6
int16
% VArMax
40280 40280 1
R
0x03 1_V7
uint16
% VRef V_SF
40281 40281 1
R
0x03 1_VAr7
int16
% VArMax
40282 40282 1
R
0x03 1_V8
uint16
% VRef V_SF
40283 40283 1
R
0x03 1_VAr8
int16
% VArMax
40284 40284 1
R
0x03 1_V9
uint16
% VRef V_SF
40285 40285 1
R
0x03 1_VAr9
int16
% VArMax
40286 40286 1
R
0x03 1_V10
uint16
% VRef V_SF
40287 40287 1
R
0x03 1_VAr10
int16
% VArMax
40288 40288 1
R
0x03 1_V11
uint16
% VRef V_SF
40289 40289 1
R
0x03 1_VAr11
int16
% VArMax
40290 40290 1
R
0x03 1_V12
uint16
% VRef V_SF
40291 40291 1
R
0x03 1_VAr12
int16
% VArMax
40292 40292 1
R
0x03 1_V13
uint16
% VRef V_SF
40293 40293 1
R
0x03 1_VAr13
int16
% VArMax
40294 40294 1
R
0x03 1_V14
uint16
% VRef V_SF
40295 40295 1
R
0x03 1_VAr14
int16
% VArMax
40296 40296 1
R
0x03 1_V15
uint16
% VRef V_SF
40297 40297 1
R
0x03 1_VAr15
int16
% VArMax
40298 40298 1
R
0x03 1_V16
uint16
% VRef V_SF
40299 40299 1
R
0x03 1_VAr16
int16
% VArMax
100
DeptRe Curve 1, Point 5 VARs.
f_SF
Curve 1, Point 6 Volts.
DeptRe Curve 1, Point 6 VARs.
f_SF
Curve 1, Point 7 Volts.
DeptRe Curve 1, Point 7 VARs.
f_SF
Curve 1, Point 8 Volts.
DeptRe Curve 1, Point 8 VARs.
f_SF
Curve 1, Point 9 Volts.
DeptRe Curve 1, Point 9 VARs.
f_SF
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40277 40277 1
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Curve 1, Point 10 Volts. Not supported
DeptRe Curve 1, Point 10 VARs. Not supportf_SF
ed
Curve 1, Point 11 Volts. Not supported
DeptRe Curve 1, Point 11 VARs. Not supportf_SF
ed
Curve 1, Point 12 Volts. Not supported
DeptRe Curve 1, Point 12 VARs. Not supportf_SF
ed
Curve 1, Point 13 Volts. Not supported
DeptRe Curve 1, Point 13 VARs. Not supportf_SF
ed
Curve 1, Point 14 Volts. Not supported
DeptRe Curve 1, Point 14 VARs. Not supportf_SF
ed
Curve 1, Point 15 Volts. Not supported
DeptRe Curve 1, Point 15 VARs. Not supportf_SF
ed
Curve 1, Point 16 Volts. Not supported
DeptRe Curve 1, Point 16 VARs. Not supportf_SF
ed
R
0x03 1_V17
uint16
% VRef V_SF
40301 40301 1
R
0x03 1_VAr17
int16
% VArMax
40302 40302 1
R
0x03 1_V18
uint16
% VRef V_SF
40303 40303 1
R
0x03 1_VAr18
int16
% VArMax
40304 40304 1
R
0x03 1_V19
uint16
% VRef V_SF
40305 40305 1
R
0x03 1_VAr19
int16
% VArMax
40306 40306 1
R
0x03 1_V20
uint16
% VRef V_SF
40307 40307 1
R
0x03 1_VAr20
int16
% VArMax
40308 40315 8
R
0x03 1_CrvNam
String
(16)
40316 40316 1
R
0x03 1_RmpTms
uint16
Secs
40317 40317 1
RW 0x03 1_RmpDecT0x06 mm
0x10
uint16
% VArMax /
min
RmpCurve 1. The maximum 60-12000
Incrate at which the VAR
0: as fast as
Dec_SF value may be reduced in possible
response to changes in
the voltage value.
40318 40318 1
RW 0x03 1_RmpIncTmm uint16
0x06
0x10
% VArMax /
min
RmpCurve 1. The maximum 60-12000
Incrate at which the VAR
0: as fast as
Dec_SF value may be increased possible
in response to changes
in the voltage value.
40319 40319 1
R
0x03 1_ReadOnly
enum16
Curve 1, Point 17 Volts. Not supported
DeptRe Curve 1, Point 17 VARs. Not supportf_SF
ed
Curve 1, Point 18 Volts. Not supported
DeptRe Curve 1, Point 18 VARs. Not supportf_SF
ed
Curve 1, Point 19 Volts. Not supported
DeptRe Curve 1, Point 19 VARs. Not supportf_SF
ed
Curve 1, Point 20 Volts. Not supported
DeptRe Curve 1, Point 20 VARs. Not supportf_SF
ed
Curve 1. Optional deNot supportscription for curve. (Max ed
16 chars)
Curve 1. The time of the Not supportPT1 in seconds (time to ed
accomplish a change of
95%).
Boolean flag indicates if 0: Readcurve is read-only or can Write
be modified.
1: ReadOnly
40320 40373 Values of curve 2
Register offset 54 to curve 1
Name with prefix "2_"
40374 40427 Values of curve 3
Register offset 108 to curve 1
Name with prefix "3_"
40428 40481 Values of curve 4
Register offset 162 to curve 1
Name with prefix "4_"
101
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40300 40300 1
Watt-PF Curve (IC131)
General
The Watt-PF characteristic curve influences the inverter's reactive power behavior using
the power factor (PF) in accordance with the effective power.
Fronius Modbus Card supports 4 characteristic curves, which each have 4 points.
Shift factor changes can also be defined by time in order to avoid erratic changes between
various operating states.
PF
0.9
Overexcited
20
40
80
60
100
1
46
-0.9
Underexcited
Managing Characteristic Curves
74
W/Wmax
[%]
The figure shows an example of a characteristic curve for the operating mode WattPF.
In this example, there is a reactive power exchange with a PF of 0.9 (overexcited) within a range of up to 40% of
the nominal effective power.
Above this range, the PF increases linearly.
No reactive power exchange takes place within a range of 46% and 74% of
the nominal effective power (deadband, PF = 1).
Above this range, the PF decreases linearly until it reaches a value of 0.9
(under-excited) at 80% of the nominal
effective power.
ActCrv (40484) to RvrtTms (40487)
These registers can be used to manage the characteristic curves.
ActCrv (40484)
This register is used to select the active Watt-PF characteristic curve. That is the characteristic curve which is communicated to the inverter when the operating mode is activated.
Valid values are 0 (no characteristic curve) until 4.
NOTE! A characteristic curve must first be selected in order to start the Watt-PF
operating mode.
ModEna (40485)
Used to start and end this operating mode
Enter value 1 into register ModEna = start operating mode
Enter value 0 into register ModEna = end operating mode
NOTE! Proceed as follows to change values when an operating mode is active
(e.g., when setting a different characteristic curve or return time):
enter the new value into the relevant register
restart the operating mode using register ModEna
WinTms (40486) and RvrtTms (40487)
These registers can be used to control the time response of the inverter for this operating
mode. => see section "Time Response of the Supported Operating Modes".
0 is set as the default for all registers.
102
Use the following registers to set one of the 4 characteristic curves:
For characteristic curve 1
1_W1 (40495) to 1_PF4 (40502)
1_RmpDecTmm (40544)
1_RmpIncTmm (40545)
For characteristic curve 2
2_W1 (40549) to 2_PF4 (40556)
2_RmpDecTmm (40598)
2_RmpIncTmm (40599)
For characteristic curve 3
3_W1 (40603) to 3_PF4 (40610)
3_RmpDecTmm (40652)
3_RmpIncTmm (40653)
For characteristic curve 4
4_W1 (40657) to 4_PF4 (40664)
4_RmpDecTmm (40706)
4_RmpIncTmm (40707)
EN-US
Setting Characteristic Curves
NOTE! There are 54 registers between each of the equivalent registers.
Only characteristic curve 1 is described here to represent all the other characteristic curves which can be set.
1_W1 (40495) to 1_PF4 (40502)
1_W1, 1_W2, 1_W3 and 1_W4 = power values as a percentage of the nominal power
1_PF1, 1_PF2, 1_PF3 and 1_PF4 = power factor values
NOTE! The power factor value must be entered with the correct sign => see section "Sign Convention for the Power Factor"
1_RmpDecTmm (40544) and 1_RmpIncTmm (40545)
These registers define how fast the inverter adjusts the reactive power as the power
changes (power factor change rate)
The value is specified as a percentage of the maximum power factor per minute
1_RmpDec_Tmm used to reduce the power factor
1_RmpInc_Tmm used to increase the power factor
NOTE! The same value must be entered into both registers because the inverter
always uses the same value for increases and reductions in this operating mode.
103
Example
This example covers the following steps:
Change the points of characteristic curve 1 (according to the values in the figure)
NOTE! The power factor value must be entered with the correct sign => see
section "Sign Convention for the Power Factor"
-
Set power factor change rate for characteristic curve 1 to
0.2 per minute
PF
1
Enter the power values [% of Wmax]
into the following registers:
1_W1 (40495) = 40
1_W2 (40497) = 46
1_W3 (40499) = 74
1_W4 (40501) = 80
2
Enter power factor values (multiplied
by a factor of 1000) into the following
registers:
1_PF1 (40496) = -900
1_PF2 (40498) = 1000
1_PF3 (40500) = 1000
1_PF4 (40502) = 900
0.9
Overexcited
20
40
80
60
100
1
W/Wmax
[%]
74
46
-0.9
Underexcited
3
Enter the change rate values into the following registers:
1_RmpDecTmm (40544) = 200
1_RmpIncTmm (40545) = 200
4
As an option, you can set the start and return time using registers WinTms (40486)
and RvrtTms (40487)
5
Select characteristic curve 1 by entering 1 into register ActCrv (40484)
6
Start the operating mode by entering 1 into register ModEna (40485)
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Watt-PF Curve
Register
40482 40482 1
R
0x03 ID
uint16
A well-known value 131. 131
Uniquely identifies this
as a SunSpec Watt-PF
Model
40483 40483 1
R
0x03 L
uint16
Length of Watt-PF Mod- 226
el
40484 40484 1
RW 0x03 ActCrv
0x06
0x10
uint16
Index of active curve.
0=no active curve.
40485 40485 1
RW 0x03 ModEna
0x06
0x10
bitfield16
Is watt-PF mode active. 0: Disabled
1: Enabled
104
0-4
Range of values
Description
40487 40487 1
RW 0x03 RvrtTms
0x06
0x10
uint16
Secs
Timeout period for watt- 0 – 28800
pf curve selection.
40488 40488 1
R
0x03 RmpTms
uint16
Secs
Ramp time for moving
from current mode to
new mode.
Not supported
40489 40489 1
R
0x03 NCrv
uint16
Number of curves supported.
4
40490 40490 1
R
0x03 NPt
uint16
40491 40491 1
R
0x03 W_SF
sunssf
Scale factor for percent
WMax.
0
40492 40492 1
R
0x03 PF_SF
sunssf
Scale factor for PF.
-3
40493 40493 1
R
0x03 RmpIncDec_SF sunssf
Scale factor for increment and decrement
ramps.
0
40494 40494 1
R
0x03 1_ActPt
Curve 1. Number of ac- 4
tive points in array.
40495 40495 1
RW 0x03 1_W1
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 1 Watts.
40496 40496 1
RW 0x03 1_PF1
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 1 PF.
40497 40497 1
RW 0x03 1_W2
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 2 Watts.
40498 40498 1
RW 0x03 1_PF2
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 2 PF.
40499 40499 1
RW 0x03 1_W3
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 3 Watts.
40500 40500 1
RW 0x03 1_PF3
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 3 PF.
40501 40501 1
RW 0x03 1_W4
0x06
0x10
int16
%
WMax
W_SF
Curve 1, Point 4 Watts.
40502 40502 1
RW 0x03 1_PF4
0x06
0x10
int16
Cos()
PF_SF
Curve 1, Point 4 PF.
40503 40503 1
R
int16
%
WMax
W_SF
Curve 1, Point 5 Watts.
0x03 1_W5
Registers
EN-US
Units
Scale factor
Type
Name
Function codes
Time window for watt-pf 0 – 300
change.
R/W
Secs
Size
uint16
End
RW 0x03 WinTms
0x06
0x10
Start
40486 40486 1
Max number of points in 4
array.
uint16
Not supported
105
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40504 40504 1
R
0x03 1_PF5
int16
Cos()
PF_SF
Curve 1, Point 5 PF.
Not supported
40505 40505 1
R
0x03 1_W6
int16
%
WMax
W_SF
Curve 1, Point 6 Watts.
Not supported
40506 40506 1
R
0x03 1_PF6
int16
Cos()
PF_SF
Curve 1, Point 6 PF.
Not supported
40507 40507 1
R
0x03 1_W7
int16
%
WMax
W_SF
Curve 1, Point 7 Watts.
Not supported
40508 40508 1
R
0x03 1_PF7
int16
Cos()
PF_SF
Curve 1, Point 7 PF.
Not supported
40509 40509 1
R
0x03 1_W8
int16
%
WMax
W_SF
Curve 1, Point 8 Watts.
Not supported
40510 40510 1
R
0x03 1_PF8
int16
Cos()
PF_SF
Curve 1, Point 8 PF.
Not supported
40511 40511 1
R
0x03 1_W9
int16
%
WMax
W_SF
Curve 1, Point 9 Watts.
Not supported
40512 40512 1
R
0x03 1_PF9
int16
Cos()
PF_SF
Curve 1, Point 9 PF.
Not supported
40513 40513 1
R
0x03 1_W10
int16
%
WMax
W_SF
Curve 1, Point 10 Watts. Not supported
40514 40514 1
R
0x03 1_PF10
int16
Cos()
PF_SF
40515 40515 1
R
0x03 1_W11
int16
%
WMax
W_SF
Curve 1, Point 11 Watts. Not supported
40516 40516 1
R
0x03 1_PF11
int16
Cos()
PF_SF
Curve 1, Point 1 1PF.
40517 40517 1
R
0x03 1_W12
int16
%
WMax
W_SF
Curve 1, Point 12 Watts. Not supported
40518 40518 1
R
0x03 1_PF12
int16
Cos()
PF_SF
Curve 1, Point 12 PF.
40519 40519 1
R
0x03 1_W13
int16
%
WMax
W_SF
Curve 1, Point 13 Watts. Not supported
40520 40520 1
R
0x03 1_PF13
int16
Cos()
PF_SF
Curve 1, Point 13 PF.
40521 40521 1
R
0x03 1_W14
int16
%
WMax
W_SF
Curve 1, Point 14 Watts. Not supported
40522 40522 1
R
0x03 1_PF14
int16
Cos()
PF_SF
Curve 1, Point 14 PF.
40523 40523 1
R
0x03 1_W15
int16
%
WMax
W_SF
Curve 1, Point 15 Watts. Not supported
40524 40524 1
R
0x03 1_PF15
int16
Cos()
PF_SF
Curve 1, Point 15 PF.
40525 40525 1
R
0x03 1_W16
int16
%
WMax
W_SF
Curve 1, Point 16 Watts. Not supported
40526 40526 1
R
0x03 1_PF16
int16
Cos()
PF_SF
Curve 1, Point 16 PF.
106
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
R
0x03 1_W17
int16
%
WMax
W_SF
Curve 1, Point 17 Watts. Not supported
40528 40528 1
R
0x03 1_PF17
int16
Cos()
PF_SF
Curve 1, Point 17 PF.
40529 40529 1
R
0x03 1_W18
int16
%
WMax
W_SF
Curve 1, Point 18 Watts. Not supported
40530 40530 1
R
0x03 1_PF18
int16
Cos()
PF_SF
Curve 1, Point 18 PF.
40531 40531 1
R
0x03 1_W19
int16
%
WMax
W_SF
Curve 1, Point 19 Watts. Not supported
40532 40532 1
R
0x03 1_PF19
int16
Cos()
PF_SF
Curve 1, Point 19 PF.
40533 40533 1
R
0x03 1_W20
int16
%
WMax
W_SF
Curve 1, Point 20 Watts. Not supported
40534 40534 1
R
0x03 1_PF20
int16
Cos()
PF_SF
Curve 1, Point 20 PF.
Not supported
40535 40542 8
R
0x03 1_CrvNam
String
(16)
Curve 1. Optional description for curve.
Not supported
40543 40543 1
R
0x03 1_RmpPT1Tms uint16
40544 40544 1
RW 0x03 1_RmpDecT0x06 mm
0x10
uint16
% PF/
min
RmpCurve 1. The maximum 1200-65535
Incrate at which the power 0: as fast as
Dec_SF factor may be reduced in possible
response to changes in
the power value.
40545 40545 1
RW 0x03 1_RmpIncTmm uint16
0x06
0x10
% PF/
min
RmpCurve 1. The maximum 1200-65535
Incrate at which the power 0: as fast as
Dec_SF factor may be increased possible
in response to changes
in the power value.
40546 40546 1
R
40547 40547 1
RW 0x03 1_Pad
0x06
0x10
0x03 1_ReadOnly
Secs
Not supported
Not supported
Not supported
Curve 1. The time of the Not supportPT1 in seconds (time to ed
accomplish a change of
95%).
enum16
Curve 1. Enumerated
value indicates if curve
is read-only or can be
modified.
pad
Curve 1. Pad register.
0: ReadWrite
1: ReadOnly
40548 40601 Values of curve 2
Register offset 54 to curve 1
Name with prefix "2_"
40601 40655 Values of curve 3
Register offset 108 to curve 1
Name with prefix "3_"
40655 40709 Values of curve 4
Register offset 162 to curve 1
Name with prefix "4_"
107
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40527 40527 1
Volt-Watt Curve (IC132)
General
The Volt-Watt characteristic curve influences the effective power feed-in operation in accordance with the locally measured voltage. To ensure static voltage stability, the effective
power decreases along a statically specified characteristic curve as the voltage is increased.
Fronius Modbus Card supports 4 characteristic curves, which each have 3 points.
Effective power changes can also be defined by time (as a percentage of the nominal effective power per minute) in order to avoid erratic changes between various operating
states.
110 (253 V)
(264.5 V) 115
100
ΔW = 33.3%
111 112
113
(259.9 V)
V/Vref
[%]
ΔU = 0.01∙Vref
≙ 2.3 V
0
ΔW/Wavail
[%]
ΔW/Wavail
= 33.3% per 0.01·Vref
14.5% per Volt
The characteristic curve shown in the example illustrates a linear reduction by 100%
of the effective power between 110%
(253 V) and 113% (259.9 V) of the nominal
voltage. This reduction relates to the effective power value at the time the lower voltage limit (253 V) was exceeded.
It corresponds to a gradient of 14.5% for
each volt of voltage change.
For the inverter, these specifications mean
that the effective power feed-in operation
within the range of 253 V and 259.9 V constantly follows the characteristic curve. If the
voltage falls back below 253 V, the operating mode is deactivated.
NOTE! This characteristic curve can only be activated and deactivated on the inverter if it is in standby mode.
The Fronius Modbus Card automatically activates and deactivates the standby
mode.
Managing Characteristic Curves
ActCrv (40712) to RvrtTms (40715)
These registers can be used to manage the characteristic curves.
ActCrv (40712)
This register is used to select the active Volt-Watt characteristic curve. That is the
characteristic curve which is communicated to the inverter when the operating mode
is activated.
Valid values are 0 (no characteristic curve) until 4.
NOTE! A characteristic curve must first be selected in order to start the Volt-Watt
operating mode.
ModEna (40713)
Used to start and end this operating mode
Enter value 1 into register ModEna = start operating mode
Enter value 0 into register ModEna = end operating mode
NOTE! Proceed as follows to change values when an operating mode is active
(e.g., when setting a different characteristic curve or return time):
enter the new value into the relevant register
restart the operating mode using register ModEna
108
Setting Characteristic Curves
EN-US
RvrtTms (40487)
This register can be used to control the time response of the inverter for this operating
mode. => see section "Time Response of the Supported Operating Modes".
0 is set as the default value.
Use the following registers to set one of the 4 characteristic curves:
For characteristic curve 1
1_V1 (40724) to 1_W3 (40729)
1_RmpDecTmm (40773)
1_RmpIncTmm (40774)
For characteristic curve 2
2_V1 (40778) to 2_W3 (40783)
2_RmpDecTmm (40827)
2_RmpIncTmm (40828)
For characteristic curve 3
3_V1 (40832) to 3_W3 (40837)
3_RmpDecTmm (40881)
3_RmpIncTmm (40882)
For characteristic curve 4
4_V1 (40886) to 4_W3 (40891)
4_RmpDecTmm (40935)
4_RmpIncTmm (40936)
NOTE! There are 54 registers between each of the equivalent registers.
Only characteristic curve 1 is described here to represent all the other characteristic curves which can be set.
1_V1 (40724) to 1_W3 (40729)
1_V1, 1_V2 and 1_V3 = voltage values in parts per thousand of the reference voltage
(VRef)
1_W1, 1_W2 and 1_W3 = power values as a percentage of the power that is actually
available
1_RmpDecTmm (40544) and 1_RmpIncTmm (40545)
These registers define how fast the inverter adjusts the output power as the voltage changes (output power change rate).
The value is specified as a percentage of the maximum output power per minute
1_RmpDec_Tmm used to reduce the output power
1_RmpInc_Tmm used to increase the output power
NOTE! The values for 1_W1 and 1_W2 must be set at 100.
109
Example
This example covers the following steps:
Change the points of characteristic curve 1 (according to the values in the figure)
Set the effective power change rate for characteristic curve 1 to
40-times the maximum output power per minute (4000% VArmax/min)
110 (253 V)
(264.5 V) 115
1
Enter the voltage values [% of V] into
the following registers:
1_V1 (40724) = 1080
1_V2 (40726) = 1100
1_V3 (40728) = 1130
2
Enter the reactive power values [% of
VArmax] into the following registers:
1_W1 (40725) = 100
1_W2 (40727) = 100
1_W3 (40729) = 0
100
ΔW = 33.3%
111 112
113
(259.9 V)
V/Vref
[%]
ΔU = 0.01∙Vref
≙ 2.3 V
0
ΔW/Wavail
[%]
ΔW/Wavail
= 33.3% per 0.01·Vref
14.5% per Volt
3
Enter the change rate values into the following registers:
1_RmpDecTmm (40773) = 4000
1_RmpIncTmm (40774) = 4000
4
As an option, you can set the return time using register RvrtTms (40715)
5
Select characteristic curve 1 by entering 1 into register ActCrv (40712)
6
Start the operating mode by entering 1 into register ModEna (40713)
40710 40710 1
R
0x03 ID
uint16
40711 40711 1
R
0x03 L
uint16
40712 40712 1
RW 0x03 ActCrv
0x06
0x10
40713 40713 1
40714 40714 1
110
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
Volt-Watt Curve
Register
A well-known value 132. 132
Uniquely identifies this
as a SunSpec Volt-Watt
Model
Length of Volt-Watt
Model.
226
uint16
Index of active curve.
0=no active curve.
0-4
RW 0x03 ModEna
0x06
0x10
bitfield16
Is Volt-Watt control active.
0: Disabled
1: Enabled
R
uint16
Time window for voltwatt change.
Not supported
0x03 WinTms
Registers
Secs
0 – 28800
40716 40716 1
R
0x03 RmpTms
uint16
Secs
Ramp time for moving
from current mode to
new mode.
Not supported
40717 40717 1
R
0x03 NCrv
uint16
Number of curves supported.
4
40718 40718 1
R
0x03 NPt
uint16
Number of points in array.
3
40719 40719 1
R
0x03 V_SF
sunssf
Scale factor for percent
VRef.
-1
40720 40720 1
R
0x03 DeptRef_SF
sunssf
Scale factor for percent
DeptRef.
0
40721 40721 1
R
0x03 RmpIncDec_SF sunssf
Scale factor for increment and decrement
ramps.
0
40722 40722 1
R
0x03 1_ActPt
uint16
Curve 1. Number of ac- 3
tive points in array.
40723 40723 1
R
0x03 1_DeptRef
enum16
40724 40724 1
RW 0x03 1_V1
0x06
0x10
uint16
% VRef V_SF
Curve 1, Point 1 Volts.
40725 40725 1
RW 0x03 1_W1
0x06
0x10
int16
%
WMax
Curve 1, Point 1 Watts.
40726 40726 1
RW 0x03 1_V2
0x06
0x10
uint16
% VRef V_SF
Curve 1, Point 2 Volts.
40727 40727 1
RW 0x03 1_W2
0x06
0x10
int16
%
WMax
Curve 1, Point 2 Watts.
40728 40728 1
RW 0x03 1_V3
0x06
0x10
uint16
% VRef V_SF
Curve 1, Point 3 Volts.
40729 40729 1
RW 0x03 1_W3
0x06
0x10
int16
%
WMax
Curve 1, Point 3 Watts.
40730 40730 1
R
0x03 1_V4
uint16
% VRef V_SF
Curve 1, Point 4 Volts.
Not supported
40731 40731 1
R
0x03 1_W4
int16
%
WMax
Curve 1, Point 4 Watts.
Not supported
40732 40732 1
R
0x03 1_V5
uint16
% VRef V_SF
Curve 1, Point 5 Volts.
Not supported
40733 40733 1
R
0x03 1_W5
int16
%
WMax
Curve 1, Point 5 Watts.
Not supported
DeptRe Curve 1. Meaning of de- 2: % of
f_SF
pendent variable.
Waval
W_SF
W_SF
W_SF
W_SF
W_SF
111
EN-US
Range of values
Description
Units
Scale factor
Type
Name
Function codes
Timeout period for voltwatt curve selection.
R/W
Secs
Size
uint16
End
RW 0x03 RvrtTms
0x06
0x10
Start
40715 40715 1
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40734 40734 1
R
0x03 1_V6
uint16
% VRef V_SF
Curve 1, Point 6 Volts.
Not supported
40735 40735 1
R
0x03 1_W6
int16
%
WMax
Curve 1, Point 6 Watts.
Not supported
40736 40736 1
R
0x03 1_V7
uint16
% VRef V_SF
Curve 1, Point 7 Volts.
Not supported
40737 40737 1
R
0x03 1_W7
int16
%
WMax
Curve 1, Point 7 Watts.
Not supported
40738 40738 1
R
0x03 1_V8
uint16
% VRef V_SF
Curve 1, Point 8 Volts.
Not supported
40739 40739 1
R
0x03 1_W8
int16
%
WMax
Curve 1, Point 8 Watts.
Not supported
40740 40740 1
R
0x03 1_V9
uint16
% VRef V_SF
Curve 1, Point 9 Volts.
Not supported
40741 40741 1
R
0x03 1_W9
int16
%
WMax
Curve 1, Point 9 Watts.
Not supported
40742 40742 1
R
0x03 1_V10
uint16
% VRef V_SF
Curve 1, Point 10 Volts. Not supported
40743 40743 1
R
0x03 1_W10
int16
%
WMax
W_SF
Curve 1, Point 10 Watts. Not supported
40744 40744 1
R
0x03 1_V11
uint16
% VRef V_SF
Curve 1, Point 11 Volts. Not supported
40745 40745 1
R
0x03 1_W11
int16
%
WMax
W_SF
Curve 1, Point 11 Watts. Not supported
40746 40746 1
R
0x03 1_V12
uint16
% VRef V_SF
Curve 1, Point 12 Volts. Not supported
40747 40747 1
R
0x03 1_W12
int16
%
WMax
W_SF
Curve 1, Point 12 Watts. Not supported
40748 40748 1
R
0x03 1_V13
uint16
% VRef V_SF
Curve 1, Point 13 Volts. Not supported
40749 40749 1
R
0x03 1_W13
int16
%
WMax
W_SF
Curve 1, Point 13 Watts. Not supported
40750 40750 1
R
0x03 1_V14
uint16
% VRef V_SF
Curve 1, Point 14 Volts. Not supported
40751 40751 1
R
0x03 1_W14
int16
%
WMax
W_SF
Curve 1, Point 14 Watts. Not supported
40752 40752 1
R
0x03 1_V15
uint16
% VRef V_SF
Curve 1, Point 15 Volts. Not supported
40753 40753 1
R
0x03 1_W15
int16
%
WMax
W_SF
Curve 1, Point 15 Watts. Not supported
40754 40754 1
R
0x03 1_V16
uint16
% VRef V_SF
Curve 1, Point 16 Volts. Not supported
40755 40755 1
R
0x03 1_W16
int16
%
WMax
W_SF
Curve 1, Point 16 Watts. Not supported
40756 40756 1
R
0x03 1_V17
uint16
% VRef V_SF
Curve 1, Point 17 Volts. Not supported
112
W_SF
W_SF
W_SF
W_SF
R
0x03 1_W17
int16
%
WMax
W_SF
Curve 1, Point 17 Watts. Not supported
40758 40758 1
R
0x03 1_V18
uint16
% VRef V_SF
Curve 1, Point 18 Volts. Not supported
40759 40759 1
R
0x03 1_W18
int16
%
WMax
W_SF
Curve 1, Point 18 Watts. Not supported
40760 40760 1
R
0x03 1_V19
uint16
% VRef V_SF
Curve 1, Point 19 Volts. Not supported
40761 40761 1
R
0x03 1_W19
int16
%
WMax
W_SF
Curve 1, Point 19 Watts. Not supported
40762 40762 1
R
0x03 1_V20
uint16
% VRef V_SF
Curve 1, Point 20 Volts. Not supported
40763 40763 1
R
0x03 1_W20
int16
%
WMax
Curve 1, Point 20 Watts. Not supported
40764 40771 8
R
0x03 1_CrvNam
String
(16)
40772 40772 1
R
0x03 1_RmpPt1Tms uint16
40773 40773 1
RW 0x03 1_RmpDecT0x06 mm
0x10
uint16
%
WMax/
min
RmpCurve 1. The maximum 60-12000
0: as fast as
Incrate at which the watt
Dec_SF value may be reduced in possible
response to changes in
the voltage value.
40774 40774 1
RW 0x03 1_RmpIncTmm uint16
0x06
0x10
%
WMax/
min
RmpCurve 1. The maximum 12-1200
Incrate at which the watt
0: as fast as
Dec_SF value may be increased possible
in response to changes
in the voltage value.
40775 40775 1
R
0x03 1_ReadOnly
W_SF
Curve 1. Optional description for curve.
Secs
Not supported
Curve 1. The time of the Not supportPT1 in seconds (time to ed
accomplish a change of
95%).
enum16
Curve 1. Enumerated
value indicates if curve
is read-only or can be
modified.
0: ReadWrite
1: ReadOnly
Identifies this as End
block
0xFFFF
Length of model block
0
40776 40829 Values of curve 2
Register offset 54 to curve 1
Name with prefix "2_"
40830 40883 Values of curve 3
Register offset 108 to curve 1
Name with prefix "3_"
40884 40937 Values of curve 4
Register offset 162 to curve 1
Name with prefix "4_"
40938 40938 1
R
0x03 ID
uint16
40939 40939 1
R
0x03 L
uint16
Registers
113
EN-US
Range of values
Description
Scale factor
Units
Type
Name
Function codes
R/W
Size
End
Start
40757 40757 1
Event Flags
SunSpec
Event Flags
Event
Event
Flags 1
Event
Flags 2
I_EVENT_GROUND_FAULT
0x00000001 0x00000000 Ground fault
I_EVENT_DC_OVER_VOLT
0x00000002 0x00000000 DC over voltage
I_EVENT_AC_DISCONNECT
0x00000004 0x00000000 AC disconnect open
I_EVENT_DC_DISCONNECT
0x00000008 0x00000000 DC disconnect open
I_EVENT_GRID_DISCONNECT
0x00000010 0x00000000 Grid shutdown
I_EVENT_CABINET_OPEN
0x00000020 0x00000000 Cabinet open
I_EVENT_MANUAL_SHUTDOWN
0x00000040 0x00000000 Manual shutdown
I_EVENT_OVER_TEMP
0x00000080 0x00000000 Over temperature
303, 304, 531, 561
I_EVENT_OVER_FREQUENCY
0x00000100 0x00000000 Frequency above limit
105, 115, 125, 135, 560
I_EVENT_UNDER_FREQUENCY
0x00000200 0x00000000 Frequency under limit
106, 116, 126, 136
I_EVENT_AC_OVER_VOLT
0x00000400 0x00000000 AC voltage above limit
102, 112, 122, 132
I_EVENT_AC_UNDER_VOLT
0x00000800 0x00000000 AC voltage under limit
103, 113, 123, 133
I_EVENT_BLOWN_STRING_FUSE
0x00001000 0x00000000 Blown string fuse
550, 551
I_EVENT_UNDER_TEMP
0x00002000 0x00000000 Under temperature
Status
Status Codes
Special
Status Codes
471, 472, 474, 475, 502
107, 117, 127, 137
I_EVENT_MEMORY_LOSS
Generic Memory or
0x00004000 0x00000000 Communication error
(internal)
402, 404, 405, 414, 416,
417, 419, 421, 425, 431,
451, 452, 453, 454, 460,
461, 464, 465, 466, 467,
504, 505, 506, 507, 508,
510, 511, 514, 516, 517,
541, 553, 558
I_EVENT_HW_TEST_FAILURE
0x00008000 0x00000000 Hardware test failure
401, 403, 406, 407, 457,
469, 515, 532, 533, 535,
555
104, 203, 204 *)
101, 201, 202 *)
*) both flags must be set
Fronius
Event Flags
Event
Event
Flags 1
I_EVENT_INSULATION_FAULT
0x00000001 0x00000000 0x00000000 0x00000000 474, 475, 502
I_EVENT_GRID_ERROR
0x00000002 0x00000000 0x00000000 0x00000000
I_EVENT_AC_OVERCURRENT
0x00000004 0x00000000 0x00000000 0x00000000 301
I_EVENT_DC_OVERCURRENT
0x00000008 0x00000000 0x00000000 0x00000000 302
I_EVENT_OVER_TEMP
0x00000010 0x00000000 0x00000000 0x00000000 303, 304
I_EVENT_POWER_LOW
0x00000020 0x00000000 0x00000000 0x00000000 306, 309
I_EVENT_DC_LOW
0x00000040 0x00000000 0x00000000 0x00000000 307, 310
I_EVENT_INTERMED_VOLT_HIGH
0x00000080 0x00000000 0x00000000 0x00000000 308
114
Event
Flags 2
Event
Flags 3
Event
Flags 4
Status Code
on Inverter
101, 104, 107, 117, 127, 137, 108,
109, 205, 206, 305
Event
Flags 1
Event
Flags 2
Event
Flags 3
Event
Flags 4
Status Code
on Inverter
I_EVENT_FREQUENCY_HIGH
0x00000100 0x00000000 0x00000000 0x00000000 105, 115, 125, 135, 203
I_EVENT_FREQUENCY_LOW
0x00000200 0x00000000 0x00000000 0x00000000 106, 116, 126, 136, 204
I_EVENT_AC_VOLTAGE_HIGH
0x00000400 0x00000000 0x00000000 0x00000000 102, 112, 122, 132, 201
I_EVENT_AC_VOLTAGE_LOW
0x00000800 0x00000000 0x00000000 0x00000000 103, 113, 123, 133, 202
I_EVENT_DIRECT_CURRENT
0x00001000 0x00000000 0x00000000 0x00000000 408
I_EVENT_RELAY_FAULT
0x00002000 0x00000000 0x00000000 0x00000000 207, 208, 457
I_EVENT_POWER_STAGE_FAULT
0x00004000 0x00000000 0x00000000 0x00000000
I_EVENT_CONTROL_FAULT
0x00008000 0x00000000 0x00000000 0x00000000 409, 413
I_EVENT_GRID_VOLT_REC
0x00010000 0x00000000 0x00000000 0x00000000 453
I_EVENT_GRID_FREQU_REC
0x00020000 0x00000000 0x00000000 0x00000000 454
I_EVENT_ENERGY_TRANSFER_FAULT
0x00040000 0x00000000 0x00000000 0x00000000 443
I_EVENT_REF_POWER_SOURCE_AC
0x00080000 0x00000000 0x00000000 0x00000000 455
I_EVENT_ANTI_ISLANDING_FAULT
0x00100000 0x00000000 0x00000000 0x00000000 456
I_EVENT_FIXED_VOLTAGE_FAULT
0x00200000 0x00000000 0x00000000 0x00000000 412
I_EVENT_EEPROM_FAULT
0x00400000 0x00000000 0x00000000 0x00000000
I_EVENT_DISPLAY_FAULT
0x00800000 0x00000000 0x00000000 0x00000000 464, 465, 466, 467
I_EVENT_COMMUNICATION_FAULT
0x01000000 0x00000000 0x00000000 0x00000000 401, 402, 416, 425, 452
I_EVENT_TEMP_SENSORS_FAULT
0x02000000 0x00000000 0x00000000 0x00000000 406, 407, 533
I_EVENT_DSP_FAULT
0x04000000 0x00000000 0x00000000 0x00000000 460, 461
I_EVENT_ENS_FAULT
0x08000000 0x00000000 0x00000000 0x00000000 405, 415
I_EVENT_FAN_FAULT
0x10000000 0x00000000 0x00000000 0x00000000
I_EVENT_DEFECTIVE_FUSE
0x20000000 0x00000000 0x00000000 0x00000000 471, 551
I_EVENT_OUTPUT_CHOKE_FAULT
0x40000000 0x00000000 0x00000000 0x00000000 469
I_EVENT_CONVERTER_RELAY_FAULT
0x80000000 0x00000000 0x00000000 0x00000000 470
I_EVENT_NO_SOLARNET_COMM
0x00000000 0x00000001 0x00000000 0x00000000 504
I_EVENT_INV_ADDRESS_FAULT
0x00000000 0x00000002 0x00000000 0x00000000 508
I_EVENT_NO_FEED_IN_24H
0x00000000 0x00000004 0x00000000 0x00000000 509
I_EVENT_PLUG_FAULT
0x00000000 0x00000008 0x00000000 0x00000000 410, 515
I_EVENT_PHASE_ALLOC_FAULT
0x00000000 0x00000010 0x00000000 0x00000000 473
I_EVENT_GRID_CONDUCTOR_OPEN
0x00000000 0x00000020 0x00000000 0x00000000 210
I_EVENT_FEATURE_DEACTIVATED
0x00000000 0x00000040 0x00000000 0x00000000 558
I_EVENT_CHANGE_OF_MASTER
0x00000000 0x00000080 0x00000000 0x00000000 517
I_EVENT_JUMPER_INCORRECT
0x00000000 0x00000100 0x00000000 0x00000000 550
I_EVENT_LOW_VOLT_RIDE_THROUGH
0x00000000 0x00000200 0x00000000 0x00000000 559
I_EVENT_VENTS_BLOCKED
0x00000000 0x00000400 0x00000000 0x00000000 501
I_EVENT_POWER_REDUCTION_ERROR
0x00000000 0x00000800 0x00000000 0x00000000 560, 561
I_EVENT_ARC_DETECTED
0x00000000 0x00001000 0x00000000 0x00000000 240
I_EVENT_AFCI_SELF_TEST_FAILED
0x00000000 0x00002000 0x00000000 0x00000000 245
I_EVENT_CURRENT_SENSOR_ERROR
0x00000000 0x00004000 0x00000000 0x00000000 247
I_EVENT_ENS_JUMPERS_WRONG
0x00000000 0x00008000 0x00000000 0x00000000 248
I_EVENT_AFCI_DEFECTIVE
0x00000000 0x00010000 0x00000000 0x00000000 249
EN-US
Event
417, 419, 421, 431, 439, 442, 445,
450, 512, 513, 514, 516, 553
403, 414, 451, 505, 506, 507, 510,
511
530, 531, 534, 535, 536, 537, 540,
541, 555, 557
115
Event
Event
Flags 1
I_EVENT_AFCI_MANUAL_TEST_OK
0x00000000 0x00020000 0x00000000 0x00000000 250
I_EVENT_AFCI_COMM_ERROR
0x00000000 0x00040000 0x00000000 0x00000000 476
I_EVENT_AFCI_NO_COMM
0x00000000 0x00080000 0x00000000 0x00000000 477
I_EVENT_AFCI_MANUAL_TEST_FAILED
0x00000000 0x00100000 0x00000000 0x00000000 478
116
Event
Flags 2
Event
Flags 3
Event
Flags 4
Status Code
on Inverter
117
EN-US
Fronius Worldwide - www.fronius.com/addresses
Fronius International GmbH
4600 Wels, Froniusplatz 1, Austria
E-Mail: [email protected]
http://www.fronius.com
Fronius USA LLC Solar Electronics Division
6797 Fronius Drive, Portage, IN 46368
E-Mail: [email protected]